Acti 9 iC60N 1P 1A…63A Miniature Circuit Breaker
Acti9 iDPN VigiARC - System Image - Closed - New Zealand
Acti 9 iC60N 1P 1A…63A Miniature Circuit Breaker
Acti9 iDPN VigiARC - System Image - Closed - New Zealand

Acti9 iC60N 1P, 16A, C Miniature Circuit Breaker

Catalogue Number: A9F44116
Acti 9 iC60N 1P 1A…63A Miniature Circuit Breaker
Acti9 iDPN VigiARC - System Image - Closed - New Zealand
Acti 9 iC60N 1P 1A…63A Miniature Circuit Breaker
Acti9 iDPN VigiARC - System Image - Closed - New Zealand
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range
Acti 9
Range of product
Acti 9
Product name
Disbo iC60
Product or component type
miniature circuit-breaker
Device short name
iC60N
Poles description
1P
Number of protected poles
1
[In] rated current
16 A
Network type
AC
Trip unit technology
thermal-magnetic
Curve code
C
Breaking capacity code
N
Breaking capacity
  • 15 kA Icu at 12...48 V DC conforming to EN/IEC 60947-2
  • 6 kA Icu at 72 V DC conforming to EN/IEC 60947-2
  • 6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
  • 36 kA Icu at 10...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
  • 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
  • 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
    • Utilisation category
      category A conforming to EN/IEC 60947-2
      Network frequency
      50/60 Hz
      [Ue] rated operational voltage
      240 V AC 50/60 Hz
      Magnetic tripping limit
      8 x In +/- 20 %
      [Ics] rated service breaking capacity
    • 27 kA 75 % conforming to EN/IEC 60947-2 - 10...60 V AC 50/60 Hz
    • 15 kA 75 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz
    • 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
    • 6000 A 100 % conforming to EN/IEC 60898-1 - 240 V AC 50/60 Hz
    • 15 kA 100 % conforming to EN/IEC 60947-2 - 12...48 V DC
    • 6 kA 100 % conforming to EN/IEC 60947-2 - 72 V DC
      • Limitation class
        3 conforming to EN/IEC 60947-2
        [Ui] rated insulation voltage
        500 V AC 50/60 Hz
        [Uimp] rated impulse withstand voltage
        6 kV conforming to EN/IEC 60947-2
        Contact position indicator
        yes
        Control type
        toggle
        Local signalling
        trip indicator
        Mounting mode
        clip-on
        Mounting support
        rail
        Connection pitch
        9 mm pitches
        2
        Height
        85 mm
        Width
        18 mm
        Depth
        78.5 mm
        Net weight
        0.125 kg
        Mechanical durability
        20000 cycles
        Electrical durability
        10000 cycles
        Provision for padlocking
        padlockable
        Connections - terminals
      • single terminal (top or bottom) 1-25 mm² rigid
      • single terminal (top or bottom) 1-16 mm² flexible
        • Wire stripping length
          14 mm for top or bottom connection
          Tightening torque
          2-2 N.m top or bottom
          Earth-leakage protection
          separate block
          Compatibility code
          iC60
          Standards
        • EN/IEC 60947-2
        • EN/IEC 60898-1
          • IP degree of protection
            IP20 conforming to IEC 60529
            Pollution degree
            3 conforming to EN/IEC 60947-2
            Tropicalisation
            2 conforming to IEC 60068-1
            Relative humidity
            95-95 % at 55-55 °C
            Ambient air temperature for operation
            -35-70 °C
            Ambient air temperature for storage
            -40-85 °C
            Sustainable offer status
            Green Premium product
            REACh Regulation
            Free of Substances of Very High Concern above the threshold
            REACh free of SVHC
            Yes
            EU RoHS Directive
            Compliant
            Toxic heavy metal free
            Yes
            Mercury free
            Yes
            RoHS exemption information
            Yes
            China RoHS Regulation
             Pro-active China RoHS declaration (out of China RoHS legal scope)
            Environmental Disclosure
            ENVPEP1409009EN
            WEEE
            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

            Frequently Asked Questions

            hide show

            Is part number A9F44106 DC rated?

            Yes, part is DC rated up to 48 volts.

            What is the code for a 10kA 16A 1p C Curve MCB?

             The code is A9F54116

            What code is the Acti9 equivalent of the Merlin Gerin 25817?

            The Acti9 A9F44216 is a 2p 16A C curve 6kA MCB.
             

            What is the Acti 9 substitute for the Multi 9 25807?

            The A9F44140 is the Acti 9 substitute.

            Please see the attached datasheet for further information on the A9F44140.

            What is the part number for a side mount auxiliary contact block to suit A9F44106 circuit breaker?

            Part number for the side mount auxiliar for the Acti 9 range of circuit breakers is A9A26924.
            See link for more details...
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9A26924

            User-added image

            what is size of the Cable that will fit into the MCB A9F54106 ?

            Cable = 25mm stranded
             

            What is a 2pole, 6A, C Curve, 6kA circuit breaker

             Part code 25815 Multi 9 - Acti 9 A9F44206

            What is the alternative Acti 9 part code for the discontinued Multi 9 24674?

            The alternative Acti 9 conversion is the A9F45316   3 Pole 16A 6kA MCB 

            Is there an alternative for a 1 module RCD-MCB part number 4RCBE116/30D?

            Yes, however it is larger in size as it requires 4 modules. The replacement part numbers are A9F55116 + A9V02663.

            What is the part number for 2 pole 25amp Acti 9 C/B?

            A9F44225

            Can the A9F44210 be used with 110v AC?

            Yes it can, the only difference between a 100v and 230v is that you will get 36kA breaking capacity as opposed to 20kA (230v).



             

            Do you have a C60H Circuit breaker single phase 10A?

            In the Schneider range we have the Acti 9 IC60H circuit breakers. The part number for a single phase, 10A is a A9F54110.

             

            Show More