Acti 9 iC60H 1P 1A…63A Miniature Circuit Breaker

Acti9 Ic60h, 1P, 32A, C Miniature Circuit Breaker

Catalogue Number: A9F54132
Acti 9 iC60H 1P 1A…63A Miniature Circuit Breaker
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range
Acti 9
Range of product
Acti 9
Product name
Disbo iC60
Product or component type
miniature circuit-breaker
Device short name
iC60H
Poles description
1P
Number of protected poles
1
[In] rated current
32 A
Network type
AC
Trip unit technology
thermal-magnetic
Curve code
C
Breaking capacity code
H
Breaking capacity
  • 20 kA Icu at 12...48 V DC conforming to EN/IEC 60947-2
  • 10 kA Icu at 72 V DC conforming to EN/IEC 60947-2
  • 10000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
  • 42 kA Icu at 10...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
  • 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
  • 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
    • Utilisation category
      category A conforming to EN/IEC 60947-2
      Network frequency
      50/60 Hz
      [Ue] rated operational voltage
      240 V AC 50/60 Hz
      Magnetic tripping limit
      8 x In +/- 20 %
      [Ics] rated service breaking capacity
    • 21 kA 50 % conforming to EN/IEC 60947-2 - 10...60 V AC 50/60 Hz
    • 15 kA 50 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz
    • 7.5 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
    • 7500 A 75 % conforming to EN/IEC 60898-1 - 240 V AC 50/60 Hz
    • 20 kA 100 % conforming to EN/IEC 60947-2 - 12...48 V DC
    • 10 kA 100 % conforming to EN/IEC 60947-2 - 72 V DC
      • Limitation class
        3 conforming to EN/IEC 60947-2
        [Ui] rated insulation voltage
        500 V AC 50/60 Hz conforming to EN/IEC 60947-2
        [Uimp] rated impulse withstand voltage
        6 kV conforming to EN/IEC 60947-2
        Contact position indicator
        yes
        Control type
        toggle
        Local signalling
        trip indicator
        Mounting mode
        clip-on
        Mounting support
        rail
        Connection pitch
        9 mm pitches
        2
        Height
        85 mm
        Width
        18 mm
        Depth
        78.5 mm
        Net weight
        0.125 kg
        Mechanical durability
        20000 cycles
        Electrical durability
        10000 cycles
        Provision for padlocking
        padlockable
        Connections - terminals
      • single terminal (top or bottom) 1-35 mm² rigid
      • single terminal (top or bottom) 1-25 mm² flexible
        • Wire stripping length
          14 mm for top or bottom connection
          Tightening torque
          3.5-3.5 N.m top or bottom
          Earth-leakage protection
          separate block
          Compatibility code
          iC60
          Standards
        • EN/IEC 60947-2
        • EN/IEC 60898-1
          • IP degree of protection
            IP20 conforming to IEC 60529
            Pollution degree
            3 conforming to EN/IEC 60947-2
            Tropicalisation
            2 conforming to IEC 60068-1
            Relative humidity
            95-95 % at 55-55 °C
            Ambient air temperature for operation
            -35-70 °C
            Ambient air temperature for storage
            -40-85 °C
            Sustainable offer status
            Green Premium product
            REACh Regulation
            Free of Substances of Very High Concern above the threshold
            REACh free of SVHC
            Yes
            EU RoHS Directive
            Compliant
            Toxic heavy metal free
            Yes
            Mercury free
            Yes
            RoHS exemption information
            Yes
            China RoHS Regulation
             Pro-active China RoHS declaration (out of China RoHS legal scope)
            Environmental Disclosure
            ENVPEP1409009EN
            WEEE
            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

            Frequently Asked Questions

            hide show

            What is the suitable vigi unit to suit with the A9F54332?

            A9F54332 is a 3 pole breaker.
            They have an option of having 3 pole vigi (A9V51363) or 4 pole vigi (A9V02763) for neutral conection .

            What is the part number of a 3 pole 32A, 10KA, C curve Acti 9 circuit breaker?

            A9F54332 is a 3 pole 32A, 10KA, C curve Acti 9 circuit breaker. For further information, please visit https://www.schneider-electric.co.uk/en/product/A9F54332/acti9-ic60h-3p-32a-c-miniature-circuit-breaker/

            Schneider Eletric A9F54332 Picture

            What is the code for a 10kA 16A 1p C Curve MCB?

             The code is A9F54116

            what is size of the Cable that will fit into the MCB A9F54106 ?

            Cable = 25mm stranded
             

            What is the part code for an Acti9 10kA 3Pole 32amp 'C' curve MCB?

            The part number is A9F54332.

            Do you do a 3 pole version of a 4RCBM232/30?

            Unfortunately we do not offer a 3 pole version of a 4RCBM230/30.

            However as an alternative we can offer a A9F54432 (4 Pole 32A Circuit Breaker) and a A9V06763 (Vigi Block).

            For further information please visit www.clipsal.com/Trade

            What is the Code for a 2 Pole 32A C curve MCB rated at 6 kA ?

            Code = A9F44232

            What is the part number for a 4 pole 32A circuit breaker?

            The part number is A9F54432.

            Do you have a C60H Circuit breaker single phase 10A?

            In the Schneider range we have the Acti 9 IC60H circuit breakers. The part number for a single phase, 10A is a A9F54110.

             

            Is part number A9F44106 DC rated?

            Yes, part is DC rated up to 48 volts.

            Is it possible to get the PDL 695R (10A Horizontal double, switched socket with Round Earth Pin) in black?

            No, the complete unit does not come complete in black. However, you can purchase the PDL 695C in black (BK) and swap the cover plates over.
            But the Sockets and the switches will still be white.
             

            Data sheet for A9F54240 ?

            Data sheet attached

            What is the part code for a 32amp 3P 6kA C Curve MCB?

            The Code is A9F44332.

            What is the part number for 20A 10kA D curve 3 pole circuit breaker?

            The part number for 20A 10kA D curve 3 pole circuit breaker is A9F55320.

            What is the part number for a 6A B-Curve circuit breaker?

            The part name is A9F53106

            What is the part number for a 25A 3 phase D curve breaker?

            The part name is A9F55325

            What is the Acti 9 substitute for the Multi 9 25807?

            The A9F44140 is the Acti 9 substitute.

            Please see the attached datasheet for further information on the A9F44140.

            Is there an alternative for a 1 module RCD-MCB part number 4RCBE116/30D?

            Yes, however it is larger in size as it requires 4 modules. The replacement part numbers are A9F55116 + A9V02663.

            What items come with the KITWALLBOX7?

            A9Z51240 = Type B single phase RCCD
            A9F54240 = 2 pole, 40A, Curve MCB
            A9A26969 = Under voltage release

            What is the part number for a side mount auxiliary contact block to suit A9F44106 circuit breaker?

            Part number for the side mount auxiliar for the Acti 9 range of circuit breakers is A9A26924.
            See link for more details...
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9A26924

            User-added image

            What is the part number for a 6A D-Curve single pole breaker?

            The part number for a 6A D-Curve single pole breaker is a A9F55106.
            Some of the key features are:
            • ACTI9 IC60H Series
            • Single phase
            • Rated at 6 Amps
            • D- Curve Minitire circuit breaker
            For further information please visit Clipsal - A9F55106 - ACTI9 IC60H 1P 6A D MINIATURE CIRCUIT BR

             

            What is a 1 pole 20 amp "D" curve RCBO?

            Use a 1 pole 20 amp "D" curve breaker A9F55120 and add the vigi unit A9V02663 to make the Combo ...(now 3 poles wide)
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F55120
            and vigi
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9V02663

            User-added image
             User-added image

            What is the part number for an A9D11810 but in "D" curve?

            need to build up with "D" curve circuit breaker A9F55110 and vigi unit A9V02663
            for more details see ....... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F55110
            and ............... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9V02663
            User-added image    User-added image

            What is the part number for a 1 pole 25amp D-Curve RCBO?

            The part number for a 1 pole 25amp D-Curve RCBO is - A9F55125 & A9V02663

            For further information , visit link below:-
            https://www.schneider-electric.com.au/en/search/A9F55125
            https://www.schneider-electric.com.au/en/search/A9V02663
            User-added image

            User-added image

            What is the part number for a 3 phase 20amp MCB/RCD combo?

            The part number for a 3 phase 20amp MCB/RCD combo is - A9F44320 & A9V02763

            For further information visit links below:-
            https://www.schneider-electric.com.au/en/search/A9F44320
            https://www.schneider-electric.com.au/en/search/A9V02763
            User-added image

            User-added image

            How to make a 1 Pole 16 Amps 30mA D Curve RCBO?

            Use a 1 Pole 16 Amps D Curve Circuit Breaker Part # A9F55116 and clip it on the Add-on Vigi Block A9V02663

            https://www.schneider-electric.com.au/en/search/A9V02663



             

            How can I make 1 Pole 10 Amps B Curve 30mA RCBO?

            To make 1 Pole 10 Amps B Curve 30mA RCBO, you need the following:
            A9F53110 - 1 Pole 10 Amps B Curve Breaker (https://www.schneider-electric.com.au/en/search/A9F53110)
            +
            A9V02663 - 2 Pole 30mA 63 Amps Add-on Vigi to suit 1 Pole iC60 Breakers (https://www.schneider-electric.com.au/en/search/A9F53110)

            Please note the total width of this combination will be equal to 3 Poles standard RCBO (3 x 18mm)