7556_A9A26948
iMX+OF tripping unit
7556_A9A26948
iMX+OF tripping unit

Acti9 Voltage Release, iMX+OF, Tripping Unit, 12..24VAC, Shunt Rel

Catalogue Number: A9A26948
7556_A9A26948
iMX+OF tripping unit
7556_A9A26948
iMX+OF tripping unit
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range
Acti 9
Product or component type
shunt trip release with OC contact
Range of product
  • iSW-NA
  • iID
  • iDPN Vigi
  • iC60
    • Device short name
      iMX+OF
      Signal contacts composition
      1 C/O
      [Ie] rated operational current
    • AC-12: 6 A at 12 V AC 50 Hz
    • AC-12: 6 A at 24 V AC 50 Hz
    • DC-12: 6 A at 12 V DC
    • DC-12: 6 A at 24 V DC
      • [Uc] control circuit voltage
      • 12...24 V AC 50/60 Hz
      • 12...24 V DC
        • 9 mm pitches
          2
          Product compatibility
        • single terminal
        • iID
        • iC60
        • double terminal
        • iDPN Vigi
        • RCA
        • ARA
        • iSW-NA
          • Range compatibility
          • Acti 9 iC65
          • Acti 9 ARA
          • Acti 9 iDPN Vigi
          • Acti 9 iID
          • Acti 9 iSW-NA
          • Acti 9 RCA
          • Acti 9 iDPN (China version)
          • Acti 9 iC60 double terminals miniature circuit breaker
          • Acti 9 iC40
            • Local signalling
              action indicator
              Mounting mode
              clip-on
              Mounting support
              DIN rail
              Width
              18 mm
              Connections - terminals
            • clamp terminal - 2 cable(s) 2.5-2.5 mm² - flexible with cable end
            • clamp terminal - 1 cable(s) 6-6 mm² - rigid
            • clamp terminal - 2 cable(s) 2.5-2.5 mm² - rigid
            • clamp terminal - 1 cable(s) 4-4 mm² - flexible
              • Tightening torque
                1-1 N.m
                Compatibility code
                iMX+OF
                Market segment
              • residential
              • small commercial
                • Standards
                  EN/IEC 60947-5-1
                  Tropicalisation
                  2 conforming to EN/IEC 60947-5-1
                  Relative humidity
                  95-95 % at 55-55 °C
                  Ambient air temperature for operation
                  -25-50 °C
                  Ambient air temperature for storage
                  -40-85 °C
                  Sustainable offer status
                  Green Premium product
                  REACh Regulation
                  Free of Substances of Very High Concern above the threshold
                  REACh free of SVHC
                  Yes
                  EU RoHS Directive
                  Compliant
                  Toxic heavy metal free
                  Yes
                  Mercury free
                  Yes
                  RoHS exemption information
                  Yes
                  China RoHS Regulation
                   Pro-active China RoHS declaration (out of China RoHS legal scope)
                  Environmental Disclosure
                  ENVPEP1305024
                  WEEE
                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                  Warranty
                  18 months

                  Frequently Asked Questions

                  hide show

                  Will a new A9A26948 fit an old MG breaker

                  No they don't fit. You will need to replace the old MG MCB with new Acti9 MCB to fit the new Auxiliaries

                  will the A9A26929 fit on a C60-DC MCB?

                  No, those are designed to fit onto the acti9 AC MCBs for those MCBs use the A9N26929

                  Are the A9N18359 and A9A26924 compatible?

                  The ref A9N18359 is C120 MCB (Multi9 design in the white material).

                  The ref A9A26924 is iOF auxiliary (Aciti9 design for iC60 MCB).

                  I can confirm that the parts A9N18359 and A9A26924 are not compliant with each other

                   

                  What is the code for the Acti9 Padlock?

                  The code is A9A26970

                  Does A9A26976 go with iDPN N VIGI?

                  No. Unfortunately it does not and we don't do the terminal Shiels for iDPN N vigi as the screws are small.

                  Padlocking device to fit Domae MCB

                  the Acti9 A9A26970 will fit on the domae breakers.

                  Does the A9A26981 fit on the A9S66163?

                  Yes, that is designed to fit on the Acti9 shaped devices including the iSW switches.

                  What items come with the KITWALLBOX7?

                  A9Z51240 = Type B single phase RCCD
                  A9F54240 = 2 pole, 40A, Curve MCB
                  A9A26969 = Under voltage release

                  What are the part numbers for Padlocking device which will go on LHS and RHS of Acti 9 iC60 and RCBO's?

                  Part number A9A26380 is for mounting on the left side of Circuit Breaker.
                  Part number A9A26381 is for mounting on the  Right side of Circuit breaker.
                  For further details please follow the below link,
                  https://www.tracepartsonline.net/(S(jj1xcpflpzf1tyxwjtna0vip))/partdetails.aspx?PartID=10-02112015-105620&class=SCHNEIDER_ELECTRIC_DISTRI&clsid=/SCHNEIDER_DISTRI/F_SCHNEIDER_DISTRI/SCHNEIDER_DISTRI.030/SCHNEIDER_DISTRI.030.010/
                  Image result for A9A26380 schneider

                  Can A9A27049 be used in ON position of RCCB?

                  No , can't uses the locking device in ON position.

                  What is the code for the Acti9 MX shunt trip equivalent to the Merlin Gerin 26948 12-24vAC?

                  A9A26948
                   

                  Contactor LE1D18N7 does it come with overload ?

                   No - Overloads can be ordered separatly depending on the current rating required
                   

                  What is the recommended screen resolution for SoMachine V4.1?

                  The recommended resolution for SoMachine V4.1 is 1680 x 1050 pixel.

                  What is the part number for plastic screw caps for Slimline white moulded and Lisse white moulded range?

                  The product code for plastic screw caps for Slimline white moulded and Lisse white moulded range is GUMSCO.
                   

                  When do we have to use the external Antenna ?

                  It is useful to use it when the base station is hidden by for instance metallic equipment, some devices or others which reduce the radio signal level and which limit the communication range.

                  How to protect the capture of a available Base from a non desirable Remote ?

                  It is possible to put a transfer password via the configuration software.See transfer password in paragraph "Project Passwords Management" in chapter 7.3 of the user guide

                  Video: How to configure the PM800 series clock via writing to registers using Modbus commands?

                  Issue
                  Configuring the time and date on the PM800 series meters through RS-485 when Ethernet is not available

                  Product Line
                  PM800 series 

                  Environment
                  RS-485 communications, Modbus register read/write

                  Resolution
                  The date and time are stored in three-register compressed format. Each of the three registers contain a high and low byte value to represent the date and time in hexadecimal. For the synchronization, the command value is written in register 8000 and the values are in registers 8001, 8002, and 8003. The command used to initiate the change in register 8000 is 1311.

                  Example Date: 01/25/2000 at 11:06:59
                                
                  Hexidemical Value Hi Byte Lo Byte
                  0119 01 = month 19 = day
                  640B 64 = year 0B = hour
                  063B 06 = minute 3B = seconds

                  Here is a video that shows how to write to these registers using Modbus Tester: