Quantcast

iEM2000 Series Modular Single Phase Power Meter, 230V, 63A, Comm Modbus

iEM2000 Series Modular Single Phase Power Meter, 230V, 63A, Comm Modbus

iEM2000 Series Modular Single Phase Power Meter, 230V, 63A, Comm Modbus

Item Number: A9MEM2150

Retail
$747.75
RRP (Inc. GST)

Product Dimensions

Width icon

Width36 mm

Height icon

Height90 mm

Depth icon

Depth64 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti 9

Product or component type

energy meter

Market segment

  • buildings small building cost management: billing: panelboard
  • buildings medium building cost management: billing: panelboard
  • buildings large building cost management: billing: panelboard
  • buildings multi-site cost management: billing: panelboard
  • datacenter cost management: billing: panelboard
  • healthcare cost management: billing: panelboard
  • industry cost management: billing: panelboard
  • buildings small building cost management: cost allocation: panelboard
  • buildings medium building cost management: cost allocation: panelboard
  • buildings large building cost management: cost allocation: panelboard
  • buildings multi-site cost management: cost allocation: panelboard
  • datacenter cost management: cost allocation: panelboard
  • healthcare cost management: cost allocation: panelboard
  • industry cost management: cost allocation: panelboard
    • Device application

    • sub billing
    • partial meter
      • Physical

        [In] rated current

        63 A

        Rated voltage

        230-230 V +/- 20 %

        Communication port protocol

        Modbus RTU at 1.2, 2.4, 4.8, 9.6, 19.2 and 38.4 kbauds even/odd or none - 3 wires, insulation 4000 V

        Local signalling

        red LED: accuracy checking 1...1000 p/kWh

        Mounting mode

        clip-on

        Mounting support

        DIN rail

        Connections - terminals

      • power circuit: tunnel type terminals (bottom) 1 1.65-33 mm² cable(s) solid
      • power circuit: tunnel type terminals (bottom) 1 1.65-33 mm² cable(s) stranded with cable end
      • communication: screw clamp terminals (top) 1 1-4 mm² cable(s) solid
      • communication: screw clamp terminals (top) 1 1-2.5 mm² cable(s) stranded with cable end
        • Wire stripping length

        • power circuit: 17 mm
        • communication: 7 mm
          • Standards

          • IEC 62052-31
          • IEC 62053-21
          • IEC 62053-23
          • IEC 62052-11
            • Product certifications

              CE

              IP degree of protection

              IP20 conforming to IEC 60529

              Ambient air temperature for operation

              -25-55 °C

              Ambient air temperature for storage

              -25-70 °C

              Relative humidity

              0-95 %

              Width

              36 mm

              Height

              90 mm

              Depth

              64 mm

              Net weight

              0.175 kg

              EU RoHS Directive

              Compliant

              Mercury free

              Yes

              RoHS exemption information

              Yes

              China RoHS Regulation

              X

              Others

              Number of Units in Package 1

              1

              Number of Units in Package 2

              29

              Package 1 Height

              5.2 cm

              Package 1 Length

              9.8 cm

              Package 1 width

              8 cm

              Package 2 Height

              15 cm

              Package 2 Length

              40 cm

              Package 2 width

              30 cm

              Unit Type of Package 1

              PCE

              Unit Type of Package 2

              S02

              Product name

              Acti 9 iEM2100

              Device short name

              iEM2150

              Poles description

              1P + N

              Type of measurement

            • active and reactive energy
            • active and reactive power
            • current
            • voltage
              • Metering type

                active, reactive, apparent energy (signed, four quadrant)

                Accuracy class

              • class 1 active energy conforming to IEC 62053-21
              • class 2 reactive energy conforming to IEC 62053-23
                • Analogue input type

                  direct input

                  Network frequency

                • 50 Hz
                • 60 Hz
                  • Frequency measurement range

                    45-65 Hz

                    Technology type

                    electronic

                    Display type

                    LCD display

                    Sampling rate

                    32 samples/cycle

                    Measurement current

                    0-63 A

                    Display digits

                    8

                    Maximum value measured

                    999999.99 kWh

                    Information displayed

                    tariff (1)

                    Communication port support

                    screw terminals: RS485

                    Number of inputs

                    0-0

                    Number of outputs

                    0

                    [Us] rated supply voltage

                    96...276 V AC 50 Hz

                    Maximum power consumption in VA

                    2 VA

                    Maximum power consumption in W

                    1 W

                    [Uimp] rated impulse withstand voltage

                    6 kV 1.2/50 µs

                    Tightening torque

                  • power circuit: 2-2 N.m PZ2 screwdriver
                  • communication: 0.5-0.5 N.m3.5 mm
                    • Compatibility code

                      iEM2150

                      Overvoltage category

                      III

                      Pollution degree

                      2

                      Flame retardance

                      V0 conforming to UL 94

                      9 mm pitches

                      4

                      Package 1 Weight

                      220 g

                      Package 2 Weight

                      6.835 kg
                      Show all specifications

                      Documents & downloads

                      hide show
                      Filter items
                      • All

                      • Product Brochures

                      • Technical Data Catalogues

                      • Technical Leaflet

                      • Installation Instruction

                      • Operating Manuals

                      • Application Solutions

                      • Declaration of Conformity

                      Frequently Asked Questions

                      hide show

                      What size cables will the termninals in the Energy Meters , A9MEM3155 & the A9MEM3355 allow?

                      A9MEM3155 - 16mm
                      A9MEM3355 - 50mm
                      For further information , visit links below:-
                      https://www.schneider-electric.com.au/en/search/A9MEM3155
                      https://www.schneider-electric.com.au/en/search/A9MEM3355
                      User-added image

                      What is the product code for the iEM2000 Acti9 230V 40A din rail mount energy monitor?

                      The product code is A9MEM2000. Please see the attached datasheet for more information.
                       

                      ETSNZ - What Single Phase Check Meter does not Require a Neutral Through Connection

                      The New range of Acti9  A9MEM2150 for example only needs a N connection  - it does not require to pass the N current through it.

                      Is the Acti 9 A9MEM3110 3 phase?

                      Yes, the iEM3110 kWh meter with pulse output, is a 3 phase digital meter for direct connection up to 63Amps.

                      What is the alternate part number for 17072

                       Replacement is a A9MEM3210

                      Wiring diagram for iEM2000.