hide show
Range
Acti 9
Product name
Acti 9 iEM2100
Device short name
iEM2105
Product or component type
energy meter
Market segment
Poles description
1P + N
Type of measurement
active energy
Device application
  • sub billing
  • partial meter
    • Accuracy class
      class 1 active energy conforming to IEC 62053-21
      Analogue input type
      direct input
      [In] rated current
      63 A
      Rated voltage
      230-230 V +/- 20 %
      Network frequency
    • 50 Hz
    • 60 Hz
      • Frequency measurement range
        45-65 Hz
        Technology type
        electronic
        Display type
        LCD display
        Sampling rate
        32 samples/cycle
        Measurement current
        0-63 A
        Display digits
        5
        Maximum value measured
        999.99 MWh
        Information displayed
        tariff (1)
        Communication port protocol
        -
        Communication port support
        -
        Local signalling
      • green indicator light: power ON
      • yellow indicator light: metering and activity 1000 p/kWh
        • Number of inputs
          0-0
          Number of outputs
          1 pulse
          Output voltage
        • 24 V DC@18 mA
        • 230 V AC@100 mA
          • Impulse duration
            200 ms
            Maximum power consumption in VA
            2.5 VA
            Mounting mode
            clip-on
            Mounting support
            DIN rail
            Connections - terminals
            power circuit: tunnel type terminals (bottom) 1 16-16 mm² cable(s)
            Tightening torque
          • power circuit: 1.5-1.5 N.m
          • remote transfer: 0.9-0.9 N.m
            • Standards
            • IEC 61557-12
            • IEC 62053-21
              • Product certifications
                CE
                Compatibility code
                iEM2105
                IP degree of protection
                IP50 conforming to IEC 60529
                IK degree of protection
                IK05
                Ambient air temperature for operation
              • -20-70 °C < 32 A
              • -20-55 °C >= 32 A
                • Ambient air temperature for storage
                  -40-70 °C
                  Relative humidity
                  0-95 % at 55-55 °C
                  9 mm pitches
                  4
                  Width
                  36 mm
                  Height
                  81 mm
                  Depth
                  65 mm
                  Net weight
                  0.135 kg
                  EU RoHS Directive
                  Compliant
                  Toxic heavy metal free
                  Yes
                  Mercury free
                  Yes
                  RoHS exemption information
                  Yes
                  China RoHS Regulation
                   Pro-active China RoHS declaration (out of China RoHS legal scope)

                  Documents & downloads

                  hide show
                  Filter items
                  • All

                  • CAD Files and Packs

                  • Product Brochures

                  • Movies

                  • Technical Data Catalogues

                  • Technical Leaflet

                  • Installation Instruction

                  • Product Environmental

                  • End of Life Manual

                  • Operating Manuals

                  • Declaration of Conformity

                  • White Paper

                  • Certificates (MSDS)

                  • Software - Updates

                  Frequently Asked Questions

                  hide show

                  What size cables will the termninals in the Energy Meters , A9MEM3155 & the A9MEM3355 allow?

                  A9MEM3155 - 16mm
                  A9MEM3355 - 50mm
                  For further information , visit links below:-
                  https://www.schneider-electric.com.au/en/search/A9MEM3155
                  https://www.schneider-electric.com.au/en/search/A9MEM3355
                  User-added image

                  What is the replacement for a 17072

                   The replacement is a A9MEM3210.

                  What is the product code for the iEM2000 Acti9 230V 40A din rail mount energy monitor?

                  The product code is A9MEM2000. Please see the attached datasheet for more information.
                   

                  What is the alternate part number for 17072

                   Replacement is a A9MEM3210

                  What is the alternative code for 17072?

                  A9MEM3210

                  What is the part number for Single phase KWH meter?

                  The part number for Single phase KWH meter will be a - A9MEM2105.
                  Please refer the below link for more information,
                  https://www.schneider-electric.com/en/product/A9MEM2105/modular-single-phase-power-meter-iem2105---230v---63a-with-pulse/
                  Image result for a9mem2105 schneider



                   

                  Can you retrieve data from the A9MEM3155 modbus meter wireless using a Modbus to WiFi converter?

                  We recommend to use  standard tested SE solution like using COM'X with Wifi dongle, which can be connected to iEM3155 over Modbus RTU and COM'X will sendthe data of meter over Wifi.

                   

                  Is the Acti 9 A9MEM3110 3 phase?

                  Yes, the iEM3110 kWh meter with pulse output, is a 3 phase digital meter for direct connection up to 63Amps.

                  What are the power terminal sizes on the A9MEM3100?

                  The power terminal sizes of the iEM3100 meter will take 16mm cable
                  see instruction sheet....https://eshop.schneider-electric.com/Download.aspx?infos=H808089_1.pdf;3

                  ETSNZ - What Single Phase Check Meter does not Require a Neutral Through Connection

                  The New range of Acti9  A9MEM2150 for example only needs a N connection  - it does not require to pass the N current through it.

                  What is the replacement for 15467 Power meter with 100/5 CTs?

                  Do you have a Bacnet, NMI approved kilowatt hour meter with CT's?

                  The part number for a Bacnet, NMI approved kilowatt-hour meter with CT's is a - A9MEM3265.


                   

                  What are the Dimensions for the A9MEM2000 single phase power meter?

                    9 mm pitches 2  
                   
                   
                    Width 18 mm  
                   
                   
                    Height 95 mm  
                   
                   
                    Depth 67 mm  
                   
                   
                    Product weight 0.073 kg  

                  Which KWH meter will measure Solar inputs with Modbus connections?

                  What is the DC rating of A9F44210?

                  Acti9 miniture circuit breakers, can handle upto 60VDC.

                  What is the DC rating of A9F44210?

                  Acti9 miniture circuit breakers, can handle upto 60VDC.

                  Can the IEM3000 series read energy output from a Solar Panel?

                  To be able to measure the energy out from a Solar Panel a meter needs to be able to do Four Quadrant Calculation.

                  This means it is capable of Identification of imported and exported active and reactive energy allows you to monitor energy flow in both directions: delivered from the utility and produced on-site.

                  In the iEM3000 series the following meters are capable of Four Quadrant Calculation.

                  iEM31** range - iEM3135, iEM3155, iEM3165, and iEM3175
                  iEM32** range - iEM3235, iEM3255, iEM3265, and iEM3275
                  iEM33** range - iEM3335, iEM3355, iEM3365, and iEM3375
                  iEM34** range - iEM3455, iEM3465, iEM3555, and iEM3565


                   

                  What is the DC rating of the A9F44210?

                  The DC rating of the Acti9 miniture circuit breakers is 60VDC.

                  Please See attachment:

                  Can Rogowski Coil Current Transformers (Rope Style CT's) Be Extended in the Field? How Far?

                  Issue
                  Rogowski Coil CT's may require secondary lead length extension.

                  Product Line
                  A9MEM3500 meters
                  EM4200 meters
                  EM3500 meters
                  U018 Rogowski Coil Current Transformers

                  Environment
                  Metering & Power Monitoring

                  Cause
                  The load may be farther from the meter than the standard 8' or 12' secondary lead lengths may reach.

                  Resolution
                  Schneider Rogowski Coil Current Transformers come in primary lengths of 12", 18", 24", or 36". 
                  This measurement only applies to the primary length only.
                  This is the length that the current transformer has to connect back to itself around a conductor or set of conductors of the load to be monitored.

                  The lead length refers to the 8' or 12' that connects from the current transformer to the meter itself.

                  It is sometimes difficult to get the meter mounting location within 8' or 12' from an appropriate location to install the current transformer on the load conductors.
                  Because of this, one may need to extend the length of the secondary leads from the current transformers.

                  Either the 8' or the 12' secondary lead length version of Schneider's Rogowski Coil (U018-xxx) Current Transformers may be extended to a maximum of 20' total lead length (to include the original lead length of either 8' or 12').
                  The conductors used must be a standard 24 gauge twisted cable.

                  What is the End Caps to suit the 2 Pole Acti 9 Busbar?

                  End cap for the A9XPH212 and A9XPH224 = A9XPE210.

                  On the PowerTag A9 F63 model, ref. A9MEM1562 if I try to be consistent with the flat cable position, the LED of the module is upwards. Should I twist the flat cable to have the LED down?

                  This has no impact on the operation but to be consistent with the rest of the range we favor the Led down, and in this case, the flat cable is twisted.

                  Power Meter Communication issue, registers not reading the correct value.

                  The Power meters, based on the manufacturing location may have an offset. 

                  In some meters the registers starts from Zero and some it is taken account from 1. So the published register list varies accordingly. 

                  For Ex: If Register 2017 is for Frequency of the meters it will read 50 HZ. 
                  But for the meter with offset the the Register 2016 will read 50HZ. 

                  So it is good to check if the meter has got an Offset before proceeding with the communication issue.