Quantcast

Clipsal MAX4 RCBO 2 module 2P 40 A C curve 30mA Type A-SI 6000A

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Sustainable offer status

Green Premium product

Range

MAX4

Product or component type

residual current breaker with overcurrent protection (RCBO)

Product brand

Clipsal

Physical

Environmental Disclosure

ENVPEP120401EN

Mercury free

Yes

REACh Regulation

Free of Substances of Very High Concern above the threshold

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

EU RoHS Directive

Compliant

RoHS exemption information

Yes

[In] rated current

40 A

[Ue] rated operational voltage

240 V AC

Standards

AS/NZS 61009

IP degree of protection

  • IP20
  • IP40
    • Ambient air temperature for operation

      -25-40 °C

      Others

      Halogen content performance

      Halogen free plastic parts product

      Package 1 Height

      38 mm

      Package 1 Length

      100 mm

      Package 1 Weight

      0.25 kg

      Package 1 width

      86 mm

      Poles description

      2P

      Number of modules

      2

      Curve code

      C

      Earth-leakage sensitivity

      30 mA

      Earth-leakage protection class

      type A

      Breaking capacity

      6000 A

      [Uimp] rated impulse withstand voltage

      4 kV

      Size

      81 x 36 x 77.5 mm conforming to DIN 43880
      Show all specifications

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Installation Instruction

      • Product Environmental

      • Operating Manuals

      • Certificates (MSDS)

      • Corporate Marketing

      Frequently Asked Questions

      hide show

      What would be the replacement for a 4RCD440A30 ?

      The replacement part would be a 4RC440SI30 which is super immune.

      For more information on this product range please visit the Clipsal website on the link provided
      https://www.clipsal.com/Trade/search-results?q=4rc440si30

      Does 4RCBM220/30 switch both active and neutral?

       4RCBM220/30 will switch both active and neutral.
      For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=4RCBM220/30

      What is the replacement for part number 4RCBM220G30?

      4RCBM220SI30 is the replacement for part number 4RCBM220G30. 4RCBM220SI30 is RCD/MCB, 2 module, 2 Pole, 20A, 30mA, 10KA, C-Curve SI-type, super immune,  A-type, surge current protected to 3000 A 8/20ms.
      For further information, please refer to the below link:
      https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RCBM220SI30
      User-added image
       

      What is the part number for replacement 40amp RCBO - 4RCBE140/30?

      The part number for replacement 40amp RCBO - 4RCBE140/30 is - A9D11840

      For further information , visit link below:-
      https://www.schneider-electric.com.au/en/search/+A9D11840
       

      Is there a 32A super immune RCBO?

      Yes the part number is a 4RCBM232SI30. this is commonly used with motors, pumps and generators as it is more immune to voltage spikes resulting in less nuisance tripping.
       

      Is the RCBM210/30 an RCD only ,or is it a combination RCD/MCB?

      The RCBM210/30 is a combination RCD/MCB.

      For further information , visit link below:-
      https://www.clipsal.com/Trade/search-results?q=RCBM210/30
      User-added image
      Show More