Acti9 iC60H2 Earth Leakage Circuit Breaker, 2P, C Curve, 20A, 30mA, 110V

Acti9 iC60H2 Earth Leakage Circuit Breaker, 2P, C Curve, 20A, 30mA, 110V

Acti9 iC60H2 Earth Leakage Circuit Breaker, 2P, C Curve, 20A, 30mA, 110V

Item Number: A9D19220

Retail
$791.05
RRP (Inc. GST)

Product Dimensions

Width icon

Width36 mm

Height icon

Height110 mm

Depth icon

Depth75.5 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti 9

Range of product

Acti 9

Product or component type

residual current breaker with overcurrent protection (RCBO)

Sustainable offer status

Green Premium product

Physical

[In] rated current

20 A at 50 °C

[Ue] rated operational voltage

110 V AC 50/60 Hz

Control type

toggle

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

DIN rail

Height

110 mm

Width

36 mm

Depth

75.5 mm

Net weight

332 g

Mechanical durability

20000 cycles

Electrical durability

5000 cycles

Connections - terminals

  • screw clamp terminal (top) 1-25 mm² rigid without cable end
  • screw clamp terminal (top) 1-16 mm² flexible
  • screw clamp terminal (bottom) 1-16 mm² rigid without cable end
  • screw clamp terminal (bottom) 1-10 mm² flexible
    • Wire stripping length

    • power circuit: 13 mm for bottom connection
    • power circuit: 14 mm for top connection
      • Standards

      • IEC 61009-1
      • AS/NZS 61009.1
      • IEC 61009-2-2
        • IP degree of protection

          IP20

          Relative humidity

          95-95 % at 55-55 °C

          Ambient air temperature for operation

          -15-60 °C

          Ambient air temperature for storage

          -40-85 °C

          EU RoHS Directive

          Compliant

          Mercury free

          Yes

          RoHS exemption information

          Yes

          China RoHS Regulation

          Product out of China RoHS scope. Substance declaration for your information

          Environmental Disclosure

          ENVPEP121008EN

          Circularity Profile

          ENVEOLI121005EN

          Others

          Circuit breaker application

          distribution

          Product name

          Acti 9 iC60 RCBO

          Device short name

          iC60H2 RCBO

          Poles description

          2P

          Earthing system

        • TN
        • IT
        • TT
          • Curve code

            C

            Earth-leakage sensitivity

            30 mA

            Breaking capacity

            10000 A Icn at 110 V AC 50/60 Hz

            Neutral position

            left

            Number of protected poles

            1

            Device location in system

            outgoer

            Network type

            AC

            Network frequency

            50 Hz

            Trip unit technology

            thermal-magnetic

            Breaking capacity code

            H2

            Residual current tripping technology

            voltage dependent

            Earth-leakage protection time delay

            instantaneous

            Earth-leakage protection class

            type A

            [Icw] rated short-time withstand current

            Icw: 250 A during 8/20 µs impulse withstand

            [Ics] rated service breaking capacity

            7500 A at 110 V AC 50/60 Hz

            Limitation class

            3

            [Ui] rated insulation voltage

            400 V AC 50/60 Hz

            [Uimp] rated impulse withstand voltage

            4 kV

            Surge current

            250 A

            Suitability for isolation

            yes

            Contact position indicator

            yes

            Comb busbar and distribution block compatibility

            NO

            9 mm pitches

            4

            Provision for padlocking

            padlockable with padlock Ø 4 mm

            Locking options description

            ON/OFF locking facilities

            Tightening torque

          • power circuit: 3.5-3.5 N.m top
          • power circuit: 2-2 N.m bottom
            • Earth-leakage protection

              integrated

              Tropicalisation

              2

              Package 1 Weight

              310 g

              Package 1 Height

              75 mm

              Package 1 width

              95 mm

              Package 1 Length

              18 mm

              WEEE

              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
              Show all specifications

              Documents & downloads

              hide show

              Frequently Asked Questions

              hide show

              What is the replacement part for a 26896 RCB?

              The replacement part is a A9D61820.
              A9D11220 is best solution
              A9D11820 is an alternative 1 pole wide but no Neutral switching
              A9D61820 is an alternative 1 pole wide but no Neutral switching and only 6kA
               

              What is the alternative to the 4RCBE210/30?

              Within the Schneider Electric range, the alternative for the 4RCBE210/30 is A9D11210

              What is the difference between the A9D73620 and A9D32620 RCBO's?

              The A9D73620 is the slimline RCBO which is the same rating and does the same as the A9D32620. It is just the physical size that is different.

              What is the part number for 2 pole 16amp RCBO 2 modules wide?

              The part name is A9D11216

              What is the code for a 20A 10mA RCBO

              The code is A9D40620

              What are the codes for a 20A 10mA 1pole rcbo ?

              4rcbe220/10
              or
              A9D40620
              Show More