PowerTag A9 F63 3P+N

PowerTag 3PN MAX 63A Energy Sensor

Catalogue Number: A9MEM1570
PowerTag A9 F63 3P+N
Retail
$365.27
RRP (Inc. GST)

Specifications

hide show
Range
PowerLogic
Product name
PowerTag A9 F63
Product or component type
energy sensor
Poles description
3P + N
Max current
63 A
[Ib] basic current
10 A
Starting current
40 mA
Saturation current
130 A
Product specific application
  • cost allocation
  • load monitoring
  • overload alarm
  • circuit monitoring
  • energy management
    • Concentrator compatibility
    • Acti9 Smartlink SI B
    • Acti9 Smartlink SI D
    • Acti9 PowerTag Link C
    • Acti9 PowerTag Link
    • Acti9 PowerTag Link HD
    • Harmony Hub
      • Market segment
      • buildings: breaker voltage monitoring
      • buildings: cost allocation
      • buildings: overload alarm
        • Range compatibility
        • Vigi DT40
        • Vigi iC40
        • Vigi iDT40
        • Vigi N40
        • Vigi C40
        • Vigi iC60
        • Acti 9 iDD40
        • Acti 9 iDD40 XA
        • Acti 9 iCV40 XA
        • Vigi iDPN
        • Acti 9 iCV40
        • Vigi iTG40
        • Vigi iCG40
          • Type of measurement
          • voltage
          • active energy
          • active power
          • current
          • power factor
            • Accuracy class
            • class 1 current conforming to IEC 61557-12
            • class 0.5 voltage conforming to IEC 61557-12
            • class 1 active power conforming to IEC 61557-12
            • class 1 active energy conforming to IEC 61557-12
            • class 1 power factor conforming to IEC 61557-12
              • Mounting location
                top or bottom
                Mounting support
                on circuit breaker
                Product destination
                switchboard
                Event management
                voltage loss with measured current at voltage loss
                Transmission support medium
                radio frequency 2.4-2.4835 GHz conforming to IEEE 802.15.4
                Maximum emission power
                10 mW
                Form factor
                flex
                Mounting mode
                by screws (terminals)
                Electrical connection
                wires with cable end
                Cable cross section
              • 1 rigid cable 1.5-16 mm²
              • 2 stranded cable 1.5-2.5 mm²
              • 2 rigid cable 1.5-2.5 mm²
              • 1 stranded cable 1.5-16 mm²
                • Cable length
                  0.25 m
                  [Ue] rated operational voltage
                • 220...240 V AC, +/- 20 %, between phase and neutral
                • 380...415 V AC, +/- 20 %, between phases
                  • Network frequency
                  • 50 Hz
                  • 60 Hz
                    • Maximum power consumption in VA
                      2 VA
                      Standards
                    • IEC 61557-12
                    • IEC 61010-1
                    • IEC 61010-2-030
                    • IEC 61326-1
                    • ETSI EN 300 328
                      • Height
                        sensor element: 20 mm
                        Width
                        sensor element: 54 mm
                        Depth
                        sensor element: 46.6 mm
                        Net weight
                        40 g
                        Compatibility code
                        PowerTag A9 P63
                        Quality labels
                        CE
                        Directives
                        2014/53/EU - radio equipment directive
                        Operating altitude
                        0...2000 m
                        Ambient air temperature for operation
                        -25-60 °C
                        Ambient air temperature for storage
                        -40-85 °C
                        Overvoltage category
                        III conforming to IEC 61010-1
                        Measurement category
                        category III conforming to IEC 61010-2-030
                        IP degree of protection
                        IP20 conforming to IEC 60529
                        IK degree of protection
                        IK05
                        Pollution degree
                        3
                        Relative humidity
                        0-95 % at 45-45 °C conforming to IEC 60721-3-3
                        Vibration resistance
                        3M4 conforming to IEC 60721-3-3
                        Environmental characteristic
                      • dustproof class 3S3 conforming to IEC 60721-3-3
                      • salt mist class 3C2 conforming to IEC 60721-3-3
                        • Sustainable offer status
                          Green Premium product
                          REACh Regulation
                          Free of Substances of Very High Concern above the threshold
                          EU RoHS Directive
                          Compliant
                          Mercury free
                          Yes
                          RoHS exemption information
                          Yes
                          China RoHS Regulation
                          Product out of China RoHS scope. Substance declaration for your information
                          Environmental Disclosure
                          ENVPEP1605012
                          Circularity Profile
                          ENVEOLI1605012
                          WEEE
                          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                          Documents & downloads

                          hide show
                          Filter items
                          • All

                          • CAD Files and Packs

                          • Product Brochures

                          • Technical Data Catalogues

                          • Catalog Page

                          • Installation Instruction

                          • Product Environmental

                          • End of Life Manual

                          • Operating Manuals

                          • Certificates (MSDS)

                          Frequently Asked Questions

                          hide show

                          What size cables will the termninals in the Energy Meters , A9MEM3155 & the A9MEM3355 allow?

                          A9MEM3155 - 16mm
                          A9MEM3355 - 50mm
                          For further information , visit links below:-
                          https://www.schneider-electric.com.au/en/search/A9MEM3155
                          https://www.schneider-electric.com.au/en/search/A9MEM3355
                          User-added image

                          Is the Acti 9 A9MEM3110 3 phase?

                          Yes, the iEM3110 kWh meter with pulse output, is a 3 phase digital meter for direct connection up to 63Amps.

                          What is the alternate part number for 17072

                           Replacement is a A9MEM3210

                          ETSNZ - What Single Phase Check Meter does not Require a Neutral Through Connection

                          The New range of Acti9  A9MEM2150 for example only needs a N connection  - it does not require to pass the N current through it.

                          What is the product code for the iEM2000 Acti9 230V 40A din rail mount energy monitor?

                          The product code is A9MEM2000. Please see the attached datasheet for more information.
                           

                          What is the alternative code for 17072?

                          A9MEM3210

                          On the PowerTag A9 F63 model, ref. A9MEM1562 if I try to be consistent with the flat cable position, the LED of the module is upwards. Should I twist the flat cable to have the LED down?

                          This has no impact on the operation but to be consistent with the rest of the range we favor the Led down, and in this case, the flat cable is twisted.

                          Can you retrieve data from the A9MEM3155 modbus meter wireless using a Modbus to WiFi converter?

                          We recommend to use  standard tested SE solution like using COM'X with Wifi dongle, which can be connected to iEM3155 over Modbus RTU and COM'X will sendthe data of meter over Wifi.

                           

                          What is the replacement for 15467 Power meter with 100/5 CTs?

                          Can Rogowski Coil Current Transformers (Rope Style CT's) Be Extended in the Field? How Far?

                          Issue
                          Rogowski Coil CT's may require secondary lead length extension.

                          Product Line
                          A9MEM3500 meters
                          EM4200 meters
                          EM3500 meters
                          U018 Rogowski Coil Current Transformers

                          Environment
                          Metering & Power Monitoring

                          Cause
                          The load may be farther from the meter than the standard 8' or 12' secondary lead lengths may reach.

                          Resolution
                          Schneider Rogowski Coil Current Transformers come in primary lengths of 12", 18", 24", or 36". 
                          This measurement only applies to the primary length only.
                          This is the length that the current transformer has to connect back to itself around a conductor or set of conductors of the load to be monitored.

                          The lead length refers to the 8' or 12' that connects from the current transformer to the meter itself.

                          It is sometimes difficult to get the meter mounting location within 8' or 12' from an appropriate location to install the current transformer on the load conductors.
                          Because of this, one may need to extend the length of the secondary leads from the current transformers.

                          Either the 8' or the 12' secondary lead length version of Schneider's Rogowski Coil (U018-xxx) Current Transformers may be extended to a maximum of 20' total lead length (to include the original lead length of either 8' or 12').
                          The conductors used must be a standard 24 gauge twisted cable.

                          What is the replacement for a 17072

                           The replacement is a A9MEM3210.

                          What are the power terminal sizes on the A9MEM3100?

                          The power terminal sizes of the iEM3100 meter will take 16mm cable
                          see instruction sheet....https://eshop.schneider-electric.com/Download.aspx?infos=H808089_1.pdf;3
                          Show More