Quantcast

Acti 9 iC60H2, Earth Leakage Circuit Breaker, 2P, C Curve, 32A, 30mA, 240V

Acti 9 iC60H2, Earth Leakage Circuit Breaker, 2P, C Curve, 32A, 30mA, 240V

Acti 9 iC60H2, Earth Leakage Circuit Breaker, 2P, C Curve, 32A, 30mA, 240V

Item Number: A9D11232

Retail
$712.18
RRP (Inc. GST)

Product Dimensions

Width icon

Width36 mm

Height icon

Height110 mm

Depth icon

Depth75.5 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti 9

Range of product

Acti 9

Product or component type

residual current breaker with overcurrent protection (RCBO)

Sustainable offer status

Green Premium product

Physical

[In] rated current

32 A at 50 °C

[Ue] rated operational voltage

240 V AC 50/60 Hz

Control type

toggle

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

DIN rail

Height

110 mm

Width

36 mm

Depth

75.5 mm

Net weight

332 g

Mechanical durability

20000 cycles

Electrical durability

5000 cycles

Connections - terminals

  • screw clamp terminal (top) 1-25 mm² rigid without cable end
  • screw clamp terminal (top) 1-16 mm² flexible
  • screw clamp terminal (bottom) 1-16 mm² rigid without cable end
  • screw clamp terminal (bottom) 1-10 mm² flexible
    • Wire stripping length

    • power circuit: 13 mm for bottom connection
    • power circuit: 14 mm for top connection
      • Standards

      • AS/NZS 61009.1
      • IEC 61009-1
      • IEC 61009-2-2
        • IP degree of protection

          IP20

          Relative humidity

          95-95 % at 55-55 °C

          Ambient air temperature for operation

          -15-60 °C

          Ambient air temperature for storage

          -40-85 °C

          REACh Regulation

          Free of Substances of Very High Concern above the threshold

          EU RoHS Directive

          Compliant

          Mercury free

          Yes

          RoHS exemption information

          Yes

          China RoHS Regulation

          Product out of China RoHS scope. Substance declaration for your information

          Environmental Disclosure

          ENVPEP121008EN

          Circularity Profile

          ENVEOLI121005EN

          Others

          Circuit breaker application

          distribution

          Product name

          Acti 9 iC60 RCBO

          Device short name

          iC60H2 RCBO

          Poles description

          2P

          Earthing system

        • TT
        • IT
        • TN
          • Curve code

            C

            Earth-leakage sensitivity

            30 mA

            Breaking capacity

            10000 A Icn at 240 V AC 50/60 Hz

            Neutral position

            left

            Number of protected poles

            2

            Device location in system

            outgoer

            Network frequency

            50 Hz

            Network type

            AC

            Trip unit technology

            thermal-magnetic

            Breaking capacity code

            H2

            Residual current tripping technology

            voltage dependent

            Earth-leakage protection time delay

            instantaneous

            Earth-leakage protection class

            type A

            [Icw] rated short-time withstand current

            Icw: 250 A during 8/20 µs impulse withstand

            [Ics] rated service breaking capacity

            7500 A at 240 V AC 50/60 Hz

            Limitation class

            3

            [Ui] rated insulation voltage

            400 V AC 50/60 Hz

            [Uimp] rated impulse withstand voltage

            4 kV

            Surge current

            250 A

            Suitability for isolation

            yes

            Contact position indicator

            yes

            Comb busbar and distribution block compatibility

            NO

            9 mm pitches

            4

            Provision for padlocking

            padlockable with padlock Ø 4 mm

            Locking options description

            ON/OFF locking facilities

            Tightening torque

          • power circuit: 3.5-3.5 N.m top
          • power circuit: 2-2 N.m bottom
            • Earth-leakage protection

              integrated

              Tropicalisation

              2

              Package 1 Weight

              318 g

              Package 1 Height

              75 mm

              Package 1 width

              95 mm

              Package 1 Length

              18 mm

              WEEE

              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

              Halogen content performance

              Halogen free plastic parts product
              Show all specifications