NEON LIGHTING ADAPTOR UNIT

C-Bus Neon Lighting Adaptor Unit

Catalogue Number: 5100NLA
NEON LIGHTING ADAPTOR UNIT
Retail
$261.9*
RRP (Inc. GST)

Specifications

hide show
Product brand
Clipsal

Frequently Asked Questions

hide show

What is used as the C-Bus to Bacnet Gateway

The 5500NAC or 5500SHAC can be used as Bacnet gateway depending on the number of Bacnet points which are required.
The 5500NAC has 500 Bacnet Points and the 5500SHAC has 50 Bacnet points.
Bacnet is normally used by Building Management systems.

What is the alternative for the C-bus network interface 5100CN2?

The alternative/ replacement part for the the 5100CN2 C-bus network interface is the 5500CN2 C-bus network interface.
The C-Bus Computer Network Interface (CNI) is a C-Bus system device designed to provide an isolated communications path between an Ethernet 10Base-T Network and a C-Bus Network. This allows high-speed control and monitoring of a C-Bus installation via the TCP/IP protocols used in computer networks and by the Internet.

The CNI is a nearly instantaneous connection to a C-Bus network. It provides a gateway between high-speed, high bandwidth Ethernet communication and the robust, timetested Clipsal C-Bus Automation System. System integrators and installers can program a C-Bus network remotely without the need for transporting a PC to the local C-Bus network and connecting via the serial port.


 


For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=5500CN2&c=2&ms=11&s=19&mg=7051  
 


 

 

Where to set Port numbers using NAC or SHAC

Access “Configuration” window on the web browser, select “System”, select “Services” which will allow you access to “HTTP server settings”, this is where your ports can be set.

How to control RS-232 enabled devices with C-Bus Network Automation Controller – 5500NAC (5500SHAC)?

A Configuration Guide exist on the Exchange Community, see the link below or the attachment.

How to control RS-232 enabled devices with C-Bus Network Automation Controller – 5500NAC



 

Why is my Conext CL showing an alarm code: 31 (AC Curr Snsr Flt Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 31 (AC Curr Snsr Flt Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
AC current sensor doesn’t measure the grid current accurately
Grid connection
Detection circuit malfunction

Resolution: 
Check AC connection on inverter

Why is my Conext CL showing an alarm code:2418 & 2419 (AC UV Slow Err & AC OV Slow Err Service Alarm)

Issue: 
Customer is calling to confirm alarm code:2418 & 2419 (AC UV slow err & AC OV slow err Service)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
AC voltage is below (Under Voltage) or above (Over Voltage) the set limits
AC Voltages are not according to the set country or custom setting

Resolution: 
Measure the voltage at the inverter AC connections and check if it is within the country or custom setting limits, adjust if necessary in accordance with utility.

Why is my Conext CL showing an alarm code:8000 (AC Internal Error Service Alarm)

Issue: 
Customer is calling to confirm alarm code:8000 (AC Internal Error Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
Grid current measured exceeds unit rating
DC bus voltage outside operational parameters
Internal AC bus voltage too high
Phase lock loop failure during inverting

Resolution: 
Reset unit by turn off both AC and DC
If problem persist replace the unit
 
 

Why is my Conext CL showing an alarm code: 9000 (DC Internal Error Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 9000 (DC Internal Error Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
PV current measured exceeds unit rating
Internal DC bus voltage too high
Difference between top or bottom DC bus voltage too high
Dc bus voltage too low
DC voltage sensor measurement failure

Resolution: 
Reset unit by turn off both AC and DC
If problem, persist replace the unit

Why is my Conext CL showing an alarm code: 32 & 33 - AC temp snsr flt & DC temp snsr flt ( AC and DC Temp Sensor Fault Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 32 & 33 ( AC temp snsr flt Service)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting
 
Cause:
Abnormal ambient temp
Cooling problem
Detection circuit malfunction

Resolution: 
Check fans, installation conditions, air inlet and outlet
Check Internal temperature displays in STATUS screen
Turn off and on AC breaker
If failure persists, replace the unit

Why is my Conext CL showing an alarm code: 10 - AC relay flt (AC Relay Fault: Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 10 (AC relay flt: Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext cL 25000E

Environment:  
On site troubleshooting

Cause:
AC output relay is either welded or opened  
Abnormal frequent disconnections from the grid that caused premature ageing of the relay

Resolution:  
If the failure persists, replace the inverter

Why is my Conext CL showing an alarm code: 712 & 713 (AC & DC Int Config Fit Service Alarm)

Issue: 
Customer is calling to confirm alarm codes: 712 & 713 (AC&DC Int Config Fit Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
Internal configuration on control processor is incorrect (firmware issue)

Resolution: 
Reset by turning off DC and AC 
Upgrade the firmware (2.6.4 or newer)
Ensure Bootloader (Control Boot) firmware is 2.02.03 or newer

Why is my Conext CL showing an alarm code: 4661 & 4662 ( PV1&PV2 SPD Service Alarm)

Issue: 
Customer is calling to confirm alarm codes: 4661 & 4662 ( PV1&PV2 SPD Service Alarm) 

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
PV1 or PV2 input SPD reached End of Life
SPD remote control wiring issue

Resolution: 
Check the SPD and replace EOL cartridges if required
Check SPD remote wiring 