Quantcast

Acti 9 iC60H Earth Leakage Circuit Breaker, 1P + N, C Curve, 45A, 100 mA, 240V

Acti 9 iC60H Earth Leakage Circuit Breaker, 1P + N, C Curve, 45A, 100 mA, 240V

Acti 9 iC60H Earth Leakage Circuit Breaker, 1P + N, C Curve, 45A, 100 mA, 240V

Item Number: A9D12845

Retail
$619.45
RRP (Inc. GST)

Product Dimensions

Width icon

Width18 mm

Height icon

Height110 mm

Depth icon

Depth77.5 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti 9

Range of product

Acti 9

Product or component type

residual current breaker with overcurrent protection (RCBO)

Sustainable offer status

Green Premium product

Physical

[In] rated current

45 A at 50 °C

[Ue] rated operational voltage

240 V AC 50/60 Hz

Control type

toggle

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

DIN rail

Height

110 mm

Width

18 mm

Depth

77.5 mm

Net weight

205 g

Mechanical durability

20000 cycles

Electrical durability

5000 cycles

Connections - terminals

  • screw clamp terminal (top) 1-25 mm² rigid without cable end
  • screw clamp terminal (top) 1-16 mm² flexible
  • screw clamp terminal (bottom) 1-16 mm² rigid without cable end
  • screw clamp terminal (bottom) 1-10 mm² flexible
    • Wire stripping length

    • power circuit: 13 mm for bottom connection
    • power circuit: 14 mm for top connection
      • Standards

      • BS EN 61009-1
      • AS/NZS 61009.1
      • IEC 61009-1
      • IEC 61009-2-2
        • IP degree of protection

          IP20

          Relative humidity

          95-95 % at 55-55 °C

          Ambient air temperature for operation

          -15-60 °C

          Ambient air temperature for storage

          -40-85 °C

          REACh Regulation

          Free of Substances of Very High Concern above the threshold

          EU RoHS Directive

          Compliant

          Mercury free

          Yes

          RoHS exemption information

          Yes

          China RoHS Regulation

          Product out of China RoHS scope. Substance declaration for your information

          Environmental Disclosure

          ENVPEP121008EN

          Circularity Profile

          ENVEOLI121005EN

          Others

          Number of Units in Package 1

          1

          Number of Units in Package 2

          34

          Package 1 width

          9.5 cm

          Package 2 Height

          15 cm

          Package 2 Length

          40 cm

          Package 1 Height

          7.5 cm

          Package 1 Length

          1.8 cm

          Package 2 width

          30 cm

          Unit Type of Package 1

          PCE

          Unit Type of Package 2

          S02

          Circuit breaker application

          distribution

          Product name

          Acti 9 iC60 RCBO

          Device short name

          iC60H RCBO

          Poles description

          1P + N

          Earthing system

          TN

          Curve code

          C

          Earth-leakage sensitivity

          100 mA

          Breaking capacity

          10000 A Icn at 240 V AC 50/60 Hz

          Neutral position

          left

          Number of protected poles

          1

          Device location in system

          outgoer

          Network type

          AC

          Network frequency

          50 Hz

          Trip unit technology

          thermal-magnetic

          Breaking capacity code

          H

          Residual current tripping technology

          voltage dependent

          Earth-leakage protection time delay

          instantaneous

          Earth-leakage protection class

          type A

          [Icw] rated short-time withstand current

          Icw: 250 A during 8/20 µs impulse withstand

          [Ics] rated service breaking capacity

          7500 A at 240 V AC 50/60 Hz

          Limitation class

          3

          [Ui] rated insulation voltage

          400 V AC 50/60 Hz

          [Uimp] rated impulse withstand voltage

          4 kV

          Surge current

          250 A

          Suitability for isolation

          yes

          Contact position indicator

          yes

          Comb busbar and distribution block compatibility

          NO

          9 mm pitches

          2

          Provision for padlocking

          padlockable with padlock Ø 4 mm

          Locking options description

          ON/OFF locking facilities

          Tightening torque

        • power circuit: 3.5-3.5 N.m top
        • power circuit: 2-2 N.m bottom
          • Earth-leakage protection

            integrated

            Tropicalisation

            2

            Package 1 Weight

            211 g

            Package 2 Weight

            8.794 kg

            WEEE

            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
            Show all specifications

            Frequently Asked Questions

            hide show

            What is the part number for a 45amp chassis style RCD/MCB combo C/B?

            The part number for a 45amp chassis style RCD/MCB combo C/B is - 6kA - A9D61845 , 10kA - A9D11845
            For further information, visit the link below:-
            https://www.schneider-electric.com.au/en/search/A9D61845
            https://www.schneider-electric.com.au/en/search/A9D11845
            User-added image
            User-added image

            What is the part number for an A9D11810 but in "D" curve?

            need to build up with "D" curve circuit breaker A9F55110 and vigi unit A9V02663
            for more details see ....... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F55110
            and ............... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9V02663
            User-added image    User-added image

            What is the replacement part for a 26896 RCB?

            The replacement part is a A9D61820.
            A9D11220 is best solution
            A9D11820 is an alternative 1 pole wide but no Neutral switching
            A9D61820 is an alternative 1 pole wide but no Neutral switching and only 6kA
             

            What is the difference between A9D32620 and A9D33620 RCBO Acti 9 devices?

             
             

            A9D33620 = SI (Super Immunised)
            A9D32620 = Type A (AC or pulsating DC)

            Type A RCBO = Tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents, whether suddenly applied or slowly rising.
            Type Si RCBO = With all the features of a Type A device, “Si” type Super Immunised earth leakage protection range has been specially developed to be used with loads or in environments causing disturbances. Examples are lightning or switching surges, harmonics generated by increasing number of loads and constant load leakage current from electronic ballasts, speed drives, computers, etc. The Si increases safety and allows improved continuity of supply.
             

            Why is the background image visible in Vista, but it does not show up in Diagrams?

            Issue
            The background image of a diagram is working correctly in Vista, but when viewed in Web Applications (Diagrams), the background is blank.

            Product Line
            StruxureWare Power Monitoring (SPM) 7.X

            Environment
            Web Applications (WebReach) Diagrams

            Cause
            This behavior can be observed when there are special characters in the image file name.

            Resolution
            Rename the image file, while ensuring to remove any special characters. 

            For example, an image filename may have an "&" symbol in it: “R&D Device.bmp".
            This could be changed to “RandD_Device.bmp”

            What is the part number for a 20A 10mA RCBO?

            The part number for a 20A 10mA RCBO is A9D10820 or  4RCBE220/10S
            A9D10820 will fit 
             Schneider chassis but cannot not be used for hospitals or body protected areas as it does not switch neutral.
            The Clipsal 4RCBE220/10S is suitable for hospitals but will not fit to Schneider chassis.
             
            A9D10820 Product picture
            A9D10820    iC60H - earth leakage circuit breaker
            1P + N - C curve - 20 A - 10 mA - 240 V
            4RCBE220/10S        SLIM CLIPSAL
            20A 10mA A-TYPE 6KA

            For more information see :
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9D10820
            https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RCBE220/10S
            Show More