Specifications

hide show
Range
MAX4
Product or component type
residual current breaker with overcurrent protection (RCBO)
Product brand
Clipsal
Poles description
1P + N
Number of modules
1
[In] rated current
25 A
Curve code
C
Earth-leakage sensitivity
30 mA
Earth-leakage protection class
type A
Breaking capacity
6000 A
[Ue] rated operational voltage
240 V AC
[Uimp] rated impulse withstand voltage
4 kV
Mounting support
DIN rail
Size
92.5 x 18 x 71.5 mm conforming to DIN 43880
Standards
AS/NZS 61009
IP degree of protection
  • IP20
  • IP40
    • Ambient air temperature for operation
      -5-40 °C
      Package 1 Weight
      146 g
      Package 1 Height
      75 mm
      Package 1 width
      98 mm
      Package 1 Length
      20 mm
      Sustainable offer status
      Green Premium product
      EU RoHS Directive
      Compliant
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
      Product out of China RoHS scope. Substance declaration for your information
      Environmental Disclosure
      ENVPEP100702EN_V1

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Product Environmental

      • Installation Instruction

      • Operating Manuals

      • Certificates (MSDS)

      • Corporate Marketing

      Frequently Asked Questions

      hide show

      What are the dimensions for the 4RCBE220/30S?

      The dimensions for the 4RCBE220/30S are - L93mm x D72mm x W18mm

      For further information , visit link below:-
      https://www.clipsal.com/Trade/search-results?q=4RCBE220/30S
       

      What does the yellow warning label adjacent the bottom neutral terminal indicate on a RCBE220/30S?

      Please refer to the attached literature for details.

      Is the part 4RCBE220/30S still available?

      Yes

      Replacement for the 4RCBE110/10

      This part has been replaced with 4RCBE210/30S

      Do you have a 10A RCBO double pole and 1 module wide?

      Yes, we do have a 10A RCBO double pole that is 1 module wide. The part number is RCBE210/30S.

      What is the part number for a 20A, 10mA RCB?

       The part number is 4RCBE220/10s

      What is the alternative to the 4RCBE210/30?

      Within the Schneider Electric range, the alternative for the 4RCBE210/30 is A9D11210

      is the 4RCBE210/10S and similar a Type 1 RCBO used for hospital applications ?

      In hospital applications, Type1 RCBO must be used.

      4RCBE210/10S is a type 1 RCBO. However it is different to the one used in medilec panels.

      Looking for a 10mA 20A RCBO.

       Part code is 4RCBE220/10

      Does 4RCBM220/30 switch both active and neutral?

       4RCBM220/30 will switch both active and neutral.
      For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=4RCBM220/30

      Do 4RCBE220/10S suit Schneider chassis?

      4RCBE216/10S does NOT fit onto a standard Chassis.
      reason is the two small terminal screws for active and neutral do not match  the tee off spacing 

      What is the part number for replacement 40amp RCBO - 4RCBE140/30?

      The part number for replacement 40amp RCBO - 4RCBE140/30 is - A9D11840

      For further information , visit link below:-
      https://www.schneider-electric.com.au/en/search/+A9D11840
       