Quantcast

Clipsal MAX4 RCBO SLIM 1PN 20A C curve 10 mAType A 6000A

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

MAX4

Product or component type

residual current breaker with overcurrent protection (RCBO)

Product brand

Clipsal

Device application

distribution

Sustainable offer status

Green Premium product

Physical

[In] rated current

20 A

[Ue] rated operational voltage

240 V AC

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

DIN rail

IP degree of protection

  • IP20 conforming to IEC 60529
  • IP40 (modular enclosure) conforming to IEC 60529
    • REACh Regulation

      Reference contains Substances of Very High Concern above the threshold

      EU RoHS Directive

      Compliant

      Mercury free

      Yes

      RoHS exemption information

      Yes

      China RoHS Regulation

      Product out of China RoHS scope. Substance declaration for your information

      Environmental Disclosure

      ENVPEP100702EN_V1

      Others

      Poles description

      1P + N

      Neutral position

      left

      Number of modules

      1

      Number of protected poles

      1

      Network type

      AC

      Trip unit technology

      thermal-magnetic

      Curve code

      C

      Earth-leakage sensitivity

      10 mA

      Earth-leakage protection class

      type A

      Breaking capacity

      6000 A

      Package 1 Weight

      0.13 kg

      Package 1 Height

      0.074 mm

      Package 1 width

      0.074 mm

      Package 1 Length

      0.098 mm
      Show all specifications

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Product Environmental

      • Installation Instruction

      • Operating Manuals

      • Certificates (MSDS)

      • Corporate Marketing

      Frequently Asked Questions

      hide show

      What is the part number for a 20A 10mA RCBO?

      The part number for a 20A 10mA RCBO is A9D10820 or  4RCBE220/10S
      A9D10820 will fit 
       Schneider chassis but cannot not be used for hospitals or body protected areas as it does not switch neutral.
      The Clipsal 4RCBE220/10S is suitable for hospitals but will not fit to Schneider chassis.
       
      A9D10820 Product picture
      A9D10820    iC60H - earth leakage circuit breaker
      1P + N - C curve - 20 A - 10 mA - 240 V
      4RCBE220/10S        SLIM CLIPSAL
      20A 10mA A-TYPE 6KA

      For more information see :
      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9D10820
      https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RCBE220/10S

      Do Clipsal have a 20a single module RCBE @ 10ma suited for hospital use ?

       
       
       
       
      Yes we do , In this case it would be the 4RCBE220/10S.
      To be approved for use in hospitals the RCBO must be approved as "Type 1" (ie: 10mA sensitivity, switch both Neutral and Active, and trip in <40ms)
      The below range of Slimline RCBO's are rated as Type 1 and therefore compatible


      For more information on Clipsal Circuit protection please visit the Clipsal web site on the provided link https://www.clipsal.com/Trade/search-results?q=circuit%20protection