Acti 9 Miniature Circuit Breaker, C60H, 2 Poles, 16A, C Curve, 500V

Acti 9 Miniature Circuit Breaker, C60H, 2 Poles, 16A, C Curve, 500V

Acti 9 Miniature Circuit Breaker, C60H, 2 Poles, 16A, C Curve, 500V

Item Number: A9N61531

Retail
$207.98
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

C60

Range

Acti 9

Product or component type

miniature circuit-breaker

Device application

distribution

Product compatibility

  • C60 auxiliary
  • C60 accessories
    • Market segment

    • small commercial
    • residential
      • Sustainable offer status

        Green Premium product

        Warranty

        18 months

        Physical

        [In] rated current

        16 A at 25 °C

        [Ue] rated operational voltage

        500 V DC

        Control type

        toggle

        Local signalling

        ON/OFF indication

        Mounting mode

        fixed

        Mounting support

        35 mm symmetrical DIN rail

        Net weight

        0.256 kg

        Mechanical durability

        20000 cycles

        Electrical durability

        6000 cycles 500 V DC

        Standards

      • EN 60947-2
      • IEC 60947-2
        • Ambient air temperature for operation

          -25-70 °C

          Ambient air temperature for storage

          -40-85 °C

          REACh free of SVHC

          Yes

          EU RoHS Directive

          Compliant

          Toxic heavy metal free

          Yes

          Mercury free

          Yes

          RoHS exemption information

          Yes

          China RoHS Regulation

           Pro-active China RoHS declaration (out of China RoHS legal scope)

          Environmental Disclosure

          ENVPEP120608EN_V0

          Others

          Product name

          Acti 9 C60H-DC

          Device short name

          C60H-DC

          Poles description

          2P

          Number of protected poles

          2

          Network type

          DC

          Trip unit technology

          thermal-magnetic

          Curve code

          C

          Breaking capacity code

          H

          Breaking capacity

        • 10 kA Icu at 440 V DC conforming to EN 60947-2
        • 10 kA Icu at 440 V DC conforming to IEC 60947-2
        • 6 kA Icu at 500 V DC conforming to EN 60947-2
        • 6 kA Icu at 500 V DC conforming to IEC 60947-2
        • 20 kA Icu at 220 V DC conforming to GB 14048.2
        • 20 kA Icu at 220 V DC conforming to IEC 60947-2
        • 20 kA Icu at 250 V DC conforming to GB 14048.2
        • 20 kA Icu at 250 V DC conforming to IEC 60947-2
          • Utilisation category

          • category A conforming to EN 60947-2
          • category A conforming to IEC 60947-2
            • Suitability for isolation

            • yes conforming to IEC 60947-2
            • yes conforming to EN 60947-2
              • Network frequency

                50/60 Hz

                [Ics] rated service breaking capacity

              • 15 kA 75 % conforming to EN 60947-2 - 220 V DC
              • 15 kA 75 % conforming to IEC 60947-2 - 220 V DC
              • 15 kA 75 % conforming to EN 60947-2 - 250 V DC
              • 15 kA 75 % conforming to IEC 60947-2 - 250 V DC
              • 4.5 kA 75 % conforming to EN 60947-2 - 500 V DC
              • 4.5 kA 75 % conforming to IEC 60947-2 - 500 V DC
              • 7.5 kA 75 % conforming to EN 60947-2 - 440 V DC
              • 7.5 kA 75 % conforming to IEC 60947-2 - 440 V DC
                • [Ui] rated insulation voltage

                • 500 V DC conforming to IEC 60947-2
                • 500 V DC conforming to EN 60947-2
                  • [Uimp] rated impulse withstand voltage

                  • 6 kV conforming to EN 60947-2
                  • 6 kV conforming to IEC 60947-2
                    • Contact position indicator

                      yes

                      Comb busbar and distribution block compatibility

                      top or bottom: standard

                      9 mm pitches

                      4

                      Provision for padlocking

                      padlockable

                      Locking options description

                      in position O

                      Tightening torque

                      power circuit: 2.5-2.5 N.m top or bottom

                      Earth-leakage protection

                      without

                      Compatibility code

                      C60H-DC

                      Pollution degree

                    • 3 conforming to EN 60947-2
                    • 3 conforming to IEC 60947-2
                      • Overvoltage category

                        IV

                        Tropicalisation

                        2 conforming to IEC 60068-2

                        Operating altitude

                        2000 m

                        Package 1 Weight

                        228 g

                        Package 1 Height

                        0.75 dm

                        Package 1 width

                        0.36 dm

                        Package 1 Length

                        0.85 dm
                        Show all specifications

                        Documents & downloads

                        hide show

                        Frequently Asked Questions

                        hide show

                        What is the part number of a 2 pole, 50A, 6KA, C curve DC circuit breaker?

                        A9N61538 is the part number of a 2 pole, 50A, 6KA, C curve C60H DC circuit breaker.
                        For further information, please visit https://www.schneider-electric.co.uk/en/product/A9N61538/miniature-circuit-breaker---c60h---2-poles---50-a---c-curve/
                        Schneider Eletric A9N61538 Picture
                         

                        What is the part code for SW60DC breaker for 275V dc 16Amp 2P

                         The part code is MGN61531

                        What is the part code for a Fuse Carrier STI, 1 pole.?

                         The Multi9 part code is 15636
                        The Acti9 part code is A9N15636

                        If a 3 pole 63A ,D curve 10kA MCB is no longer available in the C120 frame - what can I use instead?



                        Code = A9N18511  3 pole, 15kA, 63A, (27mm wide)