iETL32A extension for impulse relay 1NO

Acti9 Extension ETL iTL 32, 1P, 1NO, 32A, Coil 110VDC, 230...240VAC, 50/60Hz

Catalogue Number: A9C32836
iETL32A extension for impulse relay 1NO
Retail
$158.96*
RRP (Inc. GST)

Specifications

hide show
Range of product
iTL
Range
Acti 9
Product or component type
extension for impulse relay
Device short name
iETL iTL 32
Relay application
remote control
Poles description
1P
Pole contact composition
1 NO
[In] rated current
32 A
Network type
AC
Network frequency
50/60 Hz
[Ue] rated operational voltage
415 V AC 50/60 Hz
Control type
  • toggle
  • remote control
    • Control signal type
      impulse
      Switching frequency
      5 switching operations/minute
      Impulse duration
      50 ms
      Remote control type
      illuminated push-button 3 mA
      Local signalling
      ON/OFF indication
      [Uc] control circuit voltage
    • 230...240 V AC 50/60 Hz
    • 110 V DC
      • Supply inrush power
        19 VA
        Mounting mode
        fixed, on right side of TL
        Mounting support
        35 mm symmetrical DIN rail
        9 mm pitches
        2
        Height
        60 mm
        Width
        18 mm
        Depth
        84 mm
        Electrical durability
      • AC-21: 50000 cycles
      • AC-22: 20000 cycles
        • Connections - terminals
          tunnel type terminals - <= 10 mm²
          Range compatibility
          Acti 9 iTL iTL
          Product compatibility
          iTL 32A
          Market segment
        • small commercial
        • residential
          • Compatibility code
            iETL iTL 32
            Standards
          • EN 669-1
          • EN 669-2-2
            • Noise level
              60 dB
              IP degree of protection
              IP20 conforming to IEC 60529
              Pollution degree
              3
              Tropicalisation
              2 conforming to IEC 60068-1
              Relative humidity
              95-95 % at 55-55 °C
              Ambient air temperature for operation
              -20-50 °C
              Ambient air temperature for storage
              -40-70 °C
              Sustainable offer status
              Green Premium product
              REACh Regulation
              Free of Substances of Very High Concern above the threshold
              REACh free of SVHC
              Yes
              EU RoHS Directive
              Compliant
              Mercury free
              Yes
              RoHS exemption information
              Yes
              China RoHS Regulation
              Product out of China RoHS scope. Substance declaration for your information
              Environmental Disclosure
              ENVPEP110302EN
              WEEE
              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
              Warranty
              18 months

              Documents & downloads

              hide show
              Filter items
              • All

              • Product Brochures

              • Technical Data Catalogues

              • Product Environmental

              • Declaration of Conformity

              Frequently Asked Questions

              hide show

              what is the Acti 9 code for Merlin Gerin 15515?

              A9C30831 is the Acti9 code for the 1P 1NO 32A 230v AC impulse relay.

              What is the difference between A9D32620 and A9D33620 RCBO Acti 9 devices?

               
               

              A9D33620 = SI (Super Immunised)
              A9D32620 = Type A (AC or pulsating DC)

              Type A RCBO = Tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents, whether suddenly applied or slowly rising.
              Type Si RCBO = With all the features of a Type A device, “Si” type Super Immunised earth leakage protection range has been specially developed to be used with loads or in environments causing disturbances. Examples are lightning or switching surges, harmonics generated by increasing number of loads and constant load leakage current from electronic ballasts, speed drives, computers, etc. The Si increases safety and allows improved continuity of supply.
               

              What is the new code for 15963?

              new code is
              A9C20837

              what is new code for Merlin Gerin 15960 CT Contactor ?

              new code = A9C20736  iCT Contactor 25A 2NC AC7a rated 
               

              what is new alternative for Code 15961 ?

              Code = A9C20833

              New code for 15960?

              new code is
              A9C20736

              What is new code for 15961 contactor 3n/o 25amp?


              A9C20833 is the new code for this contactor