socket-switch-interlocked

Socket Switched Inter Locked

Catalogue Number: 56CVI540
socket-switch-interlocked
Retail
N/A
RRP (Inc. GST)
Colour Grey (GY)
  • Grey 1 PCE

Specifications

hide show
Range of product
Series 56
Product brand
Clipsal
Device application
power supply
Number of poles
5
Number of power socket outlets
1 protective cover
[In] rated current
40 A
[Ue] rated operational voltage
500 V AC
Material
PVC (polyvinyl chloride): housing
Depth
108 mm
Width
101 mm
Height
204 mm
Package 1 Weight
0.144 kg
Package 1 Height
108 mm
Package 1 width
101 mm
Package 1 Length
204 mm

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Product Environmental

  • Specifications

  • Corporate Marketing

Frequently Asked Questions

hide show

Can the 56CV520 be purchased in chemical grey?

Yes the part number is 56CV520-CG.
 

Does the 56CVI532 need to be in the off position for the plug to be removed?

Yes, the 56CVI532 does need to be off to either insert or remove the plug.

Some of the key features are:
  • 32 A thermal current
  • 5 round pins
  • 3 pole
  • Internal interlock switch

 

What is the PDL equivalent to the Clipsal 56CSC520

PDL56CR520

https://www.pdl.co.nz/product-details.aspx?rcat=products&catid=0&id=394

Is part no 56CSC520 available in Transparent?

No. Unfortunately, its only available in Orange.

What is the part number for a 3 pin 10amp switched outlet that has an interlock with the switch , so that the plug cannot be pulled out unless the isolator is switched OFF?

There is no interlock function for the 3 pin 10amp 56 series outlet. Customer would have to use 5 pin 10amp outlet and plug.
The part number for a 3 pin 10amp switched outlet that has an interlock with the switch , so that the plug cannot be pulled out unless the isolator is switched OFF is - 56CVI510 & 56P510
For further information , visit link below:-
https://www.clipsal.com/Trade/search-results?q=56CVI510
https://www.clipsal.com/Trade/search-results?q=56P510
User-added image
User-added image

What is the function of the interlock on 56CVI one peice models of 56 series switched socket outlet?

Mechanical interlock is an optional feature to ensure power disconnection before insertion or removal of the plug. Internal interlock facility is available on three phase, one piece cover  switched socket outlets.  add I to Catalogue Number e.g. 56CV410 becomes 56CVI410.

Is the 56CV532 available in white with RCD protection

Need to use 56CV532 + 56E4 + 56CB4 + RCCB

What is the switch mech for the PDL 56CV110

Replacement switch mech is PDL581/58YL

What is the rating on the Neutral for the PDL 56CV532

 The rating is 32A

What is the plug to suit a PDL 56CV516

Need to use a PDL 56P516 or PDL 56PA516

Is there a 56 series outlet to suit a 56P432 that restricts the plug from being removed when switched on?

Yes, use of the 56CVI432 series will restrict removal while the outlet is switched on as there is an interlocking pin to hold the plug in place.
 
Some of the key features are:
  • 32 A thermal current
  • Internal interlock switch
  • 4 round pins
  • 500V
  • IP66
  • 3 Pole
  • Vertical
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=56CVI432 


 

Is there a 6 or 7 pin option in the 56 series cord connectors?

No 56CR550 is the largest size we do with 5 Pins and a rating of 50A.
Show More