Acti9 iC60N, 2P, 25A, C Miniature Circuit Breaker

Acti9 iC60N, 2P, 25A, C Miniature Circuit Breaker

Acti9 iC60N, 2P, 25A, C Miniature Circuit Breaker

Item Number: A9F44225

Retail
$229.27
RRP (Inc. GST)

Product Dimensions

Width icon

Width36 mm

Height icon

Height85 mm

Depth icon

Depth78.5 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti 9

Range of product

Acti 9

Product or component type

miniature circuit-breaker

Sustainable offer status

Green Premium product

Physical

[In] rated current

25 A

[Ue] rated operational voltage

440 V AC 50/60 Hz

Control type

toggle

Local signalling

trip indicator

Mounting mode

clip-on

Mounting support

rail

Height

85 mm

Width

36 mm

Depth

78.5 mm

Net weight

0.25 kg

Mechanical durability

20000 cycles

Electrical durability

10000 cycles

Connections - terminals

  • single terminal (top or bottom) 1-25 mm² rigid
  • single terminal (top or bottom) 1-16 mm² flexible
    • Wire stripping length

      14 mm for top or bottom connection

      Standards

    • EN/IEC 60947-2
    • EN/IEC 60898-1
      • IP degree of protection

        IP20 conforming to IEC 60529

        Relative humidity

        95-95 % at 55-55 °C

        Ambient air temperature for operation

        -35-70 °C

        Ambient air temperature for storage

        -40-85 °C

        REACh free of SVHC

        Yes

        EU RoHS Directive

        Compliant

        Toxic heavy metal free

        Yes

        Mercury free

        Yes

        RoHS exemption information

        Yes

        China RoHS Regulation

         Pro-active China RoHS declaration (out of China RoHS legal scope)

        Environmental Disclosure

        ENVPEP1409009EN

        Others

        Product name

        Disbo iC60

        Device short name

        iC60N

        Poles description

        2P

        Number of protected poles

        2

        Network type

        AC/DC

        Trip unit technology

        thermal-magnetic

        Curve code

        C

        Breaking capacity code

        N

        Breaking capacity

      • 6 kA Icu at 100...133 V DC conforming to EN/IEC 60947-2
      • 6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
      • 36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
      • 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
      • 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
      • 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
        • Utilisation category

          category A conforming to EN/IEC 60947-2

          Network frequency

          50/60 Hz

          Magnetic tripping limit

          8 x In +/- 20 %

          [Ics] rated service breaking capacity

        • 27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz
        • 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
        • 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
        • 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
        • 6000 A 100 % conforming to EN/IEC 60898-1 - 415 V AC 50/60 Hz
        • 6 kA 100 % conforming to EN/IEC 60947-2 - 100...133 V DC
          • Limitation class

            3 conforming to EN/IEC 60947-2

            [Ui] rated insulation voltage

            500 V AC 50/60 Hz

            [Uimp] rated impulse withstand voltage

            6 kV conforming to EN/IEC 60947-2

            Contact position indicator

            yes

            Connection pitch

            9 mm pitches

            4

            Provision for padlocking

            padlockable

            Tightening torque

            2-2 N.m top or bottom

            Earth-leakage protection

            separate block

            Compatibility code

            iC60

            Pollution degree

            3 conforming to EN/IEC 60947-2

            Tropicalisation

            2 conforming to IEC 60068-1

            Package 1 Weight

            0.227 kg

            Package 1 Height

            0.75 dm

            Package 1 width

            0.36 dm

            Package 1 Length

            0.9 dm

            WEEE

            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
            Show all specifications

            Frequently Asked Questions

            hide show

            What is the part number for 2 pole 25amp Acti 9 C/B?

            A9F44225

            What is a 2pole, 6A, C Curve, 6kA circuit breaker

             Part code 25815 Multi 9 - Acti 9 A9F44206

            What is the Code for a 2 Pole 32A C curve MCB rated at 6 kA ?

            Code = A9F44232

            What code is the Acti9 equivalent of the Merlin Gerin 25817?

            The Acti9 A9F44216 is a 2p 16A C curve 6kA MCB.
             

            Can the A9F44210 be used with 110v AC?

            Yes it can, the only difference between a 100v and 230v is that you will get 36kA breaking capacity as opposed to 20kA (230v).



             

            Is part number A9F44106 DC rated?

            Yes, part is DC rated up to 48 volts.

            What is the DC rating of A9F44210?

            Acti9 miniture circuit breakers, can handle upto 60VDC.

            What is the DC rating of A9F44210?

            Acti9 miniture circuit breakers, can handle upto 60VDC.

            What potentiometer should I use for ATV61?

            Schneider Electric part No. SZ1RV1202

            What is the part number for a 3 phase 20amp MCB/RCD combo?

            The part number for a 3 phase 20amp MCB/RCD combo is - A9F44320 & A9V02763

            For further information visit links below:-
            https://www.schneider-electric.com.au/en/search/A9F44320
            https://www.schneider-electric.com.au/en/search/A9V02763
            User-added image

            User-added image

            Data sheet for A9F54240 ?

            Data sheet attached

            What is the DC rating of the A9F44210?

            The DC rating of the Acti9 miniture circuit breakers is 60VDC.

            Please See attachment:
            Show More