Specifications

hide show
Range of product
Series 56
Product brand
Clipsal
Device application
power supply
Number of poles
7
Number of modules
3
Number of power socket outlets
1 protective cover
[In] rated current
50 A
[Ue] rated operational voltage
500 V AC
Depth
45 mm
Width
101 mm
Height
198 mm
Package 1 Weight
0.001 kg
Package 1 Height
45 mm
Package 1 width
101 mm
Package 1 Length
198 mm

Frequently Asked Questions

hide show

What is the part number for the switch used in a 56C710?

The part number for the switch used in a 56C710 is 56SW410.

Some of the key features are:
  • 10 A thermal current
  • 2 module Model
  • 7 Round pins
  • 3 pole
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=56C710


 

How do I get a 56 Series Double outlet?

56E4 (4 Gang Base) + 56SO310LE (socket outlet) X2 + 56SW110LE (Switch) X2

What is the replacement for 56P310L, 56 series, IP66, 3 pin, 250V, 10A plug with 2 Flat Pins and round earth?

56P310SL is the alternate for 56P310L. 56P310SL is IP66, 250V 10A - 2 Flat Pins and round earth, conductor terminal [sq mm] - min: 0.75, max: 1.
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=56P310SL

Is it possible to swap a 56C315 for a 56C310 on the same base?

Yes, you can remove the 56C315 switch mechanism and socket outlet, and replace it with a 56C310LE, provided the power supply is 10 amp and not 15 amp it will be okay.

What is a daylight switch with Lux setting

A WDL10 and 56SS10WE

What are the part numbers to make up a 56 series , 5 pin 50amp switched outlet with RCD protection?

The part numbers to make up a 56 series , 5 pin 50amp switched outlet with RCD protection are - 56E4 , 56C550LE ,56CB4 & 4RC463/30

For further information , visit links below:-
https://www.clipsal.com/Trade/search-results?q=56E4
https://www.clipsal.com/Trade/search-results?q=56C550LE
https://www.clipsal.com/Trade/search-results?q=56CB4
https://www.clipsal.com/Trade/search-results?q=4RC463/30
User-added image
 

Can the 56SB13 be fitted to the 56E9 base?

The 56SB13LE can not be fitted to the standard 56E9 base. It can, however, be fitted to either the 56E8SB-GY or 56E9SB-GY.
These have had 2 pillars removed to allow placement of the din rail etc to allow fitment of the 56SB13LE to these bases.

Can I use a PDL 56SS10WE to switch MH lighting - will there be any issues

You need to use PDL 56SS10 with a relay or a Telemecanique K range contactor to switch the load

Can I use a PDL 56SS10WE to switch floodlights

 Yes - you need to use a contactor or a relay

Can I get a 56C310 with key lock switch?

What is the RCD in the 56C510RC RCD protected combination outlet?

The RCD in the 56C510RC RCD protected combination outlet is a 4RC463/30.
Some of the key features are:
  • Unique new white finish for a fresh modern look
  • Base module = 18 mm wide, compact standardised and consistent module dimensions
  • Lift-up terminals. Safer ‘no hot spot’ terminations and all cable strands are locked in
  • Cable automatically guided to the correct position: terminals with guard
  • Fast closure
  • The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety
  • Same housing as AC type MCBs. Uniformity in space requirements and installation
  • Superior, safe and reliable DC breaking per pole
  • Used with marine, telecommunications, solar power, emergency power, battery power
  • Excellent breaking capability for its compact size
  • Standard type
  • 75 mm modular spacing
  • Surge current protected to 250 A at 8/20 uS
  • Operating temperature: -5 to 40 deg C
  • Degree of pollution is 2
  • Rated Impulse withstand voltage is 6 kV
For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=4RC463/30

What is the part number for a 56 series 10amp switched inlet?

The part number for a 56 series 10amp switched inlet is - 56E2 , 56AI310LE & 56SW110LE