Specifications

Design

Range

MAX4

Product or component type

residual current breaker with overcurrent protection (RCBO)

Product brand

Clipsal

Device application

distribution

Sustainable offer status

Green Premium product

Physical

[In] rated current

16 A

[Ue] rated operational voltage

240 V AC

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

DIN rail

IP degree of protection

  • IP20 conforming to IEC 60529
  • IP40 (modular enclosure) conforming to IEC 60529
    • REACh Regulation

      Reference contains Substances of Very High Concern above the threshold

      EU RoHS Directive

      Compliant

      Mercury free

      Yes

      RoHS exemption information

      Yes

      China RoHS Regulation

      Product out of China RoHS scope. Substance declaration for your information

      Environmental Disclosure

      ENVPEP100702EN_V1

      Others

      Package 1 Height

      0.018 mm

      Package 1 Length

      0.098 mm

      Package 1 width

      0.072 mm

      Poles description

      1P + N

      Neutral position

      left

      Number of modules

      1

      Number of protected poles

      1

      Network type

      AC

      Trip unit technology

      thermal-magnetic

      Curve code

      C

      Earth-leakage sensitivity

      10 mA

      Earth-leakage protection class

      type A

      Breaking capacity

      6000 A

      Package 1 Weight

      0.13 kg
      Show all specifications

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Product Environmental

      • Installation Instruction

      • Operating Manuals

      • Certificates (MSDS)

      • Corporate Marketing

      Frequently Asked Questions

      hide show

      Replacement for the 4RCBE110/10

      This part has been replaced with 4RCBE210/30S

      is the 4RCBE210/10S and similar a Type 1 RCBO used for hospital applications ?

      In hospital applications, Type1 RCBO must be used.

      4RCBE210/10S is a type 1 RCBO. However it is different to the one used in medilec panels.

      What is part number for 2pole 10ma 16amp MCB/RCD?

      Part no 4RCBE216/10

      What is the part number for the bus bar to suit the 4RCBE216/30S slim line RCBO ?

      The combination Busbars to suit the slim line RCBO's like RCBE216/30S are the RMXPH105 ( 5 pole) , RMXPH112 (12 pole)  OR RMX124  (24 pole)
      For more information on this product range please visit the Clipsal web site on the link provided.
      https://www.clipsal.com/products/detail?CatNo=RCBE216/30S&backto=/search?q=RCBE216/30S&tab-document-1=0&itemno=RCBE216/30S
      https://www.clipsal.com/search?q=RMXPH112

      Do 4RCBE220/10S suit Schneider chassis?

      4RCBE216/10S does NOT fit onto a standard Chassis.
      reason is the two small terminal screws for active and neutral do not match  the tee off spacing 

      Is there a replacement for 4RCBE116/30Q Quicklag 16A RCBO?

      Unfortunately not,  we do not have a replacement for 4RCBE116/30Q Quicklag 16A RCBO.