Quantcast

Clipsal MAX4 RCBO 2 module 2 module 2P 16 A C curve 30mA Type A-SI 10000A

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

MAX4

Product or component type

residual current breaker with overcurrent protection (RCBO)

Product brand

Clipsal

Sustainable offer status

Green Premium product

Physical

[In] rated current

16 A

[Ue] rated operational voltage

240 V AC

Standards

AS/NZS 61009

IP degree of protection

  • IP20
  • IP40
    • Ambient air temperature for operation

      -25-40 °C

      REACh Regulation

      Free of Substances of Very High Concern above the threshold

      EU RoHS Directive

      Compliant

      Mercury free

      Yes

      RoHS exemption information

      Yes

      China RoHS Regulation

      Product out of China RoHS scope. Substance declaration for your information

      Environmental Disclosure

      ENVPEP120401EN

      Others

      Poles description

      2P

      Number of modules

      2

      Curve code

      C

      Earth-leakage sensitivity

      30 mA

      Earth-leakage protection class

      type A

      Breaking capacity

      10000 A

      [Uimp] rated impulse withstand voltage

      4 kV

      Size

      81 x 36 x 77.5 mm conforming to DIN 43880

      Package 1 Weight

      227 g

      Package 1 Height

      83 mm

      Package 1 width

      100 mm

      Package 1 Length

      40 mm

      Halogen content performance

      Halogen free plastic parts product
      Show all specifications

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Installation Instruction

      • Product Environmental

      • Operating Manuals

      • Certificates (MSDS)

      • Corporate Marketing

      Frequently Asked Questions

      hide show

      What is part number for Resimax Busbar to suit RCBM216/30?

      RCBM216/30 can be used with RMXPH105,RMXPH112 or RMXPH124.

      Does 4RCBM220/30 switch both active and neutral?

       4RCBM220/30 will switch both active and neutral.
      For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=4RCBM220/30

      Is the RCBM216/30 fed from the top or the bottom?

      The RCBM216/30 line and load terminals may be connected to either the top or bottom for ease of installation.

      Some of the key features are:
      • Separate RCD trip flag for easy fault finding
      • New insulated openings for easy busbar installation
      • No need to cut the busbar providing safe and quick fit off
      • Top and bottom line load compatible for easy installation

      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=RCBM216/30

      What are the dimensions of the RCBM216/30?

      The dimensions of the RCBM216/30 are 44mm(D) X 81mm(H) X 36mm(W).
      Some of the key feaures are:
      • Seperate RCD trip flag for easy fault finding
      • New insulated openings for easy busbar installation
      • No need to cut the busbar providing safe and quick fit off
      • Top and bottom line load compatible for easy installation
      • Operating temperature: -5 to 40 deg C/li>
      • Mechanical combination Standard-type
      • 4 kV Rated impulse withstand voltage
      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=RCBM216/30
       

      What is the part number for the bus bar to suit the 4RCBE216/30S slim line RCBO ?

      The combination Busbars to suit the slim line RCBO's like RCBE216/30S are the RMXPH105 ( 5 pole) , RMXPH112 (12 pole)  OR RMX124  (24 pole)
      For more information on this product range please visit the Clipsal web site on the link provided.
      https://www.clipsal.com/products/detail?CatNo=RCBE216/30S&backto=/search?q=RCBE216/30S&tab-document-1=0&itemno=RCBE216/30S
      https://www.clipsal.com/search?q=RMXPH112

      Is there a replacement for 4RCBE116/30Q Quicklag 16A RCBO?

      Unfortunately not,  we do not have a replacement for 4RCBE116/30Q Quicklag 16A RCBO.
      Show More