Quantcast

Acti 9 C120H Circuit Breaker, 2P, 80A, D Curve

Acti 9 C120H Circuit Breaker, 2P, 80A, D Curve

Acti 9 C120H Circuit Breaker, 2P, 80A, D Curve

Item Number: A9N18501

Retail
$1,023.81
RRP (Inc. GST)

Product Dimensions

Width icon

Width54 mm

Height icon

Height81 mm

Depth icon

Depth73 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

C120

Range

Acti 9

Product or component type

miniature circuit-breaker

Device application

distribution

Market segment

  • small commercial
  • residential
    • Sustainable offer status

      Green Premium product

      Warranty

      18 months

      Physical

      [In] rated current

      80 A at 30 °C

      [Ue] rated operational voltage

    • 380...415 V AC 50/60 Hz
    • 220...240 V AC 50/60 Hz
    • 440 V AC 50/60 Hz
    • <= 250 V DC
    • 230...400 V AC 50/60 Hz
      • Control type

        toggle

        Local signalling

        ON/OFF indication

        Mounting mode

        clip-on

        Mounting support

        35 mm symmetrical DIN rail

        Height

        81 mm

        Width

        54 mm

        Depth

        73 mm

        Net weight

        0.41 kg

        Mechanical durability

        20000 cycles

        Electrical durability

        5000 cycles conforming to IEC 60947-2

        Connections - terminals

      • tunnel type terminals1-50 mm² rigid
      • tunnel type terminals1.5-35 mm² flexible
        • Wire stripping length

          15 mm

          Standards

        • EN/IEC 60898-1
        • EN/IEC 60947-2
          • Product certifications

            EAC

            IP degree of protection

            IP20 conforming to IEC 60529

            Relative humidity

            95-95 % at 55-55 °C

            Ambient air temperature for operation

            -30-60 °C

            Ambient air temperature for storage

            -40-70 °C

            REACh free of SVHC

            Yes

            EU RoHS Directive

            Compliant

            Toxic heavy metal free

            Yes

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

             Pro-active China RoHS declaration (out of China RoHS legal scope)

            Environmental Disclosure

            ENVPEP121230EN

            Others

            Product name

            C120

            Device short name

            C120H

            Poles description

            2P

            Number of protected poles

            2

            Neutral position

            left

            Network type

            AC

            Trip unit technology

            thermal-magnetic

            Curve code

            D

            Breaking capacity code

            H

            Breaking capacity

          • 15000 A Icn at 230...400 V AC 50/60 Hz conforming to EN/IEC 60898-1
          • 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
          • 15 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2
          • 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
          • 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
            • Suitability for isolation

              yes conforming to IEC 60947-2

              Network frequency

              50/60 Hz

              Magnetic tripping limit

              10...14 x In

              [Ics] rated service breaking capacity

            • 7500 A 50 % conforming to EN/IEC 60898-1 - 230...400 V AC 50/60 Hz
            • 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
            • 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
            • 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
            • 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
              • Limitation class

                3 conforming to EN/IEC 60947-2

                [Ui] rated insulation voltage

                500 V AC 50/60 Hz conforming to EN/IEC 60947-2

                [Uimp] rated impulse withstand voltage

                6 kV conforming to EN/IEC 60947-2

                Contact position indicator

                yes

                Comb busbar and distribution block compatibility

                YES

                Connection pitch

                9 mm pitches

                6

                Tightening torque

                3.5-3.5 N.m

                Earth-leakage protection

                separate block

                Compatibility code

                C120

                Pollution degree

                3 conforming to IEC 60947-2

                Overvoltage category

                IV

                Tropicalisation

                2 conforming to IEC 60068-1

                Operating altitude

                2000 m

                Unit Type of Package 1

                PCE

                Number of Units in Package 1

                1

                Package 1 Weight

                385 g

                Package 1 Height

                5.3 cm

                Package 1 width

                6.8 cm

                Package 1 Length

                8.6 cm

                Unit Type of Package 2

                BB1

                Number of Units in Package 2

                6

                Package 2 Weight

                2.389 kg

                Package 2 Height

                10 cm

                Package 2 width

                9 cm

                Package 2 Length

                33 cm

                Unit Type of Package 3

                S03

                Number of Units in Package 3

                36

                Package 3 Weight

                14.821 kg

                Package 3 Height

                30 cm

                Package 3 width

                30 cm

                Package 3 Length

                40 cm

                WEEE

                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                Show all specifications

                Frequently Asked Questions

                hide show

                If a 3 pole 63A ,D curve 10kA MCB is no longer available in the C120 frame - what can I use instead?



                Code = A9N18511  3 pole, 15kA, 63A, (27mm wide)   

                Wanted to know if A9N18524 can be used as 3 pole breaker instead of 4 pole?

                Yes, customer can use the 3 pole and leave 4 pole open.

                Are the A9N18359 and A9A26924 compatible?

                The ref A9N18359 is C120 MCB (Multi9 design in the white material).

                The ref A9A26924 is iOF auxiliary (Aciti9 design for iC60 MCB).

                I can confirm that the parts A9N18359 and A9A26924 are not compliant with each other

                 

                What is the new code for the 18364?

                The new code is now A9N18364

                What is the part number for a B curve 125A 3P breaker?

                The part number is A9N18426.

                Do we have a 3 pole 100 amp MCB but in 18mm pitch?

                100A MCBs only available in the C120 range which are 27m pitch. There is no 18mm pitch alternative.
                Show More