865-1025-01

Conext Xw+ Conduit Box

Catalogue Number: 865-1025-01
865-1025-01
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Product brand
Clipsal

Frequently Asked Questions

hide show

Is the new SCP part number 865-1050-01 compatible with all the XW inverter chargers? (Ex. XW4024, XW6048, XW4548)

865-1050-01 SCP Compatibility
The new part number for the system control panel (SCP) is 865-1050-01.
The XW models had a part number 865-1050 but now the SCP is 865-1050-01 and it is compatible with all XW models.

Customer is requesting the utility interactive current for XWs models

Max Sell Amps

Default - 18Amps (865-1010 XW4024) 36Amps (865-1010-01 XW4024)
                27Amps (865-1000 XW6048) 20Amps (865-1005 XW4548) 48Amps (865-1000-01 XW6048)

Range - 0-18Amps (865-1010 XW4024) 0-36Amps (865-1010-01 XW4024)
                0-27Amps (865-1000 XW6048) 0-20Amps (865-1005 XW4548) 0-48Amps (865-1000-01)

Which metrics will be displayed when using the Conext Battery Monitor?

Issue:
Which metrics will be displayed when using the Conext Battery Monitor?

Product Line:
Conext Battery Monitor

Environment:
Any Schneider Electric solar installation

Cause:
Specific metrics aren't outlined on website

Resolution:
The following metrics will be displayed when using the Conext Battery Monitor:

Battery Current
Battery Temperature
Battery State of Charge
Battery Midpoint 1 Voltage
Battery Midpoint 2 Voltage
Battery Capacity Remaining
Battery Capacity Removed

You can find this and other specifications for the device on our website:
https://solar.schneider-electric.com/product/conext-battery-monitor/

What does the XW+ Welded relay faults mean (F17, F18, F19, F20, F21, F22)?

 Explanation of XW+ welded relay faults

 

If you receive one of the Welded Relay errors on an XW+ Inverter/Charger (F17 through F22), it is possible that one of the AC transfer relays has failed, but in order to rule out wiring errors or improper operation of the AC bypass breakers, you should take the following steps:

 

First, verify that the AC Bypass Breakers are in the OFF position.  If the AC Bypass breakers are switched ON while the Inverter Output breakers are also ON, the XW will sense that an AC voltage source is present on its AC Output terminals and will register one of these faults.
Any outside source of AC presented to the input and output of the XW simulataneously can potentially weld the relay. THIS IS CONSIDERED A MIS-WIRE AND MAY VOID THE WARRANTY. The Power Distribution Panel (865-1015-01) comes prewired for a single XW and has an interlock to prevent both the inverter output breakers and the AC bypass breakers from being in the ON position simultaneously. When installing dual XW units, ensure that the AC breakers and interlock plate (comes with 2nd inverter extension kit Pt # 865-1020) are installed per the installation manual to prevent this issue. Any system with 3 XW units or more must incorporate and external bypass switch.

 

If the AC Bypass Breakers are off, power the inverter OFF at the AC and DC breakers and disconnect the AC wires from the Inverter's AC Out terminals at the inverter itself. Power the inverter back on and see if the fault clears. Have a qualified person measure across the disconnected output wires while either grid or generator power is being supplied to XW input (AC1 or AC2 LEDs blinking or solid). Make sure no AC voltage is measured across the disconnected output wires.

 

If the fault does not clear, it is likely one of the AC Transfer Relays is actually welded closed.  In this case, a replacement of the AC Board will be necessary.  If this was caused by a mis-wire, it will not be covered under warranty. Contact Technical Support at 866-519-1470 for more information regarding parts and availability..

 

 

What is the difference between the old SCP and new SCP (System Control Panel)?

The old SCP (865-1050) is used to configure the original XW and SW inverter charge units, with the addition of newer features implemented by the updated firmware of these units, though the old SCP can only be firmware
 upgraded so far to the point where it could not configure a good deal of the new features.
The new SCP (865-1050-01) has all the same programming capabilities as the old SCP but also includes the ability to program the new features included with the updated firmware found on the XW and SW inverter charge units.

It is advised that if you have the old model SCP, to replace it with the new SCP.

XW Manufacturing.

Lately, I have been getting a lot of questions of where the XW and XW components are made. So.... Here is the answer.

 

 

 

XW inverter chargers  - China
XW charge controllers - China
XW power distribution Panel 865-1015 - USA
XW System control panel 865-1050 - China

 

XW AGS- China

 

 

 

As for internal surface mount components, PCB's.

 

 

 

In general, Peoples Republic of China. Sheet metal and the bare PCBs are manufactured in China which is most of the value of the unit. Some components  come from Europe or Latin America. A little bit from North America as well, but the majority of electronic components are manufactured in SE Asia.

 

 

 

We don't have detailed records for every component as suppliers can manufacture parts in multiple countries depending on which plant has capacity to build. (Per Rob S)

 

 

 

Thomas.

What are the firmware requirements for the new XW+ model

Issue
What firmware is required for older accessories to work with the XW+ models

Environment
Situation where an inverter upgrade is done, such as an RMA/Replacement

Product Line
Conext XW+, SCP, AGS, Combox

Cause
XW+ models require a certain level of firmware to the compatible with the SCP, the AGS, and the Combox.

Resolution
XW+ Model Firmware Requirements

1) The XW+ requires an SCP with fw 2.00bn13. All old SCPs in the US distribution center have been re-programmed and changed to part number 865-1050-01
2) The XW+ requires an AGS with fw 3.00bn2. All old AGSs in the US distribution center have been re-programmed and changed to part number 865-1060-01
3) The XW+ requires a Combox with fw 2.00bn656. All old AGSs in the US distribution center have been re-programmed, but the part number remains 865-1058
4) The old XW / CSW and accessories will run fine with the new AGS / SCP

How do you view multiple Combox units on one web page?

How do you view multiple comboxes in one combox view page

You would need the latest firmware on the Conext Combox and you need to navigate to settings and multi cluster configuration
One Combox is set upt as the Master and the other is set up as a slave

NOTE:Please see attachment

What is the maximum load imbalance for the Conext SW Series Solar Inverters?

Issue: 
Customer is looking to confirm the Conext SW's load imbalance 

Product Line: 
865-2524
865-4024
865-4048

Environment:  
Product information

Resolution: 
The unit will operate with up to 75% load imbalance between the lines.

Cause:
Information is not posted in the unit’s electrical specifications
 
 

Can I change my ComBox’s IP address using Modbus commands?

Issue:
Customer is trying to confirm if they can change the IP address of the ComBox using Modbus commands 

Product Line:
Conext ComBox 865-1058

Environment:
Product information

Resolution:
The IP address details and configuration parameters are not accessible through Modbus for the Conext ComBox

Cause:
The only Modbus registers that can be monitored and/or write to are published in the Modbus Map: Conext™ Modbus Converter/ComBox Device document. Available from the SE Solar Website.

What are the part numbers for the red and green LEDs used on the S-Flex enclosed drives?

Issue:
Part numbers for the red and green LEDs used on the S-Flex enclosed drives.

Product Line:
S-Flex 212 and 21

Environment:
All

Cause:
Replacement green and red leds.

Resolution:
Spare Light part numbers:
80462-110-01 Red Led
80462-109-01 Green Led

See table on page 101 of the attached S-Flex Manual.

Will the Xantrex Communication Gateway Work With The Conext XW+?

Issue
The customer owns a Communication Gateway and is looking to upgrade their legacy XW or has received a Conext XW+ unit as a replacement

Product Line
Conext XW+, Xantrex Communication Gateway

Environment
Conext XW+ connected with a Xantrex Communication Gateway on Xanbus

Cause
The Xantrex Communication Gateway was discontinued before the release of the Conext XW+.  No firmware was released for the Gateway to make it compatible with the Conext XW+ units.  Any unit carrying XW firmware that is version 2.00 or higher will not be recognized by the Gateway.

Resolution
The firmware of the XW+ unit has to be downgraded to v1.07 to work with the Communication Gateway.  It will then be recognized by the Gateway as an 865-1000.  To downgrade the firmware, a Conext Combox or a Configuration Tool will be required since the Gateway does not recognize the XW+.
 

How can I replace the fans on my Conext SW?

Issue:
Customer is looking for support on replacing the fans in their Conext SW

Product Line:
Conext SW series hybrid inverter/chargers
865-2524
865-4024
865-4048

Environment:
Any Conext SW with fan or overheating issues

Resolution:
The attached document includes information on replacing the fans. Order either part number 0J-0282 - Conext SW Fans Replacement Kit, or an equivalent fan using the specs below:

FAN 12VDC 370mA 85.2CFM 120x120x25mm 2200RPM 39.1dBA BALL-BEARING -10+75C

Cause:
Conext SW fan specs and replacement information not covered in standard documentation

How many Maximum Power Point Trackers do the Conext Solar Charge Controllers have?

Issue:
How many maximum power point tracking (MPPT) circuits are in each charge controller?

Product Line:
Conext MPPT 80 600 (p/n: 865-1032)
Conext MPPT 60 150 (p/n: 865-1030)

Environment:
PV arrays with multiple strings.

Cause:
Some larger models include multiple separate MPPT circuitry.

Resolution:
The Conext MPPT solar charge controller family only has a single maximum power point tracker in each unit. Multiple strings should be connected in parallel and the MPP will be found as an average across all strings.

The MPPT 60 150 has terminals for convenient connection of two strings without the need for an external combiner box.

The MPPT 80 600 has terminals for connecting up to three strings without an external combiner box (most installations will require external fusing when using more than 2 strings).  See attached image for locations of PV terminals.
 

Where can we find information on Berger-Lahr products?

Berger Lahr Motion Technology is a division of Schneider Electric.

Berger Lahr offers a complete Motion Control product range for machine automation. In addition, Berger Lahr develops and manufactures customized products and solutions, based on its standard products. In 2008, Berger Lahr changed the company name to Schneider Electric Motion Deutschland, and integrated its products and services into the offering of Schneider Electric. The motion products are a part of Schneider Electric's Lexium range.