61011_A9A26927
iSD Auxiliary contact
61011_A9A26927
iSD Auxiliary contact

Acti 9 Auxiliary Fault Contact iSD, 1 Change Over, 240-415VAC 24-130VDC

Catalogue Number: A9A26927
61011_A9A26927
iSD Auxiliary contact
61011_A9A26927
iSD Auxiliary contact
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range
Acti 9
Range of product
  • iSW-NA
  • iC60
  • iID
  • iDPN Vigi
  • RCA
  • ARA
    • Product or component type
      fault contact
      Device short name
      iSD
      Signal contacts composition
      1 C/O
      [In] rated current
    • 1-1 A at 130 V DC
    • 1.5-1.5 A at 60 V DC
    • 2-2 A at 48 V DC
    • 6-6 A at 24 V DC
    • 3-3 A at 415 V AC - 50/60 Hz
    • 6-6 A at 240 V AC - 50/60 Hz
      • 9 mm pitches
        1
        Range compatibility
      • Acti 9 iC60
      • Acti 9 iC65
      • Acti 9 iC60 RCBO
      • Acti 9 iID
      • Acti 9 ARA
      • Acti 9 RCA
      • Acti 9 iDPN (China version)
      • Acti 9 iDPN Vigi
      • Acti 9 iC40
      • Acti 9 iSW-NA
        • [Ui] rated insulation voltage
          500 V
          [Uimp] rated impulse withstand voltage
          4 kV
          Local signalling
          mechanical indicator
          Mounting mode
          clip-on
          Mounting support
          DIN rail
          Height
          86 mm
          Width
          9 mm
          Depth
          73 mm
          Net weight
          33 g
          Connections - terminals
        • screw clamp terminal2 cable(s) 2.5-2.5 mm² - rigid
        • screw clamp terminal2 cable(s) 1.5-1.5 mm² - flexible with ferrule
        • screw clamp terminal1 cable(s) 0.5-2.5 mm² - flexible
        • screw clamp terminal1 cable(s) 1-4 mm² - rigid
          • Wire stripping length
            10 mm
            Tightening torque
            1-1 N.m
            Product compatibility
            single terminal
            Compatibility code
            iSD
            Market segment
          • small commercial
          • residential
            • Standards
              EN/IEC 60947-5-1
              IP degree of protection
              IP20 conforming to EN/IEC 60947-5-1
              Pollution degree
              3 conforming to EN/IEC 60947-5-1
              Tropicalisation
              2 conforming to EN/IEC 60947-5-1
              Ambient air temperature for operation
              -35-70 °C
              Ambient air temperature for storage
              -40-85 °C
              Sustainable offer status
              Green Premium product
              REACh Regulation
              Free of Substances of Very High Concern above the threshold
              REACh free of SVHC
              Yes
              EU RoHS Directive
              Compliant
              Toxic heavy metal free
              Yes
              Mercury free
              Yes
              RoHS exemption information
              Yes
              China RoHS Regulation
               Pro-active China RoHS declaration (out of China RoHS legal scope)
              Environmental Disclosure
              ENVPEP091004EN
              Circularity Profile
              ENVEOLI100608EN
              WEEE
              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
              Warranty
              18 months

              Documents & downloads

              hide show
              Filter items
              • All

              • Product Brochures

              • CAD Files and Packs

              • Technical Data Catalogues

              • End of Life Manual

              • Product Environmental

              • Installation Instruction

              • Declaration of Conformity

              Frequently Asked Questions

              hide show

              will the A9A26929 fit on a C60-DC MCB?

              No, those are designed to fit onto the acti9 AC MCBs for those MCBs use the A9N26929

              Are the A9N18359 and A9A26924 compatible?

              The ref A9N18359 is C120 MCB (Multi9 design in the white material).

              The ref A9A26924 is iOF auxiliary (Aciti9 design for iC60 MCB).

              I can confirm that the parts A9N18359 and A9A26924 are not compliant with each other

               

              What is the code for the Acti9 Padlock?

              The code is A9A26970

              Will a new A9A26948 fit an old MG breaker

              No they don't fit. You will need to replace the old MG MCB with new Acti9 MCB to fit the new Auxiliaries

              Does A9A26976 go with iDPN N VIGI?

              No. Unfortunately it does not and we don't do the terminal Shiels for iDPN N vigi as the screws are small.

              Padlocking device to fit Domae MCB

              the Acti9 A9A26970 will fit on the domae breakers.

              Does the A9A26981 fit on the A9S66163?

              Yes, that is designed to fit on the Acti9 shaped devices including the iSW switches.

              What items come with the KITWALLBOX7?

              A9Z51240 = Type B single phase RCCD
              A9F54240 = 2 pole, 40A, Curve MCB
              A9A26969 = Under voltage release

              What are the part numbers for Padlocking device which will go on LHS and RHS of Acti 9 iC60 and RCBO's?

              Part number A9A26380 is for mounting on the left side of Circuit Breaker.
              Part number A9A26381 is for mounting on the  Right side of Circuit breaker.
              For further details please follow the below link,
              https://www.tracepartsonline.net/(S(jj1xcpflpzf1tyxwjtna0vip))/partdetails.aspx?PartID=10-02112015-105620&class=SCHNEIDER_ELECTRIC_DISTRI&clsid=/SCHNEIDER_DISTRI/F_SCHNEIDER_DISTRI/SCHNEIDER_DISTRI.030/SCHNEIDER_DISTRI.030.010/
              Image result for A9A26380 schneider

              What RCCB is suitable for use in a VSD application?

              B type RCCB, 63 A 4 poles 30 mA sensitivity:  Part #16756

              How to proceed with a paired Remote to be paired with another Base ?

              A remote can be paired with only one Base, in this case we will need to make a reset >5s before doing the pairing procedure. It is explained in the user guide, chapter 8

              Multi-9 C60 Breakers: Values for Watts Loss and Voltage Drop per pole

              Issue:
              Power Loss
              Watts Loss
              Contact Resistance
              Voltage Drop

              Product Line:
              Circuit Breakers

              Environment:
              Applies to Multi-9, C60 Circuit Breakers (UL489 and UL1077)

              Resolution:
              The attached document gives the Power Loss (Watts Loss) and Voltage Drop per pole, at rated current of the breaker (nominal current). For example, a 1A breaker would be expected to have a Watts Loss per pole of 2.3 W, at rated current of 1A. This information can be used to calculate voltage drop when used at other than nominal current.