Quantcast

Clipsal MAX4 Surge Protection Device (SPD) 3P Imax 40 kA

Clipsal MAX4 Surge Protection Device (SPD) 3P Imax 40 kA

Clipsal MAX4 Surge Protection Device (SPD) 3P Imax 40 kA

Item Number: 940RMT/3

Retail
$583.94
RRP (Inc. GST)

Product Dimensions

Width icon

Width54 mm

Height icon

Height85 mm

Depth icon

Depth64 mm

Datasheet

Specifications

Design

Range

MAX4

Product or component type

surge arrester

Sustainable offer status

Green Premium product

Physical

[Ue] rated operational voltage

240/415 V +/- 10 % AC 50/60 Hz

Local signalling

white/red flag

Mounting mode

clip-on

Mounting support

35 mm DIN rail

Height

85 mm

Width

54 mm

Depth

64 mm

Connections - terminals

  • tunnel type terminal2.5-25 mm² rigid
  • tunnel type terminal4-16 mm² flexible with ferrule
    • Wire stripping length

      14 mm

      Standards

      IEC 61643-11:2011

      IP degree of protection

    • IP20
    • IP40 on enclosure
      • Relative humidity

        5-95 %

        Ambient air temperature for operation

        -25-60 °C

        REACh Regulation

        Free of Substances of Very High Concern above the threshold

        REACh free of SVHC

        Yes

        EU RoHS Directive

        Compliant

        Toxic heavy metal free

        Yes

        Mercury free

        Yes

        RoHS exemption information

        Yes

        China RoHS Regulation

         Pro-active China RoHS declaration (out of China RoHS legal scope)

        Environmental Disclosure

        ENVPEP130303EN

        Circularity Profile

        ENVEOLI130301EN

        Others

        Package 1 Height

        70 mm

        Package 1 Length

        90 mm

        Package 1 width

        54 mm

        Poles description

        3P

        Remote signalling

        with

        Surge arrester type

        electrical distribution network

        Earthing system

      • TT
      • TN-C
      • TN-S
        • Surge arrester class type

          type 2

          Nominal discharge current

          15 kA

          Maximum discharge current

          40 kA

          [Uc] maximum continuous operating voltage

          350 V

          Maximum [Up] voltage protection level

          <1.6 kV

          Disconnector device type

          fusible disconnect gG 125 A

          9 mm pitches

          6

          Maximum residual current

          0.6 mA

          Package 1 Weight

          0.32 kg
          Show all specifications

          Documents & downloads

          hide show
          Filter items
          • All

          • Product Brochures

          • Technical Data Catalogues

          • Installation Instruction

          • Specifications

          • Corporate Marketing

          Frequently Asked Questions

          hide show

          What is the replacement to the 970RM?

          940RMT/1

          Will the cartridge 940pm fit the 940RMT/3?

          Yes ithe cartridges fits the single and three phase surge arrestors.
          Some of the key features are:
          • Cartridge replacement is quick and easy without the need to disconnect wiring


          For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=940PM
           

          What AC Surge Arrestor does Schneider Electric recommend for its Three Phase Grid Tie Inverters?

          We recommend the use of Schneider Electric 940RMT/3 on the AC output to our Three Phase Grid Tie Inverters to protect the inverter from power surges originating from the grid. 

          Important Note: Installation of Schneider Electric Grid Tie Inverters and related supporting components must be undertaken and completed by a CEC - Grid Connect Inverter accredited solar installer/service agent.

          Is there a replacement module for the 970RM/3?

          Yes there is a replacement for the 970RM/3 plug protection overload. Its part number is a 970PM.

          For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=970PM
           

          What is the replacement cartridge for a 940RMT/1 Surge arrestor?

          The part number for the cartridge to suit the 940RMT/1 Surge arrestor is 940PM.

          Some of the key features are:
           
          • Cartridge replacement is quick and easy without the need to disconnect wiring

          For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=940PM
           

          Does the 970RM/3 Loop in and out of the surge arrestor or does it just feed it?

          It just feeds it so if theres a spike in voltage it will go through the path of the surge arrestor not the breaker see attached pdf of wiring
          Show More