Motion Infrared Sensor Sensor, 10A, 3 Wire, Outdoor

Catalogue Number: 750WPR
Image of 750WPR Infrascan Sensor 3 Wire 10A
Image of 750WPR Infrascan Sensor 3 Wire IP66 10A
Image of 750WPR Infrascan Sensor 3 Wire 10A
Image of 750WPR Infrascan Sensor 3 Wire IP66 10A
Colour: Grey
Colour: Per UOM Std.
  • Grey 1 PCE
Added to cart

Specifications

hide show
Range of product
Infrascan
Range
Infrascan
Product brand
Clipsal
Product or component type
movement sensor
[Ue] rated operational voltage
200...265 V AC
Network frequency
50 Hz
Mounting support
  • wall
  • ceiling
    • Mounting height
      2.4 m
      IP degree of protection
      IP66
      Ambient air temperature for operation
      0-50 °C
      EU RoHS Directive
      Compliant
      Toxic heavy metal free
      Yes
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
       Pro-active China RoHS declaration (out of China RoHS legal scope)
      Circularity Profile
      ENVEOLI121002EN

      Frequently Asked Questions

      hide show

      Can 750WP be connected in parallel to control the same load .

      No. Need to use the 750WPR, three wire device when connecting in parallel
      For more information on the 750 series please visit the Clipsal web site on the link provided . https://www.clipsal.com/Trade/search-results?q=750w

      My 750WPR Infrascan has stopped switching the light on, but the red LED in the sensor is still flashing. What do I do?

      If installed within the last five years it is covered under warranty. Please contact the Clipsal warranty department using the link to have the unit replaced free of charge.
      Link: https://www.clipsal.com/warranty
       

      How do I know if 750WPR Infrascans I have installed are affected by the batch related component issue?

      If movement is still being detected (shown by the flashing RED LED indicator behind the sensor lens), however the load does not switch on, then the unit is affected. If this is the case please contact the Clipsal warranty department using the link to have the unit replaced free of charge.
      Link: https://www.clipsal.com/warranty
       

      Which outdoor sensors have a sensitivity adjustment

      The  part codes are  100SA360, 750WP and 750WPR

      Regarding the recent batch related component issue on the 750WPR Infrascan. I have installed a 750WPR Infrascan several months ago and its working fine so far, do i need to go back to replace it?

      No. Units only need to be replaced IF they become defective. If within 5 years from install the unit does however become defective, please contact the Clipsal warranty department using the link below to have the unit replaced free of charge.
      Link: https://www.clipsal.com/warranty
       

      Does the 96VH110/2 have a sensitivity adjustment

      No it does not only the 100SA360, 750WP and 750WPR do

      Is the 750WPR Cbus compatible?

      No however the 5750WPL is the same sensor just cbus compatible

      How do I know if I my stock of the 750WPR-GY Infrascan is possibly affected by the recent batch related component issue?

      Check the manufacturing date code on the bottom of the unit box or on the label under the mounting base. Products manufactured after May 2017 are not affected and are ok to use. If you have stock manufactured prior to this date, we are happy to provide free of charge replacements through our warranty process, by contacting Customer Care on email : CustomerCare.AU@schneider-electric.com or Telephone: 137328

      What is the sensing range of the 750WPR?

      The sensing range for the 750WPR , at the optimum height of 2.4metres is 18metres



       

      What is the part number for the replacement knuckle for the 750WPR?

      The part number for the replacement knuckle for the 750WPR is - 750-KNUCKLE

      For further information, visit the link below:-
      https://www.clipsal.com/Trade/search-results?q=750-KNUCKLE
      User-added image

      What is the part number for the load correction device for the 750WP?

      The part number for the load correction device for the 750WP is - 31CAP

       

      Can 750WPR be used for Resistive Loads?

      The 750WPR can be used for Resistive Loads.

      https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=750WPR

       

      Which motion sensors have ESS approval?

      750WPR is ESS approved.

      What is the part number for the CBus version of the 750WPR?

      The part number is 5750WPL.
      Please click this link for further information https://www.clipsal.com/Trade/Products/ProductDetail?catno=5750WPL

      User-added image

      What is part number for mounting base to suit 750WPR?

      The part number for mounting base to suit is a 750MBA.
      For more information please refer to the link below:
      https://www.clipsal.com/Trade/Products/ProductDetail?catno=750MBA

      What is mounting base to suit 750WPR?

      The mounting base to suit is a 750MBA.
      For more information please visit the link below:
      https://www.clipsal.com/Trade/Products/ProductDetail?catno=750MBA

      Can it 750WPR be used with LED lights?

      Because it is a three wire device, the relay terminal can completely isolate, allowing for no minimum load. This makes it suitable for LED lighting.

      Can more than one 750WPR be used to control the same load?

      Yes. Three wire devices can be connected in parallel to control the same load.

      Does the 750WPR have the double click override function?

      No, it will need to have an override switch wired into the circuit.
       

      What is the maximum time setting on a Clipsal 750WPR

      The maximum time setting is 20 minutes

      What is the part number for a 2 wire version of the 750WPR?

      The part number for a 2 wire version of the 750WPR is a - 750WP.
      Some of the key features are:
      • 5A maximum load current
      • 10mA maximum off-state leakage current
      • Stand-by power consumption is less than 1W
      • 2 Wire
      • 30 seconds warmup time
      • 18 metre radius x 110° rated detection field at maximum sensitivity
      • 5 seconds to 20 minutes timer delay range
      • Cables accommodates 4 terminals, up to 2 x 2.5mm² cable per terminal
      • Triac switching method
      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=750WP

      Is it possible to use a 750WPR in a freezer?

      No, unfortunately the temperature rating is 0 to +50 degrees.
      Please see link and document below for more information.

      https://www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR

      https://updates.clipsal.com/ClipsalOnline/Files/Brochures/W0000781.pdf

       

      Can you use a 31CAP on the 750WPR 3 wire sensor?

      Yes, the 31CAP can be used on both 2 wire and 3 wires sensors.

      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=31CAP

      What is part no for load capacitor to suit Led load on 750WPR

      Part no for load capacitor is 31LCDA

      for more information on this part please refer to https://www.clipsal.com/Trade/Products/ProductDetail?catno=31LCDA

      User-added image

      Can you install more than 1 750WPR to control the same load?

      Yes, you can.
      For further information, visit the link below:-
      https://www.clipsal.com/Trade/search-results?q=750WPR



       

      Is there a corner mounting bracket for the 750WPR?

      No there is not a corner mounting bracket for the 750WPR.
      However there is a knuckel bracket, part number 750-KNUCKLE.

      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=750-KNUCKLE

      How do i stop my LED Flood light from flashing when connected to my 750WP 2-wire Sensor?

      The LED Light is not working correctly with 750WP 2-Wire Sensor because it is NOT a compatible load.
      If controlling a LED load via a sensor is required, you will need to use a 3-Wire version. The part number for a 3 Wire version is a 750WPR.
      Please see the compatibility chart below:
      Catalogue Number 750WP 750WPR
      Compatible Load Types Incandescent Incandescent
        240V Halogen 240V Halogen
        Iron Core Transformers Fluorescent Loads
        N/A Iron Core Transformers
        N/A Electronic Transformers
        N/A Shaded Pole Induction Motors (Exhaust fans, (5A Max)
        N/A Split Phase Induction Motors (ceiling fans, 5A Max)
        N/A Other Motor Loads (Limit to 5A Max)
      Incompatible Load Types Electronic Transformers N/A
        Fluorescent Loads N/A
        Discharge Lamps N/A
        Motor Loads N/A

      Some of the key features for the 3 wire 750WPR Outdoor sensor are:
      • 10A maximum load current
      • Stand-by power consumption is less than 1W
      • 3 Wire
      • Neutral required
      • 30 seconds warmup time
      • 18 metre radius x 110° rated detection field at maximum sensitivity
      • 5 seconds to 20 minutes timer delay range
      • Cables accommodates 4 terminals, up to 2 x 2.5mm² cable per terminal
      • Relay switching method
      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR

      Why is LED Light not working correctly with 750WP?

      The LED Light is not working correctly with 750WP 2-Wire Sensor because it is not a compatible load.
      If controlling a LED load via a sensor is required, you will need to use a 3-Wire version. The part number for a 3 Wire version is a 750WPR.
      Please see the compatibility chart below:
      Catalogue Number 750WP 750WPR
      Compatible Load Types Incandescent Incandescent
        240V Halogen 240V Halogen
        Iron Core Transformers Fluorescent Loads
        N/A Iron Core Transformers
        N/A Electronic Transformers
        N/A Shaded Pole Induction Motors (Exhaust fans, (5A Max)
        N/A Split Phase Induction Motors (ceiling fans, 5A Max)
        N/A Other Motor Loads (Limit to 5A Max)
      Incompatible Load Types Electronic Transformers N/A
        Fluorescent Loads N/A
        Discharge Lamps N/A
        Motor Loads N/A

      Some of the key features for the 3 wire 750WPR Outdoor sensor are:
      • 10A maximum load current
      • Stand-by power consumption is less than 1W
      • 3 Wire
      • Neutral required
      • 30 seconds warmup time
      • 18 metre radius x 110° rated detection field at maximum sensitivity
      • 5 seconds to 20 minutes timer delay range
      • Cables accommodates 4 terminals, up to 2 x 2.5mm² cable per terminal
      • Relay switching method
      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR



       

      What is the part number for the hinge section on the 750WP range?

      The part number is 750-KNUCKLE-GY.

      Can you have multiple 750WP 2 wire sensors wired in parallel?

      No, unfortunately you will need the 3 wire version. The part number for a 3 wire sensor is 750WPR.
      Some of the key features are:
       

      • 10A maximum load current
      • Stand-by power consumption is less than 1W
      • 3 Wire
      • Neutral required
      • 30 seconds warmup time
      • 18 metre radius x 110° rated detection field at maximum sensitivity
      • 5 seconds to 20 minutes timer delay range
      • Cables accommodates 4 terminals, up to 2 x 2.5mm² cable per terminal
      • Relay switching method

      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR

       

      What is the range of a Clipsal 750WPR passive infrared sensor

      The beam scans a 18m radius out from the sensor and around 110 degrees in an arc

      Does the 750WPR have a 2x toggle (soft) manual override?

      No, any override switch is physical and not controlled by the sensor.

      Is the knuckle available as spare part for Infrascans

      Yes the part no is 750-Knuckle and it will suit both 2 wire 750WP  & 3 wire 750WPR

      Is there part number for the seal to suit the sensor 750WPR available?

      Yes,  the seal part number is 750-GASKET.

      Can you override the 750PWR sensor?

      It is dependant on the wiring. need an extra active and a 3 position switch.

      What is the warranty period for 750WP?

      This Clipsal Product is guaranteed against faulty workmanship and materials for a
      period of five (5) years from the date of installation. This warranty is expressly subject to the Clipsal product being installed, wired, tested,
      operated and used in accordance with the manufacturer’s instructions.

      For further information on this product, please visit https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=750WP

      User-added image

      What is the part number for a 750WPR sensor in C-Bus?

      The part number for a 750WPR sensor in C-Bus is a 5750WPL.
      Some of the key features are:
      • Depending on the installation design, can provide an energy efficient solution
      • Passive Infrared Occupancy Outdoor Sensor
      • A light emitting diode (LED) on the sensor head can be programmed to turn when movement is detected, via the installation software, enabling easy positioning and commissioning of the sensor
      • Time-out variation from 1 second to 18 hours, 12 minutes and 15 seconds, is set via the installation software
      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=5750WPL



       

      Do you do the 750WPR in black?

      No, unfortunately the 750WPR is only available in one colour, that being grey.

      Some of the key features are:
      • 10A maximum load current
      • Stand-by power consumption is less than 1W
      • 3 Wire
      • Neutral required
      • 30 seconds warmup time
      • 18 metre radius x 110° rated detection field at maximum sensitivity
      • 5 seconds to 20 minutes timer delay range
      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR

      Can the 750WP sensor supply LED's?

      The 750WP was not tested on LED loads, however a Load correction device may be used in conjunction for LED lighting loads. Load correction device part number = S31LCDA
      Also check what LED driver is being used.

      Can you get the bit that goes between the base and the sensor on the 750WP

      The part number is 750-KNUCKLE-GY
       

      What is the part code for a CBUS outdoor occupancy sensor

      The part code is 5750WPL

      Can the 750WP be used with LED lamps?

      The 750WP is not compatible with electronic transformers, so can not be used for LED lights.

      However, the 750WPR can be used to control LED lights.

      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=750WP
       

      Can you wire an over ride into a 2 wire 750WP?

      Yes. In order to get the system to work, you will need to wire in either 2x 30M's or a 30MAM into a wall plate and connect to the sensor.

      For further information on the sensor, please visit https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=750WP

      User-added image

      Can you wire 2 750WPR 3 wire sensors in parallel?

      Yes, the 3 wire 750WPR sensor can be wired in parallel with multiple 3 wire sensors.
      Some of the key features are:
       

      • 10A maximum load current
      • Stand-by power consumption is less than 1W
      • 3 Wire
      • Neutral required
      • 30 seconds warmup time
      • 18 metre radius x 110° rated detection field at maximum sensitivity
      • 5 seconds to 20 minutes timer delay range
      • Cables accommodates 4 terminals, up to 2 x 2.5mm² cable per terminal
      • Relay switching method

      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR

      Infrascan 750WPR is not operating correctly when a manual override on switch is wired in parallel with the LED indicator wired to stay on when the load is on.

      You are getting a backfeed through your switchwire which is causing the relay in the infrascan to stay on. The solution would be to install a diode on your switchwire to stop the backfeed going to your sensor.

      Does the 750WPR has a manual override?

      The 750WPR can be Manually overriden by wiring as per the install instructions with a physical switch. The unit itself does not have an inbuilt system for manual override.



      For further information please visit https://updates.clipsal.com/ClipsalOnline/Files/Brochures/W0000781.pdf

      Where should the Load correction devices 31CAP and S31LCDA be used?

      The 31CAP is to be use with the following two wire products
      Infrascan 750WP, 751, 753.
      Timer 31VETR
      Sunset Switch WS226SSR/2, 56SSR/2, 31VSSR/2

      The S31LCDA is suitable for use with Clipsal & Schneider Electric 2-Wire, mains powered Dimmers that use
      Leading Edge, Trailing Edge and Universal Dimming.
      Other Suitable loads: Dimmable CFL/ Dimmable LED with Electronic control

      (Load correction Devices may not correct all problems)
      Installation Instructions can be found on the Clipsal.com Website.
       

      What is the part name for a dimmer which can handle 750W?

      The part name is as follows: C2031E4RUD-WE.

      Can the 750 Series Infrascan be remotely triggered ?

      Yes, you can remotely trigger the sensor using something like a 30MBP.



      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR.

      Will a 2-wire Infrascan 750WP Sensor operate with 20W load?

      No, Unfortunately a 20W load will not operate a 2-wire Infrascan 750WP Sensor as it has a minimum load of 40W. You can increse the minimum load by adding multiple lights or a larger light. Alternatively you can install a product called a 31CAP which is a capacitor specifically designed to "increase" the minimum load. 

      The characteristics of a 31CAP capacitor are:
      Values Description
      Amp 0.025A (Ampere)  =  25mA (Milliampere).
      Watts 6W
      Voltage 240V
      Microfarad 0.33μF
      Maximum amount stacked in parallel 3

      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=31CAP

       
      Show More