Quantcast

Max 4 Residual Current Devices, Non-Delayed, 415V, 80A, 30mA, 4 Pole, 4 Module

Max 4 Residual Current Devices, Non-Delayed, 415V, 80A, 30mA, 4 Pole, 4 Module

Max 4 Residual Current Devices, Non-Delayed, 415V, 80A, 30mA, 4 Pole, 4 Module

Item Number: 4RC480/30

Retail
$613.65
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

MAX4

Product or component type

residual current circuit breaker (RCCB)

Product brand

Clipsal

Sustainable offer status

Green Premium product

Physical

[In] rated current

80 A

[Ue] rated operational voltage

415 V AC

Mounting support

DIN rail

Standards

AS/NZS 61008

IP degree of protection

IP40

Ambient air temperature for operation

-5-40 °C

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure

ENVPEP110203EN

Others

Poles description

4P

Number of modules

4

Earth-leakage sensitivity

30 mA

Earth-leakage protection class

type AC

Rated conditional short-circuit current

6 kA

[Uimp] rated impulse withstand voltage

6 kV

Size

81 x 72 x 75 mm conforming to DIN 43880

Pollution degree

2

Package 1 Weight

393 g

Package 1 Height

85 mm

Package 1 width

95 mm

Package 1 Length

78 mm
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • Product Environmental

  • Installation Instruction

  • Operating Manuals

  • Certificates (MSDS)

  • Corporate Marketing

Frequently Asked Questions

hide show

What is the difference between the RCD440/30 and 4RC440/30?

The RCD440/30 id 6ka with a fuse and the 4RC440/30 is 10ka.

What is the replacement for 4EL40/2/30?

The replacement part name is 4RC240/30

Can part number 4RC425/30 be operated without neutral?

The 4RC425/30 can be operated without neutral through resistor.

Is there an alternative for part no 4EL40/4/30?

4RC440/30

What is the difference between 4RC440/30 and RCD440/30?

The 4RC440/30 is from the Clipsal Max 4 range and the RCD440/30 is from the Clipsal ResiMax range.

For more information, please refer to the link:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=RCD440/30 
https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RC440/30 



 

What would be the replacement for a 4RCD440A30 ?

The replacement part would be a 4RC440SI30 which is super immune.