Acti 9 Contactor iCT, 3 Poles, 3 NO, 40A, 220..240VAC

Acti 9 Contactor iCT, 3 Poles, 3 NO, 40A, 220..240VAC

Acti 9 Contactor iCT, 3 Poles, 3 NO, 40A, 220..240VAC

Item Number: A9C20843

Retail
$386.98
RRP (Inc. GST)

Product Dimensions

Width icon

Width54 mm

Height icon

Height85 mm

Depth icon

Depth60 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

iCT

Range

Acti 9

Product or component type

contactor

Device application

motor-heating-lighting

Product compatibility

  • iACTs
  • iATEt
  • iACTc
  • iACTp
    • Market segment

    • residential
    • small commercial
      • Sustainable offer status

        Green Premium product

        Warranty

        18 months

        Physical

        [Ie] rated operational current

      • 40 A AC-7A
      • 15 A AC-7B
        • Control type

          remote control

          [Ue] rated operational voltage

          400 V AC 50 Hz

          Control signal type

          maintained

          Local signalling

          action indicator

          Mounting mode

          clip-on

          Mounting support

          35 mm symmetrical DIN rail

          Height

          85 mm

          Width

          54 mm

          Depth

          60 mm

          Mechanical durability

          1000000 cycles

          Electrical durability

        • 100000 cycles IEC/EN 61095 40 A 50 Hz AC-7A
        • 30000 cycles IEC/EN 61095 15 A 50 Hz AC-7B
        • 30000 cycles IEC/EN 61095 50 Hz AC-7C
        • 100000 cycles EN/IEC 60947-4-1 50 Hz AC-1
        • 30000 cycles EN/IEC 60947-4-1 50 Hz AC-3
        • 30000 cycles EN/IEC 60947-4-1 50 Hz AC-5a
        • 30000 cycles EN/IEC 60947-4-1 50 Hz AC-5b
          • Connections - terminals

          • control circuit: tunnel type terminals2 cable(s) 1.5-1.5 mm² rigid
          • control circuit: tunnel type terminals1 cable(s) 1.5-2.5 mm² rigid
          • power circuit: tunnel type terminals1 cable(s) 6-16 mm² flexible
          • power circuit: tunnel type terminals1 cable(s) 6-25 mm² rigid
          • control circuit: tunnel type terminals2 cable(s) 1.5-2.5 mm² flexible
            • Standards

              IEC/EN 61095

              IP degree of protection

              IP20

              Relative humidity

              95-95 % at 55-55 °C

              Ambient air temperature for operation

              -5-60 °C

              Ambient air temperature for storage

              -40-70 °C

              REACh free of SVHC

              Yes

              EU RoHS Directive

              Compliant

              Toxic heavy metal free

              Yes

              Mercury free

              Yes

              RoHS exemption information

              Yes

              China RoHS Regulation

               Pro-active China RoHS declaration (out of China RoHS legal scope)

              Environmental Disclosure

              ENVPEP110308EN

              Others

              Product name

              Acti 9 iCT

              Device short name

              iCT

              Poles description

              3P

              Pole contact composition

              3 NO

              Network type

              AC

              [Uc] control circuit voltage

              220...240 V AC 50 Hz

              Network frequency

              50 Hz

              Maximum power

              2.1 W at 400 V AC

              [Ui] rated insulation voltage

              500 V AC 50/60 Hz

              [Uimp] rated impulse withstand voltage

              4 kV

              Switching frequency

              100 switching operations/day

              Hold-in power consumption in VA

              6.5-6.5 VA

              Inrush power in VA

              53 VA

              9 mm pitches

              6

              Tightening torque

            • control circuit: 0.8-0.8 N.m
            • power circuit: 3.5-3.5 N.m
              • Compatibility code

                iCT

                Noise level

                30 dB

                Heat dissipation

                2.1-2.1 W at 50/60 Hz

                Pollution degree

                2

                Tropicalisation

              • 2 conforming to EN 60947-4-1
              • 2 conforming to EN 61095
              • 2 conforming to IEC 1095
                • Operating altitude

                  2000 m

                  Unit Type of Package 1

                  PCE

                  Number of Units in Package 1

                  1

                  Package 1 Weight

                  335 g

                  Package 1 Height

                  6 cm

                  Package 1 width

                  11 cm

                  Package 1 Length

                  12 cm

                  Unit Type of Package 2

                  BB1

                  Number of Units in Package 2

                  4

                  Package 2 Weight

                  1.434 kg

                  Package 2 Height

                  13 cm

                  Package 2 width

                  12 cm

                  Package 2 Length

                  25 cm

                  Unit Type of Package 3

                  S03

                  Number of Units in Package 3

                  24

                  Package 3 Weight

                  9.09 kg

                  Package 3 Height

                  30 cm

                  Package 3 width

                  30 cm

                  Package 3 Length

                  40 cm

                  WEEE

                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                  Show all specifications

                  Documents & downloads

                  hide show
                  Filter items
                  • All

                  • CAD Files and Packs

                  • Product Brochures

                  • Technical Data Catalogues

                  • Product Environmental

                  • Certificates (MSDS)

                  • Declaration of Conformity

                  Frequently Asked Questions

                  hide show

                  what is the Australian replacement for a A9C20663?

                  The replacement is a Acti 9 A9C20863

                  What is the part number for the auxiliary for A9C20843 contactor?

                  The part number for the auxiliary for A9C20843 contactor is A9C15914
                  For further information see:https://eshop.schneider-electric.com/product.aspx?prod_id=A9C15914&org=21&lang=1&dist=276&tab=0&ses_id=
                   

                  what is new alternative for Code 15961 ?

                  Code = A9C20833

                  What is the new code for 15963?

                  new code is
                  A9C20837

                  What is new code for 15961 contactor 3n/o 25amp?


                  A9C20833 is the new code for this contactor
                   

                  I am looking for a 50A rated range switch

                  You can use any switch and use this to switch a contactor at the board the ranfe / over switch becomes a control switch
                  The Isolation switch will be at the board.
                  The 63amp contractor code is A9C20862 this is a 2 pole contactor
                  The largest single pole contactor is 25 amps   

                   
                  Show More