Quantcast

Extension Sockets, Suspension Switched Socket, 250V, 10A

Extension Sockets, Suspension Switched Socket, 250V, 10A

Extension Sockets, Suspension Switched Socket, 250V, 10A

Item Number: 927

Retail
$147.73
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Others

Package 1 Height

50 mm

Package 1 Length

125 mm

Package 1 Weight

0.102 kg

Package 1 width

50 mm
Show all specifications

Frequently Asked Questions

hide show

What is another option for a 15A version of the PDL 927P ?

Could use the Clipsal SS15/15 with PDL 56P315

What distribution board is required for the CH25843 chassis?

For the customized distribution board for 72 pole (18 mm) and 12 pole (27 mm) chassis, you need to submit request for a quote to "au.estimating@schneider-electric.com". Our Standard distribution board only goes up to 60 pole (18 mm) and 12 pole (27 mm).

What does the termination A27 of the drive ATV68E5C43N4A27 means? There are many references in the Pricat/Prodat that we dont know what it is. For exa...

Goals and Symptoms

What does the termination A27 of the drive ATV68E5C43N4A27 means? There are many references in the Pricat/Prodat that we dont know what it is. For example other references: ATV68E5C10N4A23 ATV68E5C10N4A32 ATV68E5C13N4A24 ATV68E5C15N4A25 ATV68E5C19N4A14 ATV68E5C19N4A26 ATV68E5C23N4A22 ATV68E5C28N4A31 ATV68E5C43N4A27 ATV68E5C53N4A26 ATV68E5C53N4A28 ATV68E5C63N4A40 So what does the termination AXX mean for this cases of the ATV68E5?

Facts and Changes

ATV68E5

Causes and Fixes

The termination A27 and the others are for ATV68 in enclosure for specific customers. You can't order it or if the order come from Renault.


Legacy KB System (APS) Data: RESL157635 V1.0, Originally authored by on , Last Edited by on
Related ranges: Altivar 68

What type of lampholder does the oyster light for the fan have?

OYWHT, OYBEI and OYSS have 2 x E27 type of lampholder.

Error 127 in ION7650 event log

Issue
There is error code 127 in ION7650/7550 event log.

Product Line
ION7650
ION7550

Environment
Event log

Resolution
Error 127 is logged when the ION meter needs to recreate file space for a data recorder.

The 127 error is logged when there is NO data file present. The ION meter creates the file space for a data recorder and puts a message in the event log telling the user the file was created.

This is an informational message stating the meter corrected a missing file. This message is usually observed after a framework paste has occurred.

Can I use a cal file of N27 or lower for N38 or vice versa?

Cal file contains data which defines switchgear type, ratings, etc,..

Controller needs to know the switchgear type and ratings (voltage and interruption currents)  to have adequate voltage when charging trip/close capacitors.

N38 needs more trip/close energy than N27 and lower. 16kA mechanism needs more power to be driven than 12.5kA one.

Eg. A N38 switchgear with N27 data in its SCEM may results in the N38 mechanism not being closed or tripped properly. Similar for the other way round and for interrupting currents. Therefore, this must be avoided. In urgent situations, you may use cal file one N series for another N series as a temporary solution. However the two units must be of the same voltage voltage and interrupting current ratings (38KV, or 27KV and lower, 12 KA or 16kA)

 

Show More