Quantcast

Insulating shroud, Standard Size, for 30 Series

Black | Insulating shroud, Standard Size, for 30 Series

Insulating shroud, Standard Size, for 30 Series

Item Number: 90F-BK

Retail
$4.72
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Product or component type

shroud

Sustainable offer status

Green Premium product

Physical

REACh Regulation

Free of Substances of Very High Concern above the threshold

REACh free of SVHC

Yes

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure

ENVPEP120506EN

Others

Accessory / separate part category

insulation accessory

Package 1 Weight

6 g

Package 1 Height

26 mm

Package 1 width

26 mm

Package 1 Length

50 mm
Show all specifications

Frequently Asked Questions

hide show

What are the switching angles of the 7 Series rotary cam switches?

Cams can be made with 30*, 45*, 60* and 90* switching angles.

What is the part number of a 12 hole neutral link with mounting feet that can take 16 mm² cable?

BPQL12, is a 12 hole Bare Link with Mounting Blocks takes 16mm² cable. It is a 90A Link Bar with moulded mounting blocks. 

Key Features

  • Bar section 13 x 13 mm
  • Two 1/4 inch Hexagon head stud for cable lugs
  • Bare link with mounting blocks
  • 5.5 mm Diameter Tunnel
  • 190 deg C maximum temperature rating
  • 12 tunnel- single screw
  • All tunnels are numbered
  • 143 mm overall length
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=BPQL12

What is the function of the "Alarm" pilot light on the STR22SE, STR23SE and STR53UE electronic trip units.

The Alarm pilot light is an overload indicator light.

It is:
Lit with a steady light if the load current is greater than 90% of the adjustment threshold Ir
Flashing if the load current is greater than 105% of the adjustment threshold Ir. The circuit breaker will trip if the light continues to flash.

Do you need to take into consideration the service factor of the motor when setting the trip range on the Solid State Motorlogic overload relay?

Issue:
Setting the FLA on solid state overload

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment:
9065 Solid State Overload relay

Resolution:
If the  motor has a service factor of 1.0, then you would set the dial to 90% of the motor's full load current.
The solid state overload has a built in service factor of 1.15 - 1.25. If the motor has a service factor of 1.15 - 1.25,
set the dial to the motor's full load current rating. All other service factor ratings will need to be calculated by the motor manufacturer.

Why are 9001KM38 listed twice, as resistor and full voltage light modules?

Issue:
Is the 9001KM38 a resistor type or full voltage type of light module?

Product Line:
Push Buttons and Operator Interface

Environment:
Harmony Pushbuttons

Cause:
Product Features

Resolution:
Both descriptions are accurate. They are both the same device but can be selected by either description depending on the application/preference.

What is the approximate weight of a typical Model 6 LVMCC section?

Issue:
What is the approximate weight of a typical Model 6 LVMCC section?

Product Line:
Model 6 motor control centers.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
The following weights are approximate shipping weights for a normal mix of LVMCC equipment. Some sections, based on installed devices and width of section may vary from the weights shown.

NEMA 1, 1A, & 12 Enclosure, 15 inches deep - 600 lbs
NEMA 3R Non-Walk-In Enclosure, 15 inches deep - 900 lbs

NEMA 1, 1A, & 12 Enclosure, 20 inches deep - 750 lbs
NEMA 3R Non-Walk-In Enclosure, 20 inches deep - 1050 lbs


CTA-ID : 2005295