Frequently Asked Questions

hide show

Can the 681 switch fluorescent lights

Yes but only up to 19A

How much power is dissipated by the high end Quantum PLCs?

This can be calculated as Bus Current * Bus Voltage.

140 CPU 651 50 -> 2160mA * 5V = 10.8W
140 CPU 651 60 -> 2760mA * 5V = 13.8W

140 CPU 651 60S-> 2760mA * 5V = 13.8W
140 CPU 652 60 -> 2760mA * 5V = 13.8W
140 CPU 658 60 -> 2760mA * 5V = 13.8W

140 CPU 670 60 -> 2500mA * 5V = 12.5W
140 CPU 671 60 -> 2500mA * 5V = 12.5W
140 CPU 671 60S-> 2500mA * 5V = 12.5W

140 CPU 672 60 -> 2500mA * 5V = 12.5W
140 CPU 672 61 -> 2500mA * 5V = 12.5W

140 CPU 678 61 -> 2500mA * 5V = 12.5W

To calculate BTU you can take the wattage and multiply it by 3.4144.

What colour is the PDL 641 available in?

The PDL641 is available in both black and white.
 

How to apply a Register Mask in the IONE/SPM/PME Modbus Device Importer

Issue
A user would like to create a MDI driver that requires bitmasking registers.

Product Line
ION Enterprise 6.0.x
StruxureWare Power Monitoring 7.0.x
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x

Environment
Modbus Device Importer

Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

A mask is applied to the raw data received from a register. The mask is applied in an AND fashion.
For example, if the mask “0x4” is applied, then the register value displayed is only nonzero if the 2nd most significant bit in the register is a 1 (X#XXXXXXXXXXXXXX).

Note:
You can apply masks to both numeric and Boolean data types. To apply custom masks, scroll down the list and select Custom. When prompted, enter the value in Decimal, Binary, or Hexadecimal format. Custom mask can be used to allow 1 or more bits to be visible from the register being masked.

Here is a chart for a visual of the mask



Example:
An end user with a Micrologic Trip Unit might want to know Breaker Status (closed, open).
Register 661 bit 0 is the status bit.

To create this register point we would use Register Mask 0x0001.

Is the PDL 581 hinge flap mech the same as 600 series one

Yes the 681 hinge flap mechs are the same size

What is the dimensions for a PDL 681 1-Gang Switch ?

Overall Dimensions - 118mm x 74mm
Mounting Centres - 84mm

Is there an alternative for a 6601 inline exhaust fan?

The CE150D would be a suitable replacement.

For more details:
https://updates.clipsal.com/ClipsalOnline/Files/Brochures/W0000773.pdf

This includes:
Package Inclusion on CE150D
Instruction Sheet

 

What is the maximum voltage rating of the Wiggy voltage tester.

Issue:
Application

Product Line:
Wiggy Voltage Tester

Cause:
Clarifying maximum voltage

Resolution:
600 volts AC, 250 volts DC maximum.


CTA-ID : 2010590

6610VT1 Wiggy Voltage Tester Leads

Issue:
What are the replacement leads for a 6610VT1 Wiggy voltage tester? 

Product Line:
Obsolete voltage testers formerly sold by Square D Company.

Environment:
Wiggy voltage testers

Resolution:
The 6610VT1 voltage test and all related accessories are now obsolete with no replacement. Consider another manufacturer of similar devices.  

Does the PDL 691 have a red cover plate available

Not available in red as a cover only, can purchase the complete unit in red (PDL 691RD)

Where can I get dimensions for an Altivar 660 Drive Systems?

Issue:
Where can I get dimensions for an Altivar 660 Process Drive Systems?

Product Line:
Altivar 660

Environment:
All serial numbers for ATV660

Cause:
N/A

Resolution:
Please reference the Altivar 660 Process Drive Systems Manual attachment - NHA91297

https://www.schneider-electric.us/en/download/document/NHA91297/

Are there any metal cover plates available for the PDL 641?

No -The only cover plate available for the PDL 641 is white (PDL641CWH).
The complete unit is available in both black (BK) and white (WH).

How to create Status point or an Alarm for IO not responding?

Using E-series configurator and configuring the Scadapack 535E RTU.
Under IO Folder>Scadapack IO; configure 6601 module address 0. Enter Status Point number 500. Write configuration to the scadapack then restart RTU.


Add point 500 as Binary input in the Point browser: If DNP binary input point 500 value is 1; The 6601 module address 0 is responding
If DNP binary input point 500 value is 0; The 6601 module address 0 is NOT responding.


Also, using the Analog input point under Points folder, Read from the controller and see point quality flags indicates.


 

How do I upgrade Vijeo Designer 4.6 to Vijeo Designer 6.2?

You will have to upgrade from Vijeo Designer 4.6 to Vijeo Designer 6.1 Then you can upgrade from 6.1 to 6.2.

Why is my Conext CL showing an alarm code: 4661 & 4662 ( PV1&PV2 SPD Service Alarm)

Issue: 
Customer is calling to confirm alarm codes: 4661 & 4662 ( PV1&PV2 SPD Service Alarm) 

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
PV1 or PV2 input SPD reached End of Life
SPD remote control wiring issue

Resolution: 
Check the SPD and replace EOL cartridges if required
Check SPD remote wiring 

What is the 600 series unit that will fit on to a 125ml modempak ducting

Need to contact Modempak for confirmation (ph - 0800 663 367) but in theory if the mounting clip for the ducting has 84mm
centres it should fit the PDL 600 Series

Are there any metal finish cover plates available for the PDL 651?

Yes, the PDL 682 coverplate is the same one used for the PDL 651. The metal cover plates are available in Polished Brass (PB), Brushed Bronze (BBZ) and Stainless Steel (SS).
Code example (PDL 651 coverplate in Polished Brass): PDL 682MPB

Is the cover for the PDL691 available in black? (PDL 691C)

The cover (PDL 691C) for the PDL 691 is only available in White (691CWH), Polished Brass (691MPB), Brushed Bronze (691MBBZ) and Stainless Steel (691MSS). Black is not available.

What would cause the ATV66 drive to just shut down with no fault?

Issue:
Troubleshooting ATV66 drive unexpected shut down with no fault.

Product Line:
Altivar ATV66, ATV56, 66U and 56U

Environment:
All

Cause:
The drive is stopping and shutting down without showing any faults on the display.

Resolution: 
1st check the drives status in the bottom right hand side of the HMI.  What is the status? RDY, NRP,
 
If the drives status is RDY then we need to check the drives run signal on LI2 for 2 wire control.
If the drives status is NRP then we need to check the run permissives input on LI1.
You can monitor the status of the logic inputs in menu 2.1.

How the customers can request Out of Warranty repairs for CTC2 and CTC3 Touch Screen?

CTC2 and CTC3 Touch Screen "Out of Warranty" Repairs for our Customers

Warranty repairers on these units will now be Arbor.
 
Please find below their contact details and find attached a Return form to be filled and return the unit for repair directly to Arbor.
Arbor will be handling the repair side, cost of repair and charging the customer accordingly.
 
 
Arbor Australia Pty. Ltd.
Unit 1/72 Bayfield Rd, Bayswater   3153
Victoria,Australia

Phone    : +61 3 8736 0300
Fax         : +61 3 8736 0325
Email :    jasenh@arboraust.com
 

Can the current sensors in a Masterpact NW or NT breaker be replaced?

Issue:
Is it possible to change the current sensors inside of the Masterpact NT or NW breakers?

Product Line:
Circuit Breakers

Environment:
Masterpact NW NT

Resolution:
No, the current sensors or CT's are embedded inside the sealed case and not replaceable. 

 

How far away from the ATV18 drive can you wire a speed pot?

Issue:  How far away from the ATV18 drive can you wire a speed pot?
 
Product Line:  ATV18
 
Environment:  All
 
Cause:  N/A
 
Resolution:  Question is more about how much voltage drop you may have if you wire the speed pot to far from the drive. You may supply your own +10V supply externally sized properly to help alleviate this voltage drop.


 

Is it possible to get a vertical single, switched socket with two extra switches in the PDL range?

We only do a horizontal single, switched socket with two extra switches - PDL 694XX.

Another alternative would be to use a PDL 691X. This is a vertical single, switched socket with one extra switch.
 

What are the supported controllers based on the Unity Pro v11 license size?

Unity Pro v11 is available in 3 different sizes :  S, L, XL
The only difference between sizes S, L, XL  is the supported controller  references.
Supported PLCs by size :
In bold, new controllers available in Unity Pro v11
 
Controllers family Small
(S)
Large
(L)
X Large
(XL)
MC80 (*) All models All models All models
Momentum All models All models All models
Modicon M 340 All models All models All models
Atrium   TSX PCI 57 204 TSX PCI 57 204
  TSX PCI 57 354 TSX PCI 57 354
Premium   TSX P 57 00 TSX P 57 00
  TSX P 57 10 TSX P 57 10
  TSX P 57 20 TSX P 57 20
  TSX H 57 20 TSX H 57 20
  TSX P 57 30 TSX P 57 30
  TSX P 57 40 TSX P 57 40
  TSX H 57 40 TSX H 57 40
    TSX P 57 50
    TSX P 57 60
M580 Standalone   BMEP 58 10••
BMEP 58 20••
BMEP 58 30••
 
BMEP 58 10••
BMEP 58 20••
BMEP 58 30••
BMEP 58 40••
BMEP 58 5040
BMEP 58 6040
M580 Hot-Standby   BMEH 58 2040
 
BMEH 58 2040
BMEH 58 4040
BMEH 58 6040
Quantum   CPU 311 10 CPU 311 10
  CPU 434 12 U CPU 434 12 U
  CPU 534 14 U CPU 534 14 U
    CPU 651 50
    CPU 651 60
    CPU 652 60
    CPU 670 60
        CPU 671 60
        CPU 672 60
        CPU 672 61
CPU 658 60
CPU 678 61
 
Note : Unity Pro 7.0 is also available in model XLS (XL Safety).
No update of XLS version is available with Unity Pro V11, nor V8.1
 
(*) MC80 controller family is delivered in project mode only.
It requires Update UnityPro_V11_HF_MC80 to be installed in addition to Unity Pro V11
 

What reference number should I use when upgrading from Vijeo Designer 5.1 Single user licence, to Vijeo Designer 6.1?

The reference number for Vijeo Designer 6.1 single user license is, VJDSNDTGSV61M

 

What version of Vijeo Designer is required for Vijeo Design'Air app support?

Issue
Vijeo Design'Air app support

Product Line
Vijeo Design'Air

Resolution
Vijeo Designer 6.1 SP2 must be installed in order to take advantage of the Vijeo Design'Air app.

How do the PDL 600 and 800 series product codes work?

As a general rule of thumb -
PDL items require PDL at the front of the code.
600 series item codes start with 6.
600 series switch codes start with 68.
The number of switches fitted in the plate is the 3rd number in the code, 681 = single 600 series switch, 682 = double 600 series switch
600 series socket codes start with 69.
The 3rd digit in a socket code indicates the type of socket, 691 = single vertical socket, 692 = double vertical socket, 694 = single horizontal socket, 695 = double horizontal socket.
Most codes require a colour code at the end, WH = white, BK = black.
eg. To order a black double vertical switched socket the complete code would be PDL692BK.
800 series (Modena) item codes start with 8 and follow the same format as above. (800 series items with Strato plates start with S8...)
eg. An 800 series Modena double switch in white = PDL882WH, a Strato double horizontal switched socket in black = PDLS895BK 
In both series metal cover plates are an extra option to be supplied separately, coded to fit the plate required, eg. 600 series single switch metal plate in Stainless Steel = PDL681MSS (M = Metal, BBZ = Brushed Bronze, PB = Polished Brass) Some plastic cover plates are available eg. PDL681CWH (C = Cover), PDL800PSCH (PS = Plastic Surround, CH = Champagne, there are 9 colour options in 800 series)
Strato brushed aluminium plates also need BK or WH to decide the trim colour, eg. PDLS800CBABK or PDLS800CBAWH (C = Cover , BA = Brushed Aluminium)
Module grids with covers are available in BK or WH, eg. PDL684VHWH (VH = vertical/horizontal since the grid is empty and module can be fitted either way), PDLS800GPSBK (GPS = Grid, Plate, & Surround).
Grids without covers included are only available in Modena 800 series, PDL800G (horizontal) or PDL800GV (vertical)
Refer pdl.co.nz for further details and options.

What are the dimensions for the 4FCC45-WE switchboard enclosure?

The dimensions for the 4FCC45-WE switchboard enclosure are 376mm (W) X 666 (H) X 70mm (D).
Wall opening dimensions are 631mm X 335mm
Some of the key features are:
  • Supplied with neutral and earth bars
  • 15 module Jetstrea m
  • No isolating switch
  • Ample wiring entries
  • Comprehensive range of legend stickers
  • Generous earth and split neutral bars are provided and located for ease of wiring. Main neutral termination for cable up to 35 sq mm


See Page 493 of the Trade Product Guide edition 92

For further information please see https://www.clipsal.com/Trade/Products/ProductDetail?catno=4FCC45

 

How to recover historical data on an ION meter?

With ION Setup you can configure Data Logging of the ION7550, as per page 161 of the attached user guide.

The logging setting can be adjusted via three areas Memory, Revenue Log, and EnergyDemand Log.

It further explains on page 170 viewing log for various options.

If you haven't setup Data Logging already in ION Setup the above option may not work.

 

Modbus Error 161 gets returned when trying to connect with 'ProWORX 32'

Goals and Symptoms

Modbus error 161 gets returned when trying to connect to a Modicon PLC with 'ProWORX 32'

Facts and Changes

'ProWORX 32', 'ProWORX NxT', 'Modsoft' and 'Concept'.

Causes and Fixes

'Modbus error 161' is defined as an invalid address or address range.

To resolve the problem:
1.) Check the address and communications parameter setup to ensure that they are correct.
2.) Check the Modbus cable to see if the DSR connection is asserted high.
3.) Try placing the PLC into Dim Awareness and use the 'PLC & I/IO Status' function in Modsoft to
view the status. (If this is succcessful, download to the PLC using the default parameters of
(Modbus address, RTU, 8, Even, 1, 9600).


Legacy KB System (APS) Data: RESL196777 V1.0, Originally authored by AlCh on 01/08/2009, Last Edited by AlCh on 01/08/2009
Related ranges: ProWORX

What are the part numbers of the IGBT's for the ATV66 drives?

Issue:
What are the part numbers of the IGBT's for the ATV66 drives?

Product Line:
All ATV66 drives

Environment:
IGBT's

Cause:
n/a

Resolution:
See the attached attachment

What are the part numbers for the Gate Driver Boards for ATV66 drives?

Issue:
What are the part numbers for the Gate Driver Boards for ATV66 drives?

Product Line:
ATV66 Drives

Environment:
Gate Driver Boards

Resolution:
See the attached spreadsheet

Does Active Pager Module (APM) 6 use html or plain text format when sending emails?

Active Pager Module (APM) 6.0 and 6.1 send emails as plain text.
PRODUCTS Affected
APM 6.0, APM 6.1


Legacy KB System (APS) Data: RESL199622 V1.0, Originally authored by MaTh on 08/14/2009, Last Edited by MaTh on 08/14/2009
Related ranges: SMS Add-on

What is the minimum version of SoMachine that will work with a XBTGC2330?

The minimum version of SoMachine that will work with a XBTGC2330 (XBTGC2330T and XBTGC2330U) is SoMachine version 3.1 with Vijeo Designer 6.1 SP2.1 installed. We recommend to use at least Vijeo Designer v6.1 with SP3.1 (instead of SP2.1)

Are the Wiggy testers NFPA70E certified?

Issue:
Are the Wiggy voltage testers NFPA70E certified?

Product Line:
Obsolete Square D voltage testers.

Environment:
Specification

Cause:
Code Certification

Resolution:
The NFPA70E is the Standard for Electrical Safety in the Workplace. This Standard does not actually provide for certification of individual pieces of equipment. This is a Standard, not a certification document. The Wiggy`s are UL/CSA/ANCE certified.

Update:  The Wiggy line of voltage testers is obsolete and no longer available, no replacement. Consider another manufacturer for this product.


CTA-ID : 2033348

What is the improvement/benefit of upgrading the EGX200/EGX400 firmware from 6.0 to 6.1?

Issue
What is the improvement/benefit of upgrading the EGX200/EGX400 firmware from 6.0 to 6.1?

Product Line
EGX200, EGX400

Cause
User would like to know improvements/benefits made in EGX200/EGX400 firmware from 6.0 to 6.1.

Environment 
Upgrading firmware on EGX200/EGX400 gateway 

Resolution
Review the improvements/benefits made in EGX200/EGX400 firmware from 6.0 to 6.1 below: 

EGX200
The version 6.1 firmware update includes better broadcast/multicast storm resiliency, auto negotiation improvements, serial communications support for Odd parity, and the ability to communicate with ModbusTCP/IP protocol over nonstandard MTU sized Ethernet networks.

EGX400
Upgrading the EGX400 to version 6.1 provides all the features of the EGX200 mentioned above plus data logging enhancements, increased support for the number of loadable device types (PLT files) from 32 to 64, SMTP client enhancements, and additional device type support for the ION7300. 

NOTE: Review KB FA212757 which provides step-by-step instruction on how to upgrade firmware on EGX200/400 gateway. 

Error when restoring or attaching SQL database from SQL 2012 to an earlier version of SQL server 2008

Issue 
A user receives an error when restoring or attaching SQL database from SQL 2012 to earlier version of SQL server

"The database cannot be opened because it is version 706. This server supports version 663 and earlier" 

Product Line 
SQL Server 2012 and SQL Server 2008 R2
StruxureWare Power Monitoring (SPM) 7.x 
Power Monitoring Expert (PME) 7.2.x and 8.x 

Environment 
Microsoft SQL Server Management

Cause 
SQL 2008 R2 cannot attach database files that were created from or attached to SQL 2012

Resolution
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*

 
Reason of the error message:
The database was created in/attached to SQL Server 2012 version. Now this database is being attached to SQL Server 2008 R2.


 
Error when restoring database:

 
Version 706 is a database file from SQL Server 2012
Version 663 is a database file from SQL Server 2008 R2

PME7.2.2 systems running SQL server 2008 R2 cannot attach database files that were created from SQL 2012.
Upgrading SQL server 2008 R2 to  SQL 2012 must be done if restoring or attaching a database from SQL2012 is required.

Which ports are used in SoMachine controllers?

Issue:
Which ports I should open in order to communicate with a SoMachine controller

Product Line:
SoMachine controllers

Resolution:
Depending on which protocol is supported by which PLC, this is a list of ports usually used:

- 502 (Modbus TCP) 
- 8080 
- 1105 and 1217 (SoMachine protocol) 
- 21 (FTP) 
- 161 (SNMP) 

Is the VW3A3720 Ethernet module for the ATV630 Process drive available?

Issue:
Is the VW3A3720 Ethernet module for the ATV630 Process drive available?

Product Line:
Altivar Process 630

Environment:
All 

Cause:
VW3A3720 availability 

Resolution:
Yes its available and your ATV630 Process drive must be firmware version 1.5 or above so you can use this option card. 

Does the ATV630 Process drive have embedded Ethernet TCP/IP and Ethernet IP?

Issue:
Wondering if the ATV630 Process drive have embedded Ethernet TCP/IP and Ethernet IP?

Product Line:
Altivar Process 630

Environment:
All 

Cause:
Altivar Process 630 Ethernet. 

Resolution:
No. The ATV630 only has embedded Modbus TCP/IP. A VW3A3720 would be needed to use Ethernet IP protocol.

How do I reset the run time on an ATV66 VFD?

Issue:
Reset run time

Product Line:
ATV66

Environment:
All models

Cause:
None

Resolution:
The run time could be reset by jumping pins 1 and 11 on connector 10. I told him to power off, install the jumper, power on and wait for the display to come on, then power off and remove the jumper.
 

What is the part number of DC bus assembly with capacitors for ATV66C23N4 and ATV66C31N4?

Issue:
What is the part number of DC bus assembly with capacitors for ATV66C23N4 and ATV66C31N4?

Product Line:
ATV66, Altivar 66

Environment:
ATV66C23N4 , ATV66C31N4

Cause:
Replacement capacitors needed.

Resolution:
The part number for the assembly with capacitors is VY1ADC608. Unfortunately, these parts are now obsolete.  Would need to replace the drive.

Where can I find the power board part numbers for all of the the ATV66 drives?

Issue:
Where can I find the power board part numbers for all of the the ATV66 drives?

Product Line:
Altivar ATV66

Environment:
All

Cause:
Needs to get a repalcement power board part number

Resolution:
See attachment

 

What does the "SL" in SL66 drive mean?

Issue:
Part number is a SL66

Product Line:
ATV66

Environment:
Enclosed product

Cause:
n/a

Resolution:
SL means "Skinless" The drive does not have side panels and was installed in our enclosed product or MCC. 
 

It is possible to use HMI as Remote Gateway for OPC Server access to connect PLCs on Remote side?

Until SoMachine V3.1 / VJD 6.1 it was possible to connect Remote PLC to an OPC Server by using the remote HMI as Gateway.

With VJD 6.2 SP 2.x this was not any more working, because of an issue inside the VJD runtime.
 
But in VJD 6.2 SP3 it is fixed and can be used again.


 

What is the ATV66 VW3A66206U replacement keypad part number?

Issue:
What is the ATV66 replacement keypad part number?

Product Line:
Altivar 66

Environment:
VFD Version 3.0 or greater

Cause:
Keypad needs to be replaced.

Resolution:
The drive MUST be version 3.0 or greater. Verify the drive control board version level before replacing the keypad. Ignore the version number of the keypad itself.
The part # for the keypad is VW3A66206U.
Update:  The VW3A66206U keypad is no longer available for sale and is obsolete with no direct replacement.

Video: How do I configure IO boards and points on a SCADAPack RTU and then test them with Series E Configurator software?


Issue: Need to use Series E Configurator software to configure the IO boards to communicate correctly with your SCADAPack RTU processor board. Need to use Series E Configurator software to configure system points, derived points and physical points on the IO boards correctly. Need to use Point Browser tool in Series E Configurator software to test reading from and writing to configured points.
Product Lines:
Series E Configurator
SCADAPack RTU
Environment:
Microsoft Windows XP, Windows Server 2003, Windows Vista, Windows Server 2008, Windows 7, Windows 8, or Windows 10, on 32-bit or 64-bit Operating System
Cause: N/A
Solution:
  1. Factory reset your RTU
  2. Start Series E Configurator,
  3. Use USB communication setting
  4. Read the RTU Configuration
  5. Open IO-> SCADAPack IO on the left-hand side of Series E Configurator window
  6. When you read the configuration of a factory reset rtu, the modules will not be automatically created
  7. Add a 6601 composite IO module if you are using a 535e RTU.
  8. If we’re using remote IO you’re going to need to change the address so that each address is unique so that you can target each IO board correctly.
  9. Now add another module. You’re going to add the 6201 IO board these are the IO on the actual processor of the 535e on the top rack. Now you can see that your physical IO has been created and it correlates to the physical points on the SCADAPack.
  10. Map the physical points to the dnp points for all physical IO. So just type in 1, 2, 3, 4, 5, 6, 7, 8 for DIs 1, 2, 3, 4, 5, 6, 7, 8 etc. so it’s easy to keep track of their point numbers.
  11. Write the configuration to the SCADAPack. Once the configuration is written open the Points pages and you can see that your physical points have been mapped to dnp points here.
  12. Double click a point to observe the properties.
  13. Create a point from the Points page. To do this you can either create a range or a single point. You must select your point type. For this point we're going to select system and point number 50005. This point correlates to the point the which represents the 6601 IO firmware version.
  14. Open your point browser and start creating some points to test: DIs 1 and 2 and the Dos and AIs from the 6601 module; the last DO from the 6201 module; and the system point you created.
  15. Select the read button and all your values will update.
  16. Make a comment. This is just a point description and this will come straight through to the point browser.
  17. Observe that point 50005 matches your IO firmware.
  18. Test your binary values by writing a 1 to some of them and checking if the corresponding led comes on. If it doesn’t, go to controller setting as and check the led power always on the box and write the configuration. Once it's written and you’ve confirmed the binary points were written to the SCADAPack you should see the led come on.

171CCC9x0x0 M1E Processor 984LL Exec. Upgrade to v.1.28

Release Notice

The purpose of this resolution is to inform Momentum M1E users that the 984LL Exec. has been upgraded to version 1.28 on Jan 4, 2008.

Goals and Symptoms

984LL Exec version 1.28 resolves the following issues:


  • 1) Fixes a problem in the M1E web page where the 'TCP Retry' counter would increment every time a TCP MSTR Function Block was activated.

    2) The PSH flag is no longer set in the SYN or FIN. Previous versions of the Exec would set the PSH flag in the SYN or FIN.

    3) The M1E will now respond to a second ARP request.

    4) Crash code 631 would occur under certain conditions

    5) Fixes an issue if two or more MSTRs are programmed in logic, randomly one of the MSTRs may stop operating (freeze) for up to 3-5 minutes before recovering on its own.

Facts and Changes

This resolution affects the following processors:
· 171CCC98030
· 171CCC96030
· 171CCC98020
· 171CCC96020

  • Note: It is recommended to power cycle the M1E immediately after downloading an Exec.

Causes and Fixes

Installing 984LL Exec. v.1.28 resolves the above mentioned issues.


Legacy KB System (APS) Data: RESL190558 V3.0, Originally authored by DaDz on 01/08/2008, Last Edited by DaDz on 04/11/2008
Related ranges: Modicon Momentum

What is the difference in ATV660 and ATV960 drives?

Issue:
What is the difference in ATV660 and ATV960 drives?
 
Product Line:
ATV660, ATV990
 
Environment:
Process Drive enclosures
 
Cause:
n/a
 
Resolution:
ATV630 is a product
ATV660 and ATV680 are drive systems
The same for ATV930/960/980

All ATV600 are dedicated to variable torque applications as pump and fan applications.
All ATV900 are dedicated to constant torque applications like cranes, conveyor belts, centrifuges, extruder...)

The difference between ATV660 and ATV960?
The internal power electronic is completely the same.
The control electronics including firmware is different.

ATV900 has also the possibility of braking units and speed feedback cards. (Not availalble for ATV600)

What impedance line reactors can be used with the ATV630 or 930 drives?

Issue: 
What impedance line reactors can be used with the ATV630 or 930 drives?
 
Product Line:   
Altivar 600
ATV630, ATV650
Altivar 900
ATV930, ATV950
 
Environment:
All
 
Resolution:
The internal DC chokes provide a impedance between about 2 and 3.5%, depending on the drive.
If higher total impedance is needed, then a line reactor can be added up to max 5% total impedance (built-in plus additional combined).