PB115440.eps
Reflex iC60H Ti24 3P; integrated control MCB
PB115440.eps
Reflex iC60H Ti24 3P; integrated control MCB

Acti 9 iC60H Ti24, 25A, 3P, Curve C, Integrated Control MCB

Catalogue Number: A9C65325
PB115440.eps
Reflex iC60H Ti24 3P; integrated control MCB
PB115440.eps
Reflex iC60H Ti24 3P; integrated control MCB
Retail
$1490.43*
RRP (Inc. GST)

Specifications

hide show
Device application
  • control
  • distribution
    • Range
      Acti 9
      Range of product
      Reflex iC60
      Product name
      Reflex iC60
      Device short name
      Reflex iC60H
      Product or component type
      integrated control circuit breaker
      Poles description
      3P
      Number of protected poles
      3
      Network type
      AC
      Trip unit technology
      thermal-magnetic
      Curve code
      C
      [In] rated current
      25 A
      Network frequency
      50/60 Hz
      Breaking capacity code
      H
      Breaking capacity
    • 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
    • 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
      • [Ui] rated insulation voltage
        500 V AC
        Contact position indicator
        yes
        Control type
      • ON/OFF button
      • toggle
      • remote control by continuous command
      • remote control by pulse
        • Control signal type
        • maintained
        • maintained very low voltage
        • impulse
          • Local signalling
          • flashing LED: device ready
          • green LED: device ON
          • flashing LED: device tripped
          • red LED: fault
          • flashing LED: device overheat
            • [Uc] control circuit voltage
            • 230 V AC 50/60 Hz
            • 24 V AC 50/60 Hz
            • 48 V AC 50/60 Hz
            • 24 V DC
            • 48 V DC
              • [Us] rated supply voltage
                230 V AC at 50/60 Hz
                Mounting mode
                fixed
                Mounting support
                35 mm symmetrical DIN rail
                9 mm pitches
                11
                Height
                84 mm
                Width
                99 mm
                Depth
                77 mm
                Mechanical durability
                50000 cycles
                Electrical durability
                AC-1: 50000 cycles AC 50 Hz
                Provision for padlocking
                padlockable
                Locking options description
                padlock in OFF position
                Earth-leakage protection
                separate block
                Product compatibility
                with PLC
                Compatibility code
                Reflex_iC60
                IP degree of protection
                IP20 conforming to IEC 60529
                Pollution degree
                3
                Tropicalisation
                2
                Relative humidity
                93-93 % at 40-40 °C
                Sustainable offer status
                Green Premium product
                REACh Regulation
                Free of Substances of Very High Concern above the threshold
                EU RoHS Directive
                Compliant
                Mercury free
                Yes
                RoHS exemption information
                Yes
                China RoHS Regulation
                Product out of China RoHS scope. Substance declaration for your information
                Environmental Disclosure
                ENVPEP110722EN
                Circularity Profile
                ENVEOLI1107022EN
                WEEE
                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                Warranty
                18 months

                Documents & downloads

                hide show
                Filter items
                • All

                • CAD Files and Packs

                • Product Brochures

                • Technical Data Catalogues

                • Installation Instruction

                • Operating Manuals

                • Certificates (MSDS)

                • Declaration of Conformity

                Frequently Asked Questions

                hide show

                What is the part number for a 25A 3 phase D curve breaker?

                The part name is A9F55325

                What is the replacement for Merlin Gerin 15322 ?

                A9A15322

                What is the part number for 20A 10kA D curve 3 pole circuit breaker?

                The part number for 20A 10kA D curve 3 pole circuit breaker is A9F55320.

                What is the part number for a 1 pole 25amp D-Curve RCBO?

                The part number for a 1 pole 25amp D-Curve RCBO is - A9F55125 & A9V02663

                For further information , visit link below:-
                https://www.schneider-electric.com.au/en/search/A9F55125
                https://www.schneider-electric.com.au/en/search/A9V02663
                User-added image

                User-added image

                Database Manager Not Responding After Running a Trim or Archive Job

                Issue:
                When running an archive or trim task in Database Manager, the manger will return a "Not Responding" state (see picture below). 



                Product:
                PME 8.X, PME7.2

                Environment:
                Database Management 

                Cause:
                This issue is caused when an archive or trim of a large portion of the database is selected. Which can arise when you selected a large time frame as the start and stop date. 

                Resolution:
                Although an error is displayed, do not exit the manager. The job is still running in the background. You can check that the manager is still running by going to Drive:\Program Files X86\Power Monitoring Expert\Database and looking at the ION_Data.mdf file. You will see this file growing as the manager runs.