Quantcast

Acti 9 Step by Step control Iatl5, 230VAC 50-60Hz

Acti 9 Step by Step control Iatl5, 230VAC 50-60Hz

Acti 9 Step by Step control Iatl5, 230VAC 50-60Hz

Item Number: A9C15412

Retail
$305.69
RRP (Inc. GST)

Product Dimensions

Width icon

Width36 mm

Height icon

Height86 mm

Depth icon

Depth71 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Acti 9

Range

Acti 9

Product or component type

step by stel control auxiliary

Product compatibility

  • iTL (32 A)
  • iTL (16 A)
    • Market segment

    • small commercial
    • residential
      • Sustainable offer status

        Green Premium product

        Warranty

        18 months

        Physical

        Remote control type

        push-button

        Mounting mode

        fixed, between 2 TL

        Mounting support

        DIN rail

        Height

        86 mm

        Width

        36 mm

        Depth

        71 mm

        Connections - terminals

      • tunnel type terminals0.5-4 mm² - rigid
      • tunnel type terminals0.5-4 mm² - rigid - with cable end
      • tunnel type terminals1-4 mm² - flexible
      • tunnel type terminals1-4 mm² - flexible - with cable end
        • Wire stripping length

          11 mm

          Range compatibility

        • Acti 9 iTL iTL
        • Acti 9 iTL iTLi
        • Acti 9 iTL iTLs
        • Acti 9 iTL iTLc
          • IP degree of protection

            IP20 conforming to IEC 60529

            Relative humidity

            95-95 % at 55-55 °C

            Ambient air temperature for operation

            -20-50 °C

            Ambient air temperature for storage

            -40-70 °C

            Standards

            EN/IEC 60669-2-2

            REACh Regulation

            Free of Substances of Very High Concern above the threshold

            REACh free of SVHC

            Yes

            EU RoHS Directive

            Compliant

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

            Product out of China RoHS scope. Substance declaration for your information

            Environmental Disclosure

            ENVPEP110302EN

            Others

            Number of Units in Package 1

            1

            Number of Units in Package 2

            36

            Package 1 Height

            6 cm

            Package 1 Length

            11 cm

            Package 1 width

            8.5 cm

            Package 2 Height

            30 cm

            Package 2 Length

            40 cm

            Package 2 width

            30 cm

            Unit Type of Package 1

            PCE

            Unit Type of Package 2

            S03

            Device short name

            iATL4

            [Uc] control circuit voltage

            230 V AC 50/60 Hz impulse 50 ms

            [Ui] rated insulation voltage

            440 V

            [Uimp] rated impulse withstand voltage

            Step sequences

          • 1st impulse - TL1 on, TL2 off
          • 3rd impulse - TL1 on, TL2 on
          • 4th impulse - TL1 off, TL2 off
          • 2nd impulse - TL1 off, TL2 on
            • 9 mm pitches

              4

              Tightening torque

              1-1 N.m

              Compatibility code

              iATL4

              Overvoltage category

              III

              Tropicalisation

              2

              Package 1 Weight

              200 g

              Package 2 Weight

              7.701 kg

              WEEE

              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
              Show all specifications

              Documents & downloads

              hide show

              Frequently Asked Questions

              hide show

              What is the Alternative for the Merlin Gerin 15913?

              A9C15913

              What is the replacement for Merlin Gerin 15322 ?

              A9A15322

              How wide is A9A15219 Safety Transformer ?

              10 Modules of 9mm = 90mm 

              How do you din rail mount a harmony pushbutton?

              You can use either the A9A15151 or A9A15152

              What is the dimensions of the load shedding device A9C15906 ?

              Height = 77 mm  Width = 145 mm Depth = 60 mm

              what is the maximum current for the R2 relay contacts on all sizes of ATS48 range of soft start

              Goals and Symptoms

              what is the maximum current for the R2 relay contacts on all sizes of ATS48 range of soft start

              Facts and Changes

              maximum current
              R2 relay
              soft start

              Causes and Fixes


              Characteristics of ATS48 relay :
              max voltage : 400Vac (0.2A max)
              thermal current : 5A
              During life :
              AC load
              AC1 5A 250V 10E5 cycles (resistor)
              AC15-14 : 0.5A (240Vac) 10E6 cycles (contactor)
              Cos 0.5 1.8A (240Vac) 10E5 cycles (inductive)

              DC load
              DC13 : 0.5A (48Vdc) 10E6 cycles (contactor)
              L/R 20mS 1.8A (30Vdc) 10E5 cycles (inductive)
              minima commutation capacities :
              6Vdc 10mA 10E7 cycles (PLC low level)

              It's availble for all range.


              Legacy KB System (APS) Data: RESL156323 V4.0, Originally authored by on , Last Edited by on
              Related ranges: Altistart 48