iATL4 step by step control auxiliary

Acti 9 Step by Step control Iatl5, 230VAC 50-60Hz

Catalogue Number: A9C15412
iATL4 step by step control auxiliary
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
Acti 9
Range
Acti 9
Device short name
iATL4
Product or component type
step by stel control auxiliary
[Uc] control circuit voltage
230 V AC 50/60 Hz impulse 50 ms
[Ui] rated insulation voltage
440 V
[Uimp] rated impulse withstand voltage
Remote control type
push-button
Step sequences
  • 1st impulse - TL1 on, TL2 off
  • 3rd impulse - TL1 on, TL2 on
  • 4th impulse - TL1 off, TL2 off
  • 2nd impulse - TL1 off, TL2 on
    • Mounting mode
      fixed, between 2 TL
      Mounting support
      DIN rail
      9 mm pitches
      4
      Height
      86 mm
      Width
      36 mm
      Depth
      71 mm
      Connections - terminals
    • tunnel type terminals0.5-4 mm² - rigid
    • tunnel type terminals0.5-4 mm² - rigid - with cable end
    • tunnel type terminals1-4 mm² - flexible
    • tunnel type terminals1-4 mm² - flexible - with cable end
      • Wire stripping length
        11 mm
        Tightening torque
        1-1 N.m
        Range compatibility
      • Acti 9 iTL iTL
      • Acti 9 iTL iTLi
      • Acti 9 iTL iTLs
      • Acti 9 iTL iTLc
        • Product compatibility
        • iTL (32 A)
        • iTL (16 A)
          • Market segment
          • small commercial
          • residential
            • Compatibility code
              iATL4
              Overvoltage category
              III
              IP degree of protection
              IP20 conforming to IEC 60529
              Tropicalisation
              2
              Relative humidity
              95-95 % at 55-55 °C
              Ambient air temperature for operation
              -20-50 °C
              Ambient air temperature for storage
              -40-70 °C
              Standards
              EN/IEC 60669-2-2
              Sustainable offer status
              Green Premium product
              REACh Regulation
              Free of Substances of Very High Concern above the threshold
              REACh free of SVHC
              Yes
              EU RoHS Directive
              Compliant
              Mercury free
              Yes
              RoHS exemption information
              Yes
              China RoHS Regulation
              Product out of China RoHS scope. Substance declaration for your information
              Environmental Disclosure
              ENVPEP110302EN
              WEEE
              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
              Warranty
              18 months

              Documents & downloads

              hide show

              Frequently Asked Questions

              hide show

              What is the Alternative for the Merlin Gerin 15913?

              A9C15913

              What is the replacement for Merlin Gerin 15322 ?

              A9A15322

              How wide is A9A15219 Safety Transformer ?

              10 Modules of 9mm = 90mm 

              What is the dimensions of the load shedding device A9C15906 ?

              Height = 77 mm  Width = 145 mm Depth = 60 mm

              what is the maximum current for the R2 relay contacts on all sizes of ATS48 range of soft start

              Goals and Symptoms

              what is the maximum current for the R2 relay contacts on all sizes of ATS48 range of soft start

              Facts and Changes

              maximum current
              R2 relay
              soft start

              Causes and Fixes


              Characteristics of ATS48 relay :
              max voltage : 400Vac (0.2A max)
              thermal current : 5A
              During life :
              AC load
              AC1 5A 250V 10E5 cycles (resistor)
              AC15-14 : 0.5A (240Vac) 10E6 cycles (contactor)
              Cos 0.5 1.8A (240Vac) 10E5 cycles (inductive)

              DC load
              DC13 : 0.5A (48Vdc) 10E6 cycles (contactor)
              L/R 20mS 1.8A (30Vdc) 10E5 cycles (inductive)
              minima commutation capacities :
              6Vdc 10mA 10E7 cycles (PLC low level)

              It's availble for all range.