Auxiliary switch; iSW
Auxiliary switch; iSW
Auxiliary switch; iSW
Auxiliary switch; iSW

Acti 9 Contact OC, for Isw, 3A, 415V

Catalogue Number: A9A15096
Auxiliary switch; iSW
Auxiliary switch; iSW
Auxiliary switch; iSW
Auxiliary switch; iSW
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
iSW 20...32
Range
Acti 9
Device short name
iOF
Product or component type
OC contact
Signal contacts composition
1 C/O
[Ie] rated operational current
  • 3 A at 415 V AC
  • 6 A at 250 V AC
    • Mounting mode
      fixed
      Mounting support
      35 mm DIN rail
      9 mm pitches
      2
      Height
      77 mm
      Width
      18 mm
      Depth
      75 mm
      Range compatibility
      Acti 9 iSW
      Auxiliary connection terminal
      screw terminal 10-10 mm²
      Market segment
      small commercial
      Compatibility code
      iOF
      Sustainable offer status
      Green Premium product
      REACh Regulation
      Free of Substances of Very High Concern above the threshold
      REACh free of SVHC
      Yes
      EU RoHS Directive
      Compliant
      Toxic heavy metal free
      Yes
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
       Pro-active China RoHS declaration (out of China RoHS legal scope)
      Environmental Disclosure
      ENVPEP110310EN
      Circularity Profile
      ENVEOLI1103010EN
      WEEE
      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
      Warranty
      18 months

      Documents & downloads

      hide show
      Filter items
      • All

      • End of Life Manual

      • Product Environmental

      Frequently Asked Questions

      hide show

      Is there a shunt trip that can be used in conjunction with a iSW series?

      No unfortunately the ISW series can't be used with shunt release.

      For further information please visit Global Specialist in Energy Management | Schneider Electric

      Is A9A27006 suitable to use on A9S66463?

      Yes, A9A27006 is suitable to use on A9S66463

       

      What is the replacement for Merlin Gerin 15322 ?

      A9A15322

      What is the part code for a Fuse Carrier STI, 1 pole.?

       The Multi9 part code is 15636
      The Acti9 part code is A9N15636

      How wide is A9A15219 Safety Transformer ?

      10 Modules of 9mm = 90mm 

      What is the code for a din mount time switch analogue IRTB?

      A9E16066

      What is the dimensions of the load shedding device A9C15906 ?

      Height = 77 mm  Width = 145 mm Depth = 60 mm

      What does partial metering in iME1Z and iME1zr mean?

      Partial metering is the same as full metering, just that you have the luxury of reseting the partial meter whereas the full metering will continue running without possibility of reset.

      ‘z’ denotes partial metering (with reset facility)

      What is the power consumption of timer A9E16066?

      [Ie] rated operational current:
      8 A AC 250 V
      8 A DC 250 V
      0.01 A DC 5 V  

      Din Rail Mount for 22mm Operators

      Issue:
      Is there a mounting adapter which will allow 22mm operators to be mounted onto 35mm Din Rail?

      Product Line:
      22mm Accessories - GIC Product

      Environment:
      US Product

      Cause:
      Product Selection

      Resolution:
      The A9A15151 is an adpater which will allow 22mm operators to be mounted onto 35mm Din Rail

      Are the Altivar Process Drives suitable for use on ungrounded, corner grounded and hi leg Delta systems?

      Issue:
      Are the Altivar Process Drives suitable for use on ungrounded, corner grounded and hi leg Delta systems?

      Product line:
      Altivar Process, ATV600,  ATV900

      Environment:
      All

      Cause:
      Delta voltage system

      Resolution:
      The drive can operate on corner grounded and high leg voltage systems.  However, the built-in EMC filter must be disconnected.  For High leg, the neutral must not be used.
      The VFD can also operate on an ungrounded delta system but the EMC filter must also be disconnected.

      What is the meaning of fault code 151 in XXMIT block in Unity Pro.

      The fault code 151 means that MsgOut is smaller than 12 Byte when 'Modbus Master Messaging' function is selected.

      To prevent this fault do the following:
       
      1. Increase the array size of variable defined for MsgOut parameter.
       
      2. Use array of same size as defined in step#1 for the variable of parameter MsgIN.