Brush Bronze Cover

Brush Bronze Cover

Brush Bronze Cover

Item Number: 661M-BZ

Retail
N/A
RRP (Inc. GST)
Colour Bronze (BZ)
  • Bronze 1 PCE
  • Stainless Steel 1 PCE

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

PDL 600 Designer Series

Product brand

Clipsal

Product destination

switch

Surface finish

matt

Material

Material

metal

Others

Package 1 Weight

0.01 kg
Show all specifications

Frequently Asked Questions

hide show

What is the diameter of a 93b

diameter of 93b is 66mm

Is there a Lexcom RJ45 connector that fits in a PDL plate

Yes, use a VDI552012 + 611M

What is the dimensions for the PDL 611M mounting adaptor clip

 They only fit the 600 series plates

What is the maximum voltage rating of the Wiggy voltage tester.

Issue:
Application

Product Line:
Wiggy Voltage Tester

Cause:
Clarifying maximum voltage

Resolution:
600 volts AC, 250 volts DC maximum.


CTA-ID : 2010590

6610VT1 Wiggy Voltage Tester Leads

Issue:
What are the replacement leads for a 6610VT1 Wiggy voltage tester? 

Product Line:
Obsolete voltage testers formerly sold by Square D Company.

Environment:
Wiggy voltage testers

Resolution:
The 6610VT1 voltage test and all related accessories are now obsolete with no replacement. Consider another manufacturer of similar devices.  

What are the Dimensions for the Clipsal PIR sensor sae_ue_ms_csawe?

What is the part number for a PDL single gang grid and cover?

The part number for a PDL single gang grid and cover is a 681VH.
Some of the key features are:
  • Standard
  • also suitable for a 681M metal cover plate
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=681VH​

What is the part number for a 63mm saddle?

The part number for a 63mm saddle is a 178/63.
Some of the key features are:
  • 1.6mm gauge
  • 7mm diameter Hole
  • 107mm Centres
  • 130mm Length x 39mm Width x 66mm Height
For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=178/63

What are the dimensions for the 43VF15?

The dimensions for the 435VF15 are 118mm high, 80mm wide and 65mm deep.
It has a cut-out diameter of 66mm and the mounting centres are 70mm x 54mm.

For more information, please refer to the link:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=435VF15

Are the Wiggy testers NFPA70E certified?

Issue:
Are the Wiggy voltage testers NFPA70E certified?

Product Line:
Obsolete Square D voltage testers.

Environment:
Specification

Cause:
Code Certification

Resolution:
The NFPA70E is the Standard for Electrical Safety in the Workplace. This Standard does not actually provide for certification of individual pieces of equipment. This is a Standard, not a certification document. The Wiggy`s are UL/CSA/ANCE certified.

Update:  The Wiggy line of voltage testers is obsolete and no longer available, no replacement. Consider another manufacturer for this product.


CTA-ID : 2033348

Is it allowed to extend the lead on a BCPM split core CT?

Issue:
Is it allowed to extend the lead on a BCPM split core CT?
If so, What is the maximum recommended length of the lead extension?

Product Line:
BCPM split core CT

Environment:
Extending CT Leads for BCPM split core CT

Cause:
Customer is requesting to extend the CT length with minimal to no accuracy changes.

Resolution: 

Yes, you may extend the CT leads.

6.1m (20ft) is the our recommended maximum length for CT extension leads.
One of our recommended accessories, the BCPMSCCT0R20, is such a 6.1m lead, referred to on page xxiii of the PowerLogic¿ BCPMSC
Branch Circuit Power Meter with Split-Core CTs Panelboard Monitoring System Installation Guide, available here:
https://www.powerlogic.com/literature/BCPMSC_Z205658-0C.pdf
See also RESL191029 which discusses wire size and attenuation.

How to apply a Register Mask in the IONE/SPM/PME Modbus Device Importer

Issue
A user would like to create a MDI driver that requires bitmasking registers.

Product Line
ION Enterprise 6.0.x
StruxureWare Power Monitoring 7.0.x
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x

Environment
Modbus Device Importer

Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

A mask is applied to the raw data received from a register. The mask is applied in an AND fashion.
For example, if the mask “0x4” is applied, then the register value displayed is only nonzero if the 2nd most significant bit in the register is a 1 (X#XXXXXXXXXXXXXX).

Note:
You can apply masks to both numeric and Boolean data types. To apply custom masks, scroll down the list and select Custom. When prompted, enter the value in Decimal, Binary, or Hexadecimal format. Custom mask can be used to allow 1 or more bits to be visible from the register being masked.

Here is a chart for a visual of the mask



Example:
An end user with a Micrologic Trip Unit might want to know Breaker Status (closed, open).
Register 661 bit 0 is the status bit.

To create this register point we would use Register Mask 0x0001.