iC60H RCBO 1P+N 6A�45A 30/100mA with overcurrent protection

Acti 9 iC60H Earth Leakage Circuit Breaker, 1P + N, C Curve, 25A, 100mA, 240V

Catalogue Number: A9D12825
iC60H RCBO 1P+N 6A�45A 30/100mA with overcurrent protection
Retail
$619.45
RRP (Inc. GST)

Specifications

hide show
Circuit breaker application
distribution
Range
Acti 9
Range of product
Acti 9
Product name
Acti 9 iC60 RCBO
Product or component type
residual current breaker with overcurrent protection (RCBO)
Device short name
iC60H RCBO
Poles description
1P + N
[In] rated current
25 A at 50 °C
Earthing system
TN
Curve code
C
Earth-leakage sensitivity
100 mA
Breaking capacity
10000 A Icn at 240 V AC 50/60 Hz
Neutral position
left
Number of protected poles
1
Device location in system
outgoer
Network type
AC
Network frequency
50 Hz
[Ue] rated operational voltage
240 V AC 50/60 Hz
Trip unit technology
thermal-magnetic
Breaking capacity code
H
Residual current tripping technology
voltage dependent
Earth-leakage protection time delay
instantaneous
Earth-leakage protection class
type A
[Icw] rated short-time withstand current
Icw: 250 A during 8/20 µs impulse withstand
[Ics] rated service breaking capacity
7500 A at 240 V AC 50/60 Hz
Limitation class
3
[Ui] rated insulation voltage
400 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
4 kV
Surge current
250 A
Suitability for isolation
yes
Contact position indicator
yes
Control type
toggle
Local signalling
ON/OFF indication
Mounting mode
clip-on
Mounting support
DIN rail
Comb busbar and distribution block compatibility
NO
9 mm pitches
2
Height
110 mm
Width
18 mm
Depth
77.5 mm
Net weight
205 g
Mechanical durability
20000 cycles
Electrical durability
5000 cycles
Provision for padlocking
padlockable with padlock Ø 4 mm
Locking options description
ON/OFF locking facilities
Connections - terminals
  • screw clamp terminal (top) 1-25 mm² rigid without cable end
  • screw clamp terminal (top) 1-16 mm² flexible
  • screw clamp terminal (bottom) 1-16 mm² rigid without cable end
  • screw clamp terminal (bottom) 1-10 mm² flexible
    • Wire stripping length
    • power circuit: 13 mm for bottom connection
    • power circuit: 14 mm for top connection
      • Tightening torque
      • power circuit: 3.5-3.5 N.m top
      • power circuit: 2-2 N.m bottom
        • Earth-leakage protection
          integrated
          Standards
        • IEC 61009-2-2
        • BS EN 61009-1
        • IEC 61009-1
        • AS/NZS 61009.1
          • IP degree of protection
            IP20
            Tropicalisation
            2
            Relative humidity
            95-95 % at 55-55 °C
            Ambient air temperature for operation
            -15-60 °C
            Ambient air temperature for storage
            -40-85 °C
            Package 1 Weight
            211 g
            Package 1 Height
            75 mm
            Package 1 width
            95 mm
            Package 1 Length
            18 mm
            Sustainable offer status
            Green Premium product
            EU RoHS Directive
            Compliant
            Mercury free
            Yes
            RoHS exemption information
            Yes
            China RoHS Regulation
            Product out of China RoHS scope. Substance declaration for your information
            Environmental Disclosure
            ENVPEP121008EN
            Circularity Profile
            ENVEOLI121005EN
            WEEE
            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

            Documents & downloads

            hide show
            Filter items
            • All

            • Product Brochures

            • CAD Files and Packs

            • Technical Data Catalogues

            • Installation Instruction

            • Product Environmental

            • End of Life Manual

            • Certificates (MSDS)

            • Declaration of Conformity

            Frequently Asked Questions

            hide show

            What is the replacement part for a 26896 RCB?

            The replacement part is a A9D61820.
            A9D11220 is best solution
            A9D11820 is an alternative 1 pole wide but no Neutral switching
            A9D61820 is an alternative 1 pole wide but no Neutral switching and only 6kA
             

            What is the difference between A9D32620 and A9D33620 RCBO Acti 9 devices?

             
             

            A9D33620 = SI (Super Immunised)
            A9D32620 = Type A (AC or pulsating DC)

            Type A RCBO = Tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents, whether suddenly applied or slowly rising.
            Type Si RCBO = With all the features of a Type A device, “Si” type Super Immunised earth leakage protection range has been specially developed to be used with loads or in environments causing disturbances. Examples are lightning or switching surges, harmonics generated by increasing number of loads and constant load leakage current from electronic ballasts, speed drives, computers, etc. The Si increases safety and allows improved continuity of supply.
             

            What is the part number for an A9D11810 but in "D" curve?

            need to build up with "D" curve circuit breaker A9F55110 and vigi unit A9V02663
            for more details see ....... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F55110
            and ............... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9V02663
            User-added image    User-added image

            What is the difference between the A9D73620 and A9D32620 RCBO's?

            The A9D73620 is the slimline RCBO which is the same rating and does the same as the A9D32620. It is just the physical size that is different.

            What is the part number for a 45amp chassis style RCD/MCB combo C/B?

            The part number for a 45amp chassis style RCD/MCB combo C/B is - 6kA - A9D61845 , 10kA - A9D11845
            For further information, visit the link below:-
            https://www.schneider-electric.com.au/en/search/A9D61845
            https://www.schneider-electric.com.au/en/search/A9D11845
            User-added image
            User-added image

            Where can I find the CAD drawing for 140XCP40100?

            Issue:
            Where can I find the CAD drawing for 140XCP40100?

            Product Line:
            Quantum, 140CPU

            Resolution:
            There are currently no CAD drawings available for the 140XCP40100.

            However, all classic "1 slot" quantum modules share the same dimensions once the terminal block is inserted.


             

            Why can't I acknowledge alarms from the Global Event Viewer in Vista in StruxureWare Power Monitoring 7.0?

            From the StruxureWare Power Monitoring 7.0.1 User Guide:
            Acknowledging Alarms
            The alarm acknowledgement function is now available only in the Alarms application in the Web Applications component. See the online help for the Alarms for information about acknowledging alarms.
            Every type of event has a prioritized value that identifies its relative significance on a scale of 0 (zero) to 255. By default, Vista identifies any event with a priority of 128 (default) or greater as an alarm.

            Keywords: SPM, PME, Power Monitoring Expert, SPM7, AAV, active alarms viewer, cannot acknowledge all, disabled


            Legacy KB System (APS) Data: RESL210004 V1.0, Originally authored by AnVa on 12/13/2012, Last Edited by AnVa on 12/13/2012
            Related ranges: Power Monitoring 7.0

            Which RCBO can ben used in hospitals?

            The only range of RCBO's that can be used in hospitals are:
            Electronic Models -
            4RCBE206/10 4RCBE206/10S
            4RCBE210/10  4RCBE210/10S
            4RCBE220/10 4RCBE220/10S
            4RCBE225/10 4RCBE225/10S
            4RCBE232/10 4RCBE232/10S
            4RCBE240/10  

            Unfortunately you cannot use Schneider A9D108** range as it doesnt switch the neutral.


            For further information see attached PDF or visit https://www.clipsal.com/Trade/search-results?q=4RCBE%20range&t=documentation



             

            Can an AFDD replace an earth leakage current protection device?

            The new AFDD comes with different versions:
            - Without a protection against earth leakage current (Catalogue No. A9TS1225 for commercial applications). In this case, AFDD, can help to provide a protection against arc faults (serial arc faults, parallel arc faults and arc to earth). Indeed, even if it helps to protect against electrical arcs between phase and earth, because of its design and technology, monitoring and protection provided by arc detectors is not equivalent to the one provided by a traditional earth leakage protection device.
            - With a protection against earth leakage current. All Clipsal branded AFDD references for residential applications and remaining Schneider branded AFDD references for commercial applications come with protection against earth leakage current. in this case AFDD can provide a combined protection against overcurrent, overvoltage, arc faults (serial arc fault, parallel arc fault and arc to earth) and earth leakage.