Quantcast

Acti 9 Low Level Auxiliary Contact OF+SD - for C60, C120, C60H-DC, DPN, ID

Acti 9 Low Level Auxiliary Contact OF+SD - for C60, C120, C60H-DC, DPN, ID

Acti 9 Low Level Auxiliary Contact OF+SD - for C60, C120, C60H-DC, DPN, ID

Item Number: A9N26899

Retail
$289.31
RRP (Inc. GST)

Product Dimensions

Width icon

Width9 mm

Height icon

Height85.5 mm

Depth icon

Depth73.5 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

  • Acti 9
  • Clario
  • Librio
  • Prodis
    • Range of product

    • C40
    • ID
    • DPN Vigi
    • DPN
    • Librio
    • ProDis
    • I-NA
    • ITG40
    • C120
    • C60
    • Clario
    • DT60
    • DT40
      • Product or component type

        OC and fault contact with PLC interface

        Product compatibility

      • IDc
      • DT40
      • DPN Vigi
      • C60H-DC
      • C60
      • with PLC
      • SW60-DC
      • C120NA-DC
      • ITG40
      • DT60
      • ID C40
      • C60PV-DC
      • C40
      • iDPN
      • C120
      • C60NA-DC
        • Market segment

        • small commercial
        • residential
          • Sustainable offer status

            Green Premium product

            Warranty

            18 months

            Physical

            [In] rated current

            2-100 mA at 24 V DC +/- 20 %

            Range compatibility

          • Acti 9 DPN Vigi
          • Acti 9 RCCB-ID
          • connectors Ti24
          • Acti 9 C60H-DC
          • Acti 9 C60PV-DC
          • Acti 9 C40
          • Acti 9 ID C40
          • Acti 9 C120
          • Acti 9 DT40
          • Acti 9 DT60
          • Acti 9 IDc
          • Acti 9 C120NA-DC
          • Acti 9 DPN
          • Acti 9 iDPN
          • Acti 9 ITG40
          • Acti 9 SW60-DC
          • Acti 9 C60NA-DC
            • Local signalling

              mechanical indicator

              Mounting mode

              fixed

              Mounting support

              DIN rail

              Height

              85.5 mm

              Width

              9 mm

              Depth

              73.5 mm

              Net weight

              28 g

              Electrical durability

              20000 cycles conforming to IEC 60947-5-4

              Connections - terminals

            • spring-loaded terminal Ti24 (top) 1 cable(s) 0.5-1.5 mm² - rigid
            • spring-loaded terminal Ti24 (top) 1 cable(s) 0.5-1.5 mm² - flexible
              • Wire stripping length

                10 mm

                Standards

              • IEC 60947-5-4
              • IEC 60947-5-1
                • Relative humidity

                  93-93 % at 40-40 °C

                  Ambient air temperature for operation

                  -25-70 °C

                  Ambient air temperature for storage

                  -40-85 °C

                  REACh Regulation

                  Free of Substances of Very High Concern above the threshold

                  REACh free of SVHC

                  Yes

                  EU RoHS Directive

                  Compliant

                  Toxic heavy metal free

                  Yes

                  Mercury free

                  Yes

                  RoHS exemption information

                  Yes

                  China RoHS Regulation

                   Pro-active China RoHS declaration (out of China RoHS legal scope)

                  Environmental Disclosure

                  ENVPEP1505007EN

                  Circularity Profile

                  ENVEOLI1505007EN

                  Others

                  Device short name

                  OF+SD 24

                  Signal contacts composition

                  1 NO + 1 NC

                  9 mm pitches

                  1

                  [Ui] rated insulation voltage

                  500 V conforming to IEC 60664-1

                  [Uimp] rated impulse withstand voltage

                  6 kV conforming to IEC 60664-1

                  Compatibility code

                  OF+SD 24

                  Quality labels

                  CE

                  Pollution degree

                  2 conforming to IEC 60664-1

                  Overvoltage category

                  III

                  Tropicalisation

                  2 conforming to IEC 60947-5-1

                  Unit Type of Package 1

                  PCE

                  Number of Units in Package 1

                  1

                  Package 1 Weight

                  35 g

                  Package 1 Height

                  2 cm

                  Package 1 width

                  8 cm

                  Package 1 Length

                  9.5 cm

                  Unit Type of Package 2

                  BB1

                  Number of Units in Package 2

                  12

                  Package 2 Weight

                  481 g

                  Package 2 Height

                  10 cm

                  Package 2 width

                  9 cm

                  Package 2 Length

                  27 cm

                  Unit Type of Package 3

                  S03

                  Number of Units in Package 3

                  108

                  Package 3 Weight

                  4.864 kg

                  Package 3 Height

                  30 cm

                  Package 3 width

                  30 cm

                  Package 3 Length

                  40 cm

                  WEEE

                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                  Show all specifications

                  Documents & downloads

                  hide show
                  Filter items
                  • All

                  • CAD Files and Packs

                  • Product Brochures

                  • Technical Data Catalogues

                  • Installation Instruction

                  • Operating Manuals

                  Frequently Asked Questions

                  hide show

                  will the A9A26929 fit on a C60-DC MCB?

                  No, those are designed to fit onto the acti9 AC MCBs for those MCBs use the A9N26929

                  What items come with the KITWALLBOX7?

                  A9Z51240 = Type B single phase RCCD
                  A9F54240 = 2 pole, 40A, Curve MCB
                  A9A26969 = Under voltage release

                  What are the codes of the items supplied with the 3 phase EV parking protection kits?

                  Parts that should be supplied as follows:

                  KITPARKING22-1:
                  A9F54440 x 1, MCB, iC60H 4P 40A C Curve
                  A9Z51440 x 1, RCD, iIDP 4P 40A 30mA Type B, 400V
                  A9A26969 x 2, Under voltage release, iMNX 220 240VAC
                  A9F44204 x 1, MCB, iC60N 2P 4A C Curve
                  A9R91240 x 1, RCCB, iID 2P 40A 30mA Type Asi
                  A9A26924 x 2, Aux contact, iOF 240 415VAC 24 130VDC

                  KITPARKING22-2:
                  A9F54440 x 2, MCB, iC60H 4P 40A C Curve
                  A9Z51440 x 2, RCD, iIDP 4P 40A 30mA Type B, 400V
                  A9A26969 x 3, Under voltage release, iMNX 220 240VAC
                  A9F44204 x 1, MCB, iC60N 2P 4A C Curve
                  A9R91240 x 1, RCCB, iID 2P 40A 30mA Type Asi
                  A9A26924 x 4, Aux contact, iOF 240 415VAC 24 130VDC