Quantcast

Acti 9 Triphase kWh iEM3255 Energy Meter Modbus, 1 Digital I, 1 Digital O

Acti 9 Triphase kWh iEM3255 Energy Meter Modbus, 1 Digital I, 1 Digital O

Acti 9 Triphase kWh iEM3255 Energy Meter Modbus, 1 Digital I, 1 Digital O

Item Number: A9MEM3255

Retail
$1,030.58
RRP (Inc. GST)

Product Dimensions

Width icon

Width90 mm

Height icon

Height95 mm

Depth icon

Depth69 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti 9

Product or component type

energy meter

Market segment

  • buildings small building cost management: billing: main incomer
  • buildings small building cost management: billing: sub feeder
  • buildings small building cost management: billing: panelboard
  • buildings medium building cost management: billing: main incomer
  • buildings medium building cost management: billing: sub feeder
  • buildings medium building cost management: billing: panelboard
  • buildings large building cost management: billing: main incomer
  • buildings large building cost management: billing: sub feeder
  • buildings large building cost management: billing: panelboard
  • buildings multi-site cost management: billing: main incomer
  • buildings multi-site cost management: billing: sub feeder
  • buildings multi-site cost management: billing: panelboard
  • datacenter cost management: billing
  • healthcare cost management: billing
  • industry cost management: billing
  • buildings small building cost management: cost allocation: main incomer
  • buildings small building cost management: cost allocation: sub feeder
  • buildings small building cost management: cost allocation: panelboard
  • buildings medium building cost management: cost allocation: main incomer
  • buildings medium building cost management: cost allocation: sub feeder
  • buildings medium building cost management: cost allocation: panelboard
  • buildings large building cost management: cost allocation: main incomer
  • buildings large building cost management: cost allocation: sub feeder
  • buildings large building cost management: cost allocation: panelboard
  • buildings multi-site cost management: cost allocation: main incomer
  • buildings multi-site cost management: cost allocation: sub feeder
  • buildings multi-site cost management: cost allocation: panelboard
  • datacenter cost management: cost allocation
  • healthcare cost management: cost allocation
  • industry cost management: cost allocation
    • Device application

    • multi-tariff
    • partial meter
    • sub billing
      • Market segment

      • small commercial
      • residential
        • Sustainable offer status

          Green Premium product

          Warranty

          18 months

          Physical

          [In] rated current

        • 5 A
        • 1 A
          • Rated voltage

          • 100-277 V
          • 173-480 V
            • Communication port protocol

              Modbus RTU at 9.6, 19.2 and 38.4 kbauds even/odd or none, insulation 4000 V

              Local signalling

            • green indicator light: power ON
            • yellow flashing LED: accuracy checking
            • alarm: overload
            • yellow indicator light: communications are active on the Modbus port (Modbus)
              • Mounting mode

                clip-on

                Mounting support

                DIN rail

                Connections - terminals

              • current circuit: screw terminals 6-6 mm² cable(s)
              • voltage circuit: screw terminals 2.5-2.5 mm² cable(s)
                • Standards

                • IEC 61036
                • IEC 62053-23
                • UL 61010-1
                • IEC 61010
                • IEC 62053-22
                • IEC 61557-12
                  • Product certifications

                  • CE conforming to IEC 61010 (safety)
                  • CE conforming to EN 61557-12 (power monitor)
                  • CE conforming to IEC 61326-1 (EMC)
                  • cULus conforming to UL 61010 (safety)
                  • cULus conforming to ANSI C12.20 (sub-meter)
                  • EAC (sub-meter)
                  • RCM conforming to NMI M 6-1 (sub-meter)
                  • UL
                  • MID conforming to EN 50470-3 (sub-meter)
                  • MID conforming to EN 62052 (sub-meter)
                    • IP degree of protection

                    • IP40 front panel: conforming to IEC 60529
                    • IP20 body: conforming to IEC 60529
                      • Relative humidity

                        5-95 % at 50-50 °C

                        Ambient air temperature for operation

                        -25-55 °C - IEC

                        Ambient air temperature for storage

                        -40-85 °C

                        Width

                        90 mm

                        Height

                        95 mm

                        Depth

                        69 mm

                        REACh Regulation

                        Free of Substances of Very High Concern above the threshold

                        EU RoHS Directive

                        Compliant

                        Mercury free

                        Yes

                        RoHS exemption information

                        Yes

                        China RoHS Regulation

                        X

                        Environmental Disclosure

                        ENVPEP111276EN

                        Circularity Profile

                        ENVEOLI111261EN_V1

                        Others

                        Product name

                        Acti 9 iEM3000

                        Device short name

                        iEM3255

                        Poles description

                      • 3P + N
                      • 1P + N
                      • 3P
                        • Type of measurement

                        • active and reactive energy
                        • active and reactive power
                        • current
                        • voltage
                          • Metering type

                            active, reactive, apparent energy (signed, four quadrant)

                            Accuracy class

                          • class 0.5S active energy conforming to IEC 62053-22
                          • class 0.5S active energy conforming to IEC 61557-12
                          • class C active energy conforming to EN 50470-3
                            • Analogue input type

                              external CT 1 A or 5 A

                              Network frequency

                            • 60 Hz
                            • 50 Hz
                              • Technology type

                                electronic

                                Display type

                                LCD display

                                Sampling rate

                                32 samples/cycle

                                Measurement current

                                1-32767000 mA

                                Maximum value measured

                                99999999 MWh

                                Information displayed

                                tariff (4)

                                Communication port support

                                screw terminal block: RS485

                                Number of inputs

                                1 digital 0...5 V/11...40 V 24 V DC

                                Number of outputs

                                1 digital (static)

                                Output voltage

                                5...40 V DC@50 mA

                                Overvoltage category

                                III

                                Compatibility code

                                iEM3255

                                Pollution degree

                                2

                                Operating altitude

                                < 2000 m

                                9 mm pitches

                                10

                                Package 1 Weight

                                0.374 kg

                                Package 1 Height

                                8.8 cm

                                Package 1 width

                                9.6 cm

                                Package 1 Length

                                10.6 cm

                                WEEE

                                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                Show all specifications

                                Documents & downloads

                                hide show
                                Filter items
                                • All

                                • CAD Files and Packs

                                • Product Brochures

                                • Technical Data Catalogues

                                • Technical Leaflet

                                • End of Life Manual

                                • Product Environmental

                                • Installation Instruction

                                • Operating Manuals

                                • Certificates (MSDS)

                                • Declaration of Conformity

                                Frequently Asked Questions

                                hide show

                                What size cables will the termninals in the Energy Meters , A9MEM3155 & the A9MEM3355 allow?

                                A9MEM3155 - 16mm
                                A9MEM3355 - 50mm
                                For further information , visit links below:-
                                https://www.schneider-electric.com.au/en/search/A9MEM3155
                                https://www.schneider-electric.com.au/en/search/A9MEM3355
                                User-added image

                                What is the alternate part number for 17072

                                 Replacement is a A9MEM3210

                                Which KWH meter will measure Solar inputs with Modbus connections?

                                Can you retrieve data from the A9MEM3155 modbus meter wireless using a Modbus to WiFi converter?

                                We recommend to use  standard tested SE solution like using COM'X with Wifi dongle, which can be connected to iEM3155 over Modbus RTU and COM'X will sendthe data of meter over Wifi.

                                 

                                What is the alternative code for 17072?

                                A9MEM3210

                                Do you have a Bacnet, NMI approved kilowatt hour meter with CT's?

                                The part number for a Bacnet, NMI approved kilowatt-hour meter with CT's is a - A9MEM3265.


                                 
                                Show More