Do you still have the 521A threaded nipple?
No ,unfortunately this part is no longer available.
For further information please visit
https://www.clipsal.com/Trade
whats the difference between 891ma dn 891a
advised 891MA is socket module only and the 891A is fully assembled grid, plate, socket and switch
What are the outside dimensions of the FPSS121-CAT6?
The dimensions are 121mm (W) X 83mm (H) X 155mm (D).
Can the LUCA12BL be controlled with a PLC?
Issue:
The LUCA12BL is to be controlled directly with the output of a PLC.
Product Line:
Tesys U line
Environment:
LUB32+LUCA12BL
Cause:
PLC doing remote control of the motor starter.
Resolution:
Yes, if the output of the PLC is 24 V DC and can handle an inrush of 220mA . A reversing module will add 120mA to the inrush when it has to change the direction of the motor.
What is the Software Filter Time for TM2/TM3 Analog I/O Modules in Somachine Basic?
Software filter time parameter for TM2/TM3 analog input module is the time constant of the 1st order filter (or the time to reach 63% of the final value).
for example, for 4...20mA signal, it will take 20ms for the signal to change from 4mA to 12.6mA (20mA x 63%).
Can the RM35JA31MW monitor positive and negative currents?
Issue:
Cheching if Zelio relays can monitor negative currents.
Product line:
Relays and Timers
Environment:
Zelio Control and Measurement Relays
Cause:
Documentation shows on 4-20mA does not clarify postive or negative.
Resolution:
Yes, the RM35JA31MW can monitor +4 to +20mA or -4 to -20mA.