Quantcast

Acti 9 iC60H Ti24, 40A, 4P, Curve C, Integrated Control MCB

Acti 9 iC60H Ti24, 40A, 4P, Curve C, Integrated Control MCB

Acti 9 iC60H Ti24, 40A, 4P, Curve C, Integrated Control MCB

Item Number: A9C65440

Retail
$2,493.33
RRP (Inc. GST)

Product Dimensions

Width icon

Width117 mm

Height icon

Height84 mm

Depth icon

Depth77 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Market segment

  • small commercial
  • residential
    • Device application

    • control
    • distribution
      • Range

        Acti 9

        Range of product

        Reflex iC60

        Product or component type

        integrated control circuit breaker

        Product compatibility

        with PLC

        Sustainable offer status

        Green Premium product

        Warranty

        18 months

        Physical

        [In] rated current

        40 A

        Control type

      • remote control by pulse
      • ON/OFF button
      • remote control by continuous command
      • toggle
        • Control signal type

        • impulse
        • maintained very low voltage
        • maintained
          • Local signalling

          • red LED: fault
          • green LED: device ON
          • flashing LED: device ready
          • flashing LED: device overheat
          • flashing LED: device tripped
            • Mounting mode

              fixed

              Mounting support

              35 mm symmetrical DIN rail

              Height

              84 mm

              Width

              117 mm

              Depth

              77 mm

              Mechanical durability

              50000 cycles

              Electrical durability

              AC-1: 50000 cycles AC 50 Hz

              IP degree of protection

              IP20 conforming to IEC 60529

              Relative humidity

              93-93 % at 40-40 °C

              REACh Regulation

              Free of Substances of Very High Concern above the threshold

              EU RoHS Directive

              Compliant

              Mercury free

              Yes

              RoHS exemption information

              Yes

              China RoHS Regulation

              Product out of China RoHS scope. Substance declaration for your information

              Environmental Disclosure

              ENVPEP110722EN

              Circularity Profile

              ENVEOLI1107022EN

              Others

              Product name

              Reflex iC60

              Device short name

              Reflex iC60H

              Poles description

              4P

              Number of protected poles

              4

              Network type

              AC

              Trip unit technology

              thermal-magnetic

              Curve code

              C

              Network frequency

              50/60 Hz

              Breaking capacity code

              H

              Breaking capacity

            • 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
            • 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
              • [Ui] rated insulation voltage

                500 V AC

                Contact position indicator

                yes

                [Uc] control circuit voltage

              • 230 V AC 50/60 Hz
              • 24 V AC 50/60 Hz
              • 48 V AC 50/60 Hz
              • 24 V DC
              • 48 V DC
                • [Us] rated supply voltage

                  230 V AC at 50/60 Hz

                  9 mm pitches

                  13

                  Provision for padlocking

                  padlockable

                  Locking options description

                  padlock in OFF position

                  Earth-leakage protection

                  separate block

                  Compatibility code

                  Reflex_iC60

                  Pollution degree

                  3

                  Tropicalisation

                  2

                  Unit Type of Package 1

                  PCE

                  Number of Units in Package 1

                  1

                  Package 1 Weight

                  880 g

                  Package 1 Height

                  9 cm

                  Package 1 width

                  11.2 cm

                  Package 1 Length

                  16.5 cm

                  Unit Type of Package 2

                  S03

                  Number of Units in Package 2

                  14

                  Package 2 Weight

                  12.454 kg

                  Package 2 Height

                  30 cm

                  Package 2 width

                  30 cm

                  Package 2 Length

                  40 cm

                  WEEE

                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                  Halogen content performance

                  Halogen free plastic parts product
                  Show all specifications

                  Documents & downloads

                  hide show
                  Filter items
                  • All

                  • CAD Files and Packs

                  • Product Brochures

                  • Technical Data Catalogues

                  • Installation Instruction

                  • Operating Manuals

                  • Certificates (MSDS)

                  • Declaration of Conformity

                  Frequently Asked Questions

                  hide show

                  What is the replacement code for a Merlin Gerin 23332 ?.

                  The current equivalent is the A9R91440

                  What is kA rating for A9R91440 ?

                  The A9R91440 is Rated 10kA

                   

                  What protective devices are required for EV Chargers?

                  Protective devices which are required for EV chargers can be either RCBO or MCB+RCCB. 

                  For 1P 16A  => 3,7Kw load    protection devices = 20A curve C + type B 30mA ( A9F54220 + A9Z51240)
                  For 1P 32A  => 7Kw load       protection devices = 40A curve C + type B 30mA  ( A9F54240 + A9Z51240)
                  For 3P 16A  => 11Kw load     protection devices = 20A curve C + type B 30mA  ( A9F54420 + A9Z51440)
                  For 3P 32A  => 22Kw load     protection devices = 40A curve C + type B 30mA  ( A9F54440 + A9Z51440)

                  The circuit breaker value (20A or 40A) depends on the cable size, length and environmental parameters (up to the electrician)
                  For further information see:https://www.se.com/au/en/product-subcategory/80408-evlink-charging-station/


                   

                  What are the codes of the items supplied with the 3 phase EV parking protection kits?

                  Parts that should be supplied as follows:

                  KITPARKING22-1:
                  A9F54440 x 1, MCB, iC60H 4P 40A C Curve
                  A9Z51440 x 1, RCD, iIDP 4P 40A 30mA Type B, 400V
                  A9A26969 x 2, Under voltage release, iMNX 220 240VAC
                  A9F44204 x 1, MCB, iC60N 2P 4A C Curve
                  A9R91240 x 1, RCCB, iID 2P 40A 30mA Type Asi
                  A9A26924 x 2, Aux contact, iOF 240 415VAC 24 130VDC

                  KITPARKING22-2:
                  A9F54440 x 2, MCB, iC60H 4P 40A C Curve
                  A9Z51440 x 2, RCD, iIDP 4P 40A 30mA Type B, 400V
                  A9A26969 x 3, Under voltage release, iMNX 220 240VAC
                  A9F44204 x 1, MCB, iC60N 2P 4A C Curve
                  A9R91240 x 1, RCCB, iID 2P 40A 30mA Type Asi
                  A9A26924 x 4, Aux contact, iOF 240 415VAC 24 130VDC
                   

                  Data sheet for A9F54240 ?

                  Data sheet attached

                  What is the replacement for the Merlin Gerin 23332?

                  A9R91440
                  Show More