Clipsal MAX4 RCBO 3P+N 10A C curve 30mA Type A 6000A 5 modules

Clipsal MAX4 RCBO 3P+N 10A C curve 30mA Type A 6000A 5 modules

Clipsal MAX4 RCBO 3P+N 10A C curve 30mA Type A 6000A 5 modules

Item Number: 4RCBE410/30

Retail
$367.02
RRP (Inc. GST)

Product Dimensions

Width icon

Width90 mm

Height icon

Height91 mm

Depth icon

Depth78.5 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Clipsal MAX4

Product or component type

residual current breaker with overcurrent protection (RCBO)

Product brand

Clipsal

Market segment

small commercial

Sustainable offer status

Green Premium product

Physical

[In] rated current

10 A

[Ue] rated operational voltage

380...415 V AC

Control type

toggle

Local signalling

ON, OFF, fault trip

Mounting mode

clip-on

Mounting support

DIN rail

Height

91 mm

Width

90 mm

Depth

78.5 mm

Net weight

498 g

Mechanical durability

20000 cycles

Electrical durability

20000 cycles

Connections - terminals

  • tunnel type terminal (top or bottom) - 0.33...10 mm² - flexible with ferrule
  • tunnel type terminal (top or bottom) - 0.33...10 mm² - flexible
  • tunnel type terminal (top or bottom) - 0.75...16 mm² - rigid
    • Wire stripping length

      15 mm for top or bottom connection

      Standards

      AS/NZS 61009

      IP degree of protection

    • IP20
    • IP40
      • Relative humidity

        90-90 % at 55-55 °C

        Ambient air temperature for operation

        -25-60 °C

        Ambient air temperature for storage

        -30-70 °C

        REACh Regulation

        Free of Substances of Very High Concern above the threshold

        EU RoHS Directive

        Compliant

        Mercury free

        Yes

        RoHS exemption information

        Yes

        China RoHS Regulation

        Product out of China RoHS scope. Substance declaration for your information

        Environmental Disclosure

        ENVPEP2003017

        Others

        Package 1 Height

        8.5 cm

        Package 1 Length

        9 cm

        Package 1 width

        7.5 cm

        Poles description

        3P + N

        Number of protected poles

        3

        Network type

        AC

        Curve code

        C

        Earth-leakage sensitivity

        30 mA

        Earth-leakage protection class

        type A

        Breaking capacity

        6 kA

        Network frequency

        50/60 Hz

        [Uimp] rated impulse withstand voltage

        4 kV

        Contact position indicator

        yes

        9 mm pitches

        10

        Locking options description

      • sealable
      • padlocking device
        • Tightening torque

          2-2 N.m top or bottom

          Earth-leakage protection

          integrated

          Pollution degree

          3

          Package 1 Weight

          500 g

          WEEE

          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
          Show all specifications

          Frequently Asked Questions

          hide show

          Replacement for the 4RCBE110/10

          This part has been replaced with 4RCBE210/30S

          What is the replacement for a 4RCBE110/30?

          The replacement for a 4RCBE110/30 is a A9D61810.
          Some of the key features are:
          • 2 Pole wide
          • 30mA
          • 10A
          • RCBO
          For further informatio please visit www.clipsal.com/Trade/Products/ProductDetail?catno=A9D61810

          What is the part number for replacement 40amp RCBO - 4RCBE140/30?

          The part number for replacement 40amp RCBO - 4RCBE140/30 is - A9D11840

          For further information , visit link below:-
          https://www.schneider-electric.com.au/en/search/+A9D11840
           

          What is the alternative to the 4RCBE210/30?

          Within the Schneider Electric range, the alternative for the 4RCBE210/30 is A9D11210

          Is there a replacement for 4RCBE116/30Q Quicklag 16A RCBO?

          Unfortunately not,  we do not have a replacement for 4RCBE116/30Q Quicklag 16A RCBO.

          What is the part code for a 10A 1phase Socket protected by 10mA RCD

          You can use 56SO310 +56CB4 + 56E3 + 4RCBE210/10
          Show More