iSW switch-disconnector 1P 40A...125A

Acti 9 Switch Disconnector iSW, 1P, 125A, 240V

Catalogue Number: A9S66192
iSW switch-disconnector 1P 40A...125A
Retail
$162.47
RRP (Inc. GST)

Specifications

hide show
Range of product
iSW 40...125
Range
Acti 9
Product name
Acti 9 iSW
Product or component type
switch disconnector
Device short name
iSW
Device application
  • control
  • isolation
    • Poles description
      1P
      Utilisation category
      AC-22A
      Suitability for isolation
      yes
      [Ie] rated operational current
      125 A at 240 V AC 50/60 Hz
      [Ue] rated operational voltage
      240 V AC 50/60 Hz
      [Icm] rated short-circuit making capacity
      5 kA switch-disconnector alone
      [Icw] rated short-time withstand current
      1500 A
      [Ui] rated insulation voltage
      250 V AC 50/60 Hz
      [Uimp] rated impulse withstand voltage
      6 kV
      Control type
      toggle
      Local signalling
      ON/OFF indication
      Contact position indicator
      yes
      Mounting mode
      fixed
      Mounting support
      DIN rail
      Comb busbar and distribution block compatibility
      top or bottom: YES
      Connection pitch
      9 mm pitches
      2
      Height
      85 mm
      Width
      18 mm
      Depth
      73 mm
      Mechanical durability
      20000 cycles
      Electrical durability
      2500 cycles
      Connections - terminals
    • tunnel type terminals (top or bottom) - <= 1 x 50 mm² - rigid
    • tunnel type terminals (top or bottom) - <= 1 x 35 mm² - flexible
    • tunnel type terminals (top or bottom) - <= 1 x 35 mm² - flexible with ferrule
      • Wire stripping length
        9 mm
        Tightening torque
        3.5 N.m
        Compatibility code
        iSW
        Standards
      • AS 60947-3
      • IEC 60947-3
      • EN 60947-3
      • NZS 60947-3
      • BS EN 60947-3
        • IP degree of protection
          IP20
          Pollution degree
          3
          Tropicalisation
          2
          Relative humidity
          95-95 % at 55-55 °C
          Ambient air temperature for operation
          -25-60 °C
          Ambient air temperature for storage
          -40-85 °C
          Unit Type of Package 1
          PCE
          Number of Units in Package 1
          1
          Package 1 Weight
          95 g
          Package 1 Height
          7.85 cm
          Package 1 width
          1.8 cm
          Package 1 Length
          9.2 cm
          Sustainable offer status
          Green Premium product
          REACh free of SVHC
          Yes
          EU RoHS Directive
          Compliant
          Toxic heavy metal free
          Yes
          Mercury free
          Yes
          RoHS exemption information
          Yes
          China RoHS Regulation
           Pro-active China RoHS declaration (out of China RoHS legal scope)
          Environmental Disclosure
          ENVPEP121216EN
          WEEE
          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
          Warranty
          18 months

          Documents & downloads

          hide show
          Filter items
          • All

          • Product Brochures

          • CAD Files and Packs

          • Technical Data Catalogues

          • Product Environmental

          • Declaration of Conformity

          Frequently Asked Questions

          hide show

          Is there a shunt trip that can be used in conjunction with a iSW series?

          No unfortunately the ISW series can't be used with shunt release.

          For further information please visit Global Specialist in Energy Management | Schneider Electric

          What is the new code for 15005?

          The new code is A9S60120

          Does the A9A26981 fit on the A9S66163?

          Yes, that is designed to fit on the Acti9 shaped devices including the iSW switches.

          Is A9A27006 suitable to use on A9S66463?

          Yes, A9A27006 is suitable to use on A9S66463

           

          What is the part code for a 3 pole din rail mount main switch

           What curent rating ?
          The part code is 3 pole 40amp mains Isolating switch is A9S66340 or Domae DCK12646 63amp 3 pole

          Java Cryptography Extension requirement for SNMPv3 configuration in PowerChute Network Shutdown and PowerChute Business Edition

          Issue:
          In certain geographies it is necessary to install the Java Cryptography Extension to use privacy protocols AES-192 or AES-256 in the PowerChute Network Shutdown and PowerChute Business Edition SNMPv3 configuration.
             
          Product Line:
          PowerChute Network Shutdown v4.2 or higher and PowerChute Business Edition v9.5


          Environment: 
          All
          supported operating systems

          Solution:

          Due to the import control restrictions of some countries, the version of the Java Cryptography Extension (JCE) policy files that are bundled with the Java Runtime Environment 8 (JRE 8) allow ‘strong’ but limited cryptography to be used; they have in-built restrictions on available cryptographic strength. Depending on your geographical location (e.g. outside of the United States), to use the privacy protocol AES-192 or AES-256 in PowerChute SNMPv3 configuration, it may be necessary to first download and install the Unlimited Strength Java™ Cryptography Extension (JCE) Policy Files available from the Oracle website (
          https://www.oracle.com/technetwork/java/javase/downloads/index.html).
          The Unlimited Strength JCE contains no restrictions on cryptographic strengths.
           
          NOTE: It is recommended to consult your export/import control counsel or legal counsel to determine the exact cryptographic strength required for your geographical jurisdiction.
           

          Steps for PowerChute Business Edition v9.5:

          Windows:
          1. Download and extract the Unlimited Strength Jurisdiction Policy Files available on the Oracle website.
          2. Navigate to the installed directory of PowerChute. If the default location was chosen during installation, this will be C:\Program Files\APC\PowerChute Business Edition or C:\Program Files (x86)\APC\PowerChute Business Edition depending on your operating system.
          3. Navigate to \jre1.8.0_144\lib\security and replace the existing Policy Files with the ones extracted in Step 1.
          Note: If you change the JRE used with PowerChute via the JRE Configuration Tool, the existing Policy Files will be in \JreConfigTool\<JRE>\lib\security\policy\unlimited. However, the Policy Files extracted in Step 1 must be copied to the \JreConfigTool\<JRE>\lib\security\ directory. For example: \JreConfigTool\1.8.0_152\lib\security.
          1. Restart the PCBE service.
           
          Linux:
          1. Download and extract the Unlimited Strength Jurisdiction Policy Files available on the Oracle website.
          2. Navigate to the installed directory of PowerChute. If the default location was chosen during installation, this will be /opt/APC/PowerChuteBusinessEdition.
          3. Navigate to \jre1.8.0_144\lib\security and replace the existing Policy Files with the ones extracted in Step 1.
          NOTE: If you change the JRE used with PowerChute via the JRE Configuration Tool, navigate to the installed directory of the JRE. For example, if the JRE is stored on your desktop, this will be /root/Desktop/<JRE> (e.g. /root/Desktop/jre1.8.0_152). The existing Policy Files will be in /<JRE>/lib/security/policy/unlimited. However, the Policy Files extracted in Step 1 must be copied to the /<JRE>/lib/security directory.
          1. Restart the PCBE service.
          NOTE: If you change the JRE used with PowerChute via the JRE Configuration Tool, an additional step must be performed after Step 3 to edit the java.security file in the security directory. See Knowledge Base article FA333166 on the APC website for more information.
           
          NOTE: This issue has been resolved in PowerChute Business Edition v10.x which is available to download on the APC website.
           

          Why can't I purchase Schneider Electric US Lighting Control products any more?

          Issue:
          As of March 1, 2015 all US Lighting Control products (EXCEPT Powerlink and MVP panels) will enter their obsolescence phase and will no longer be purchasable for new orders. Management of the Prosumer Business has made a strategic decision to stop the Lighting Control initiative and concentrate our effort in new businesses with higher growth potential – Connected Home, Building Control in small buildings, and Electric Vehicle solutions.

          Product Line:
          All US Lighting Control product except Powerlink and MVP panels are affected. CBus, Occupancy Sensors, Low Voltage Switches, Relay Panels, Emergency Lighting Control Panels, Schneider Electric branded Current Limiting Panels, and Architectural Dimming Panels.

          Environment:
          US Lighting Control products

          Cause:
          Management of the Prosumer Business has made a strategic decision to stop the Lighting Control initiatives.

          Resolution:
          See cross reference sheet attached for available completive cross references.