c-bus cat. 5e cable, stranded

C-Bus LAN Cable, 305m, Category 5, UTP, LSZH, Stranded Conductor

Catalogue Number: 5005C305BST
c-bus cat. 5e cable, stranded
Retail
$414.08
RRP (Inc. GST)

Specifications

hide show
Range of product
C-Bus
Product brand
Clipsal
Communication network category
5
Cable stiffness
stranded class 2
Number of conductors
2
Cable shielding type
UTP
Length
305 m
Environmental characteristic
  • halogen free conforming to EN 50267-2-2
  • low smoke emission conforming to EN 61034-2
    • Package 1 Weight
      10.18 kg
      Package 1 Height
      37.2 mm
      Package 1 width
      38.2 mm
      Package 1 Length
      19.4 mm
      Sustainable offer status
      Green Premium product
      REACh free of SVHC
      Yes
      EU RoHS Directive
      Compliant
      Toxic heavy metal free
      Yes
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
      X
      Environmental Disclosure
      ENVPEP110210EN

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • CAD Files and Packs

      • Technical Data Catalogues

      • Technical Leaflet

      • Installation Instruction

      • Corporate Marketing

      Frequently Asked Questions

      hide show

      C-Bus - What is the Insulation rating of the C-Bus Cable?

      The C-Bus Cat5 cable working voltage has been tested, it's rated up to and inclucing 0.6/1 kV

      - See attached Certification for the C-Bus Cable.

      What is the part number for a Cat5 pink cable

      Code is 5005C305B

      What is the C-Bus cable part name?

      5005C305B for solid cable or 5005C305BST for stranded cable, this cable is mains rated to be safely used inside of an electrical switchboard
      Both versions of cable are specified as low smoke, zero halogen.

      Is the Cbus cable stranded or solid core?

      Solid core Cbus cable is stocked, code 5005C305B
      Stranded Cbus cable is indent, code 5005C305BST 

      What is the outer diameter of the pink CBus cable 5005C305B ?

      The Nominal Diameter of the pink sheath is 5.2mm  ?
      Please follow the links provided to the Data sheet and clipsal website 
      https://www2.clipsal.com/cis/__data/page/428/5005C305B%20data%20sheet2.pdf
      https://www.clipsal.com/Trade/search-results?q=5005c305b
      User-added image

      Can C-Bus cable be used underground?

      C-Bus cable (5005C305B) does not go underground.
      If customer requires cable for underground use, they can use any CAT 5 or CAT 6 JELLY FILLED cable

      Is the pink, C-Bus cable rated at 240 volts?

      Yes, The Pink outer sheath of the 5005C305B Cable is rated for 240 volts.
      However the internal conductors are not rated for 240 Volts