Frequently Asked Questions

hide show

What is the XD2AC221?

Issue:
XD2AC221 description

Product Line:
Push Buttons and Operator Interface

Environment:
Harmony Pushbuttons

Resolution:
It is a 30mm joystick., a 2 direction with spring return to 0 with a 68mm long lever.

NOTE: XD2 Joysticks have been replaced by XD4

What is the battery life of the graphic Display VW3A1111?

Issue:
Battery life of the graphic Display VW3A1111

Environment:
Altivar Process, Altivar Machine, ATV600, ATV900, ATV320

Product Line:
Variable Frequency Drives

Cause:
What is the battery life of the Advance Graphic Display VW3A1111?

Resolutions:
The battery life time inside the VW3A1111 is 8 years.

Where can the 2-wire type (TCT) parameter be found on the Altivar process drive?

Issue:
TCT parameter on the Altivar process drive

Product Line:
Altivar Process

Environment:
All models, All serial numbers

Cause:
Documentation

Resoultion:
Complete Settings-> Command and Reference-> 2-wire type

From the main menu, Navigate to "Complete Settings" then "Command and Reference".  From here, you can scroll down to 2/3 wire control, and if it is set to 2 wire, 2-wire control type can be found just below.

Do any of the Altivar Drives have a Profinet option?

Issue:
Profinet option on ATV Drives

Product Line:
ATV61, ATV71, ATV32, ATV600, ATV900

Environment:
All
 
Cause:
Product Selection & Services

Resolution:
Yes, ATV600, ATV900, ATV320, ATV340, ATV61, ATV71 and ATV32 offer options cards that support Profinet.
​ATV600/ATV900/ATV320/ATV340/ATV32 Profinet option card part number VW3A3627.
ATV61 / ATV71 Profinet option card part number VW3A3327.
Some older version drives may not support the Profinet option card. Be sure to verify compatiblity before ordering.

What can I use to replace the air filter in an enclosed drive?

Issue:
Replace the air filter in an enclosed drive.

Product Line:
Drives and soft starters.

Environment:
Products sold in the United States.

Cause:
Selection.

Resolution:
It is a 20 Pore per inch foam air filter.
A similar material could be obtained from an HVAC supplier.
There is no system recognized part number.
The internal number 52012-273-01 is an 18 inch square piece of this material.
 

Is it possible to give Start/Stop commands from PLC via Modbus Port on LUCM module of TeSys U.

You can connect the Modbus port of LUCM module (Multi Functional Control Unit) of TeSys U controller with PLC in order to access all the registers, except the registers from 680 to 705. To access these registers for write function, you need a communication module depending on the protocol.

Therefore the command registers (like Start/Stop) 700,703,704,705 cannot be accessed for writing by the PLC via LUCM Modbus port. However, you can read and monitor the values of Tesys U controller.
Show More