Quantcast

Clipsal - 600 Series, Double Horizontal Switched Socket 10A

Black | Clipsal - 600 Series, Double Horizontal Switched Socket 10A

Clipsal - 600 Series, Double Horizontal Switched Socket 10A

Item Number: 695-BK

Datasheet

Specifications

Design

Range of product

PDL 600 Designer Series

Product brand

Clipsal

Sustainable offer status

Green Premium product

Physical

Control type

ON/OFF button

Number of gangs

2 gangs

Pin number

3

Number of power socket outlets

2

Actuator

  • rocker
  • switch

Fixing mode

by screws

Local signalling

without light indicator

Mounting position

horizontal

[Ue] rated operational voltage

230...240 V AC

[In] rated current

10 A

Height

74 mm

Width

118 mm

Fixing center

84 mm

Standards

  • AS 3100
  • AS 3133
  • AS 3112

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure

ENVPEP120506EN

Material

Material

plastic

Others

Package 1 Bare Product Quantity

1

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

3.5 cm

Package 1 Width

7.5 cm

Package 1 Length

11.7 cm

Package 1 Weight

100.5 g
Show all specifications

Frequently Asked Questions

hide show

Video: Why is the Micrologic Trip Unit Type P or H reading negative power?

Product Line
Micrologic Trip Unit Type P and H
Breakers: Powerpact P and R Frames, Masterpact NT and NW, Compact NS630B- NS3200

Environment
Micrologic Trip Unit Type P and H

Cause
The power readings from the device are all negative, yet all of the voltages and currents are positive numbers.

Resolution
The power sign must be changed to accommodate this issue. The power sign has two different settings: (+) and (-). The (+) setting implies that power is absorbed from upstream to downstream (meaning it is top-fed). The (-) setting implies that power is absorbed from downstream to upstream (meaning it is bottom-fed).

The power sign can only be changed from the front panel of the Trip Unit. From the main menu go to either the Micrologic Setup or Metering Setup menus then follow the steps in the diagrams below. In order to change settings via the menu buttons on the trip unit, the trip unit must be energized AND the door over the adjustment dials MUST be OPEN. 
To change the power sign:
  1. Press the Wrench menu button
  2. Select Micrologic Setup
  3. Select Power Sign
  4. Open the trip unit door (see video for details)
  5. Toggle power sign with up or down arrow
  6. Press Enter to select sign
  7. Press Wrench button to exit
  8. Select YES to save settings on exit





For further information about the Micrologic Trip Units Type P and H see link for the instruction bulletins below.
Powerpact P, R, and Masterpact NW, NT Micrologic™ 5.0P and 6.0P Trip Units, see 48049-137-05
Powerpact P, R, and Masterpact NW, NT Micrologic™ 5.0H and 6.0H Trip Units, see 48049-330-03

Where can I find ATV61 programming assistance with the water solutions card VW3A3503?

Issue:  
Programming and wiring up a water solution card on the ATV61 drives?

Product line:
Altivar ATV61 with water solutions option card VW3A3503.

Environment:
All models, all serial numbers 

Cause:
Water Solution Card set up configuration.

Resolution:
First, go through the Pre-Configuration section in the manual.   Transducer is 0-145 PSI with 4-20mA Output. There are 2 additional External pumps.   Go to Page 86 to set System Units =1 (Imp, Gallon and Degree Fahrenheit)   Water Solutions/Expansion/PID PID Ref Local (Local PID reference will appear under Water Solutions menu) PID Max Ref 100 psi PID Feedback  Drive AI2 PID Gain 50 PID Integral 1   Water Solutions/Expansion/Sensors Outlet Transducer Maximum   145 psi Pressure Units PSI   Water Solutions/Expansion/Start Set Setpoint Ramp  5.0   Water Solutions/Expansion/Stage Number of External Pumps 1 Stage Speed  50 hZ  Jumper: +24 to CI_LI54 External Pump 1 No Fault +24 to CI_LI55 External Pump 2 No Fault +24 to CI_LI57      Auto enable   The Feedback Pressure(monitored under water Solution menu) must be lower than the Start Pressure(programmed in Start Set) when closing CI_LI57 and want the unit to start.
 
Wiring examples:
CLI57= auto enable or start
CLI58= fault reset

Transducer input
AI2= Analog input on the drive
AI52 and AI51= analog inputs on the water solutions card

Fault feedback inputs from aux pump overload relays
CLI54= for fault input for Aux pump 1
CLI55= for fault input for Aux pump 2
CLI56= for fault input for Aux pump 3

Aux pump outputs
CLO51= Aux output for pump 1
CLO52= Aux output for pump 2
CLO53= Aux output for pump 3

Status outputs from the WSC
CLO55= Run status
CLO56= Fault status

Jockey pump option
CLO56= Jockey or priming pump output


Water Solution Control Card User manual

5080CTC touch screen Repair

For C-BUS 5000 CTC 6" Touch Screen Repairs - NOW Done by our JEA Technologies

please see attached RMA form for CTC touchscreen repair.

Contact detail for CTC repair is

Trevor Callaghan

Workshop Manager

JEA Technologies

M- 0404 887 463

Trevor.callaghan@jeatech.com.au

www.jeatech.com.au

CTC Repair RMA form


 

What are the repair parts for the HU363SS, series F6? (may be shown as F06)

Issue:
Repair parts

Product Line:
Heavy Duty Safety Switch

Resolution:
The repair parts for the HU363SS, series F6 (F06) are as follows. No other parts are available.
Line Base Assembly - 4056775250 (arc suppressor not included)
-Line Base mounting screw - 4020515101 (3 required)
-Arc Suppressor Assembly - 4056635550
-Arc Suppressor mounting screw - 4020514501 (1 required)
-Lug assembly - 4025101851 (per lug)
-Lug Mounting Screw - 4020514202 (per lug)
-Mechanism Assembly - 4056646950 (NOTE: handle coupling, cover interlock defeat coupling, and lockplate gaskets may also need replacing)
-Handle Coupling - 4056699850
-Cover Interlock Defeat Coupling - 4056699750
-Handle Assembly - 4056894150 (also recommend replacing lockplate gaskets)
-Lockplate - 4056894201 (also recommend replacing lockplate gaskets)
-Lockplate Gasket - 4050322802 (2 required)
-Lockplate mounting screw - 2194900001 (2 required)
-Ground Lug - 4025101851 (2 required)
-Ground Lug Mounting Screw - 4020514801

What is the ATS48 soft starters dissipated watts loss for calculating heat loss for enclosure sizing?

Issue:
Looking for the watts loss on a  ATS48 soft start

Product Line:
Altistart ATS48 soft starters

Environment:
All

Cause:
Needs to know the dissipated heat loss in watts the ATS48 soft starter will produce when running at full load.

Resolution:
See the table below and choose the ATS48's watt loss based on if a shorting contactor is being used or not.


ATS48 Watts Loss


 

What do the ATV61/71 1.1-1.5 status LED's indicate?

Issue
Where can I find information on the 1.1 through 1.5 LED indicator lights?

Product Line:
ALTIVAR 61/71

Environment:
All
 
Cause:
Product Selection & Services

Resolution:
LED's 1.1-1.5 belong to Controller Inside Card (or similar, like a Water Solutions Pump Card).

When used with a Controller Inside Card (CIC), the LED's indicate status as shown below in an excerpt from the ATV61/71 Controller Inside manual:

ComcardLED



When used with a Water Solutions Pump Card, the LED's indicate status as shown below in an excerpt from the Water Solution Control Card User manual:
comcard




For further details see the attached files. 
 