Image of 751 Indoor Infrascan 2 Wire 2A

751

Passive Infrared Sensor, 2 Wire, 2A

Image of 751 Indoor Infrascan 2 Wire 2A
Colour: White Electric
Colour: Per UOM Std.
  • White Electric 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
  • Maximum load current: 2A
  • Minimum load: 40W
  • Maximum off-state leakage current: 5mA
  • Conductors Required: 2 Wire
Range of product
Infrascan
Range
Infrascan
Product brand
Clipsal
Product or component type
movement sensor
[Ue] rated operational voltage
200...265 V
Mounting support
  • ceiling
  • wall
    • Mounting height
      2.4 m
      Ambient air temperature for operation
      0-40 °C
      REACh Regulation
      Free of Substances of Very High Concern above the threshold
      EU RoHS Directive
      Compliant
      Toxic heavy metal free
      Yes
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
       Pro-active China RoHS declaration (out of China RoHS legal scope)
      Circularity Profile
      ENVEOLI121002EN

      Frequently Asked Questions

      hide show

      Which 751 infrascan , can use 2 units to control the same load??

      751R-WE

      Can a 751 be used with 25W LED?

      Yes, it can but you will need to put a 31CAP in parallel with the load.

       

      Why are my lights flickering on a 751 sensor?

      Generally it is because 1 of 2 reasons, Incompatible load type or your not exceeding your minimum load.
      Please see table below for specifications:
       
      Catalogue Number 751 751R
      Minimum Loads 40W 0W
      Compatible Load types Incandescent Incandescent
        240V Halogen 240V Halogen
        Iron Core Transformers* Iron Core Transformers
          Fluorescent
          Electronic Transformers
           
      Incompatible Loads Fluorescent N/A
        Electronic Transformers N/A
        Small Motor Loads 5A Max N/A
        Dischharge Lamps N/A

      For further information please visit Trade - Clipsal by Schneider Electric

      Why wont my 751 passive infrared sensor work, it has a 20W flood light wired to it?

      The reason why the light/ sensor wont operate as deisred is because the minimum operating load is 40W. Due to the design of this sensor it is only capable of a maximum of 2 Amps and a minimum of 40W. It also has a maximum off-state leakage current of 5mA.
      If any of these values are exceeded this may casue the system not to work.

      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=751
       

      Is there a recessed wall mount sensor?

      No unfortunately we do not offer a recessed sensor. However we can offer a Surface mount sensor, part number 751R.
      Some of the key features are:
      • 10A maximum load current
      • Stand-by power consumption is less than 1W
      • 3 Wire
      • Neutral required
      • 30 seconds warmup time
      • 6m x 6m, 8.5m from sensor head, head rotatable through 120° rated detection field at maximum sensitivity
      • 5 seconds to 20 minutes timer delay range
      • Cables accommodates 3 terminals, up to 1 x 2.5mm² cable per terminal
      • Length of sensor 57mm
      • 100mm Diameter

      For furthur information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=751R

      OR 

      See the attached installation instructions.