Acti 9 Auxiliary Fault Contact iSD, 1 Change Over, 240-415VAC 24-130VDC

Acti 9 Auxiliary Fault Contact iSD, 1 Change Over, 240-415VAC 24-130VDC

Acti 9 Auxiliary Fault Contact iSD, 1 Change Over, 240-415VAC 24-130VDC

Item Number: A9A26927

Retail
$221.66
RRP (Inc. GST)

Product Dimensions

Width icon

Width9 mm

Height icon

Height86 mm

Depth icon

Depth73 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti 9

Range of product

  • iSW-NA
  • iC60
  • iID
  • iDPN Vigi
  • RCA
  • ARA
    • Product or component type

      fault contact

      Product compatibility

      single terminal

      Market segment

    • small commercial
    • residential
      • Sustainable offer status

        Green Premium product

        Warranty

        18 months

        Physical

        [In] rated current

      • 1-1 A at 130 V DC
      • 1.5-1.5 A at 60 V DC
      • 2-2 A at 48 V DC
      • 6-6 A at 24 V DC
      • 3-3 A at 415 V AC - 50/60 Hz
      • 6-6 A at 240 V AC - 50/60 Hz
        • Range compatibility

        • Acti 9 iC60
        • Acti 9 iC65
        • Acti 9 iC60 RCBO
        • Acti 9 iID
        • Acti 9 ARA
        • Acti 9 RCA
        • Acti 9 iDPN (China version)
        • Acti 9 iDPN Vigi
        • Acti 9 iC40
        • Acti 9 iSW-NA
          • Local signalling

            mechanical indicator

            Mounting mode

            clip-on

            Mounting support

            DIN rail

            Height

            86 mm

            Width

            9 mm

            Depth

            73 mm

            Net weight

            33 g

            Connections - terminals

          • screw clamp terminal2 cable(s) 2.5-2.5 mm² - rigid
          • screw clamp terminal2 cable(s) 1.5-1.5 mm² - flexible with ferrule
          • screw clamp terminal1 cable(s) 0.5-2.5 mm² - flexible
          • screw clamp terminal1 cable(s) 1-4 mm² - rigid
            • Wire stripping length

              10 mm

              Standards

              EN/IEC 60947-5-1

              IP degree of protection

              IP20 conforming to EN/IEC 60947-5-1

              Ambient air temperature for operation

              -35-70 °C

              Ambient air temperature for storage

              -40-85 °C

              REACh free of SVHC

              Yes

              EU RoHS Directive

              Compliant

              Toxic heavy metal free

              Yes

              Mercury free

              Yes

              RoHS exemption information

              Yes

              China RoHS Regulation

               Pro-active China RoHS declaration (out of China RoHS legal scope)

              Environmental Disclosure

              ENVPEP091004EN

              Circularity Profile

              ENVEOLI100608EN

              Others

              Device short name

              iSD

              Signal contacts composition

              1 C/O

              9 mm pitches

              1

              [Ui] rated insulation voltage

              500 V

              [Uimp] rated impulse withstand voltage

              4 kV

              Tightening torque

              1-1 N.m

              Compatibility code

              iSD

              Pollution degree

              3 conforming to EN/IEC 60947-5-1

              Tropicalisation

              2 conforming to EN/IEC 60947-5-1

              Package 1 Weight

              46 g

              Package 1 Height

              0.78 dm

              Package 1 width

              0.2 dm

              Package 1 Length

              0.925 dm

              WEEE

              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
              Show all specifications

              Documents & downloads

              hide show
              Filter items
              • All

              • Product Brochures

              • CAD Files and Packs

              • Technical Data Catalogues

              • Installation Instruction

              • Product Environmental

              • End of Life Manual

              • Declaration of Conformity

              Frequently Asked Questions

              hide show

              will the A9A26929 fit on a C60-DC MCB?

              No, those are designed to fit onto the acti9 AC MCBs for those MCBs use the A9N26929

              Are the A9N18359 and A9A26924 compatible?

              The ref A9N18359 is C120 MCB (Multi9 design in the white material).

              The ref A9A26924 is iOF auxiliary (Aciti9 design for iC60 MCB).

              I can confirm that the parts A9N18359 and A9A26924 are not compliant with each other

               

              What is the code for the Acti9 Padlock?

              The code is A9A26970

              Will a new A9A26948 fit an old MG breaker

              No they don't fit. You will need to replace the old MG MCB with new Acti9 MCB to fit the new Auxiliaries

              Does A9A26976 go with iDPN N VIGI?

              No. Unfortunately it does not and we don't do the terminal Shiels for iDPN N vigi as the screws are small.

              Padlocking device to fit Domae MCB

              the Acti9 A9A26970 will fit on the domae breakers.

              Does the A9A26981 fit on the A9S66163?

              Yes, that is designed to fit on the Acti9 shaped devices including the iSW switches.

              What items come with the KITWALLBOX7?

              A9Z51240 = Type B single phase RCCD
              A9F54240 = 2 pole, 40A, Curve MCB
              A9A26969 = Under voltage release

              What are the part numbers for Padlocking device which will go on LHS and RHS of Acti 9 iC60 and RCBO's?

              Part number A9A26380 is for mounting on the left side of Circuit Breaker.
              Part number A9A26381 is for mounting on the  Right side of Circuit breaker.
              For further details please follow the below link,
              https://www.tracepartsonline.net/(S(jj1xcpflpzf1tyxwjtna0vip))/partdetails.aspx?PartID=10-02112015-105620&class=SCHNEIDER_ELECTRIC_DISTRI&clsid=/SCHNEIDER_DISTRI/F_SCHNEIDER_DISTRI/SCHNEIDER_DISTRI.030/SCHNEIDER_DISTRI.030.010/
              Image result for A9A26380 schneider

              What RCCB is suitable for use in a VSD application?

              B type RCCB, 63 A 4 poles 30 mA sensitivity:  Part #16756

              How to proceed with a paired Remote to be paired with another Base ?

              A remote can be paired with only one Base, in this case we will need to make a reset >5s before doing the pairing procedure. It is explained in the user guide, chapter 8

              Multi-9 C60 Breakers: Values for Watts Loss and Voltage Drop per pole

              Issue:
              Power Loss
              Watts Loss
              Contact Resistance
              Voltage Drop

              Product Line:
              Circuit Breakers

              Environment:
              Applies to Multi-9, C60 Circuit Breakers (UL489 and UL1077)

              Resolution:
              The attached document gives the Power Loss (Watts Loss) and Voltage Drop per pole, at rated current of the breaker (nominal current). For example, a 1A breaker would be expected to have a Watts Loss per pole of 2.3 W, at rated current of 1A. This information can be used to calculate voltage drop when used at other than nominal current.