RCD commercial 4P 4 modules; Max 4; Clipsal

Max 4 Residual Current Devices, Non-Delayed, 415V, 63A, 30Ma, 4 Pole, 4 Module

Catalogue Number: 4RC463/30
RCD commercial 4P 4 modules; Max 4; Clipsal
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
Series 4
Range
Clipsal - Series 4
Product or component type
residual current device
Product brand
Clipsal
Poles description
4P
Number of modules
4
[In] rated current
63 A
Earth-leakage sensitivity
30 mA
Earth-leakage protection class
class AC
[Ue] rated operational voltage
415 V AC
[Uimp] rated impulse withstand voltage
6 kV
Mounting support
DIN rail
Size
81 x 72 x 75 mm conforming to DIN 43880
Standards
AS/NZS 61008
IP degree of protection
IP40
Pollution degree
2
Ambient air temperature for operation
-5-40 °C
Sustainable offer status
Green Premium product
REACh Regulation
Free of Substances of Very High Concern above the threshold
EU RoHS Directive
Compliant
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
ENVPEP110203EN
Circularity Profile
N/A

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Product Environmental

  • Installation Instruction

  • Operating Manuals

  • Specifications

  • Certificates (MSDS)

  • Corporate Marketing

Frequently Asked Questions

hide show

What is replacement for part no 4EL63/4/30

Replacement part no is 4RC463/30

Can part number 4RC425/30 be operated without neutral?

The 4RC425/30 can be operated without neutral through resistor.

Is there an alternative for part no 4EL40/4/30?

4RC440/30

What is the replacement for 4EL40/2/30?

The replacement part name is 4RC240/30

Does the 4 pole 63A super immune 4RC463SI30 RCD have a kA rating?

No as it doesnt deal with over current fault protecttion.

 

What is the difference between the RCD440/30 and 4RC440/30?

The RCD440/30 id 6ka with a fuse and the 4RC440/30 is 10ka.

What is the difference between 4RC440/30 and RCD440/30?

The 4RC440/30 is from the Clipsal Max 4 range and the RCD440/30 is from the Clipsal ResiMax range.

For more information, please refer to the link:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=RCD440/30 
https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RC440/30 



 

What is the part number for the RCD in the 56SC532RC?

The part number for the RCD in the 56SC532RC is a 4RC463/32.

What is the part number of the replacement RCD to suit 56SC520RC?

4RC425/30 can be used as a replacement RCD for 56SC520RC. For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RC425/30

What is replacement for part number 4EL25/4/30?

Part no 4EL25/4/30 has been replaced with 4RC425/30.

What is the replacement for a 4EL40/4/30

Replacement for the discontinued 4EL40/4/30 is the 4RC440/30.

For more information on our Circuit protection range please go to the Clipsal web site on the link supplied https://www.clipsal.com/Trade/search-results?q=4RC440/30

What is the RCD used in the 32A 3 phase outlet with RCD combination 56SC532RC-GY?

The RCD used in the 32A 3 phase outlet with RCD combination 56SC532RC-GY is the 4RC463/30.
Some of its key features are:
  • Unique new white finish for a fresh modern look
  • Base module = 18 mm wide, compact standardised and consistent module dimensions
  • Lift-up terminals. Safer ‘no hot spot’ terminations and all cable strands are locked in
  • Cable automatically guided to the correct position: terminals with guard
  • Fast closure
  • The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety
  • Same housing as AC type MCBs. Uniformity in space requirements and installation
  • Superior, safe and reliable DC breaking per pole
  • Used with marine, telecommunications, solar power, emergency power, battery power
  • Excellent breaking capability for its compact size
  • Standard type
  • 75 mm modular spacing
  • Surge current protected to 250 A at 8/20 uS
  • Operating temperature: -5 to 40 deg C
  • Degree of pollution is 2
  • Rated Impulse withstand voltage is 6 kV
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RC463/30


 

What is the part number for a 4 pole 63amp RCD unit?

The part number for a 4 pole 63amp RCD unit is - 4RC463/30

For further information , visit link below:-
https://www.clipsal.com/Trade/search-results?q=4RC463/30
 

What is the closest alternative to a 4RC425A30?

The closest alternative to a 4RC425A30 is a 4RC425SI30.
Some of the key features are:
  • Unique new white finish for a fresh modern look
  • Base module = 18 mm wide, compact standardised and consistent module dimensions
  • Lift-up terminals. Safer ‘no hot spot’ terminations and all cable strands are locked in
  • Cable automatically guided to the correct position: terminals with guard
  • Fast closure
  • The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety
  • Same housing as AC type MCBs. Uniformity in space requirements and installation
  • Superior, safe and reliable DC breaking per pole
  • Used with marine, telecommunications, solar power, emergency power, battery power
  • Excellent breaking capability for its compact size
  • Super immune type
  • 75 mm modular spacing
  • Operating temperature: -5 to 40 deg C
  • Degree of pollution is 2
  • Rated Impulse withstand voltage is 6 kV
For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=4RC425SI30






 

What would be the replacement for a 4RCD440A30 ?

The replacement part would be a 4RC440SI30 which is super immune.

For more information on this product range please visit the Clipsal website on the link provided
https://www.clipsal.com/Trade/search-results?q=4rc440si30

What are the features for the 4RC440SI30?

Some of the key features are:
  • Unique new white finish for a fresh modern look
  • Base module = 18 mm wide, compact standardised and consistent module dimensions
  • Lift-up terminals. Safer ‘no hot spot’ terminations and all cable strands are locked in
  • Cable automatically guided to the correct position: terminals with guard
  • Fast closure
  • The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety
  • Same housing as AC type MCBs. Uniformity in space requirements and installation
  • Superior, safe and reliable DC breaking per pole
  • Used with marine, telecommunications, solar power, emergency power, battery power
  • Excellent breaking capability for its compact size
  • Super immune type
  • 75 mm modular spacing
  • Operating temperature: -5 to 40 deg C
  • Degree of pollution is 2
  • Rated Impulse withstand voltage is 6 kV
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RC440SI30
 

 

What are the part numbers to make up a 56 series , 5 pin 50amp switched outlet with RCD protection?

The part numbers to make up a 56 series , 5 pin 50amp switched outlet with RCD protection are - 56E4 , 56C550LE ,56CB4 & 4RC463/30

For further information , visit links below:-
https://www.clipsal.com/Trade/search-results?q=56E4
https://www.clipsal.com/Trade/search-results?q=56C550LE
https://www.clipsal.com/Trade/search-results?q=56CB4
https://www.clipsal.com/Trade/search-results?q=4RC463/30
User-added image
 

What is the replacement for a 4RC440G30?

The alternative is a 4RC440SI30

What is the alternate to part number 4EL25/2/30, 25A , 30mA, 2 module RCD?

4RC225/30 is an alternate for 4EL25/2/30, 25A , 30mA, 2 module RCD.

Key Features

  • Unique new white finish for a fresh modern look
  • Base module = 18 mm wide, compact standardised and consistent module dimensions
  • Lift-up terminals. Safer ‘no hot spot’ terminations and all cable strands are locked in
  • Cable automatically guided to the correct position: terminals with guard
  • Fast closure
  • The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety
  • Same housing as AC type MCBs. Uniformity in space requirements and installation
  • Superior, safe and reliable DC breaking per pole
  • Used with marine, telecommunications, solar power, emergency power, battery power
  • Excellent breaking capability for its compact size
  • Standard type
  • 75 mm modular spacing
  • Surge current protected to 250 A at 8/20 uS
  • Operating temperature: -5 to 40 deg C
  • Degree of pollution is 2
  • Rated Impulse withstand voltage is 6 kV

https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RC225/30

What is the part number for a RCD 40A?

part number is RCD440/30

What are the dimensions on the RCD440/30 RCD 40A?

The overall dimensions are 81mm (H) X 72mm (W) X 75mm (D)

 

User-added image

How do you wire an RCD RCD440/30 with no neutral?

You need a 2200Ω resistor going from the outgoing neutralto the outgoing white phase. be sure there in no cable in the ingoing neutral terminal as that would create a dead short.

This Task should only ever be performed by a licenced electrician.

User-added image

 

What is the RCD used in the 56 series?

The RCD used in the 56 series is the 4RC463/30.
For further information, visit the link below:-​
https://updates.clipsal.com/ClipsalOnline/Files/Brochures/I0000097.pdf
 

Do 4CB series circuit breakers have different color toggles?

No,previous models had different color toggles for different current ratings but unfortunately current models do not.
For further information please visit the following link:
https://www.clipsal.com/trade/search-results?q=circuit

Is there a suitable Shunt trip available to suit the clipsal circuit breaker 4CB363/10

Yes, you can get a shunt trip 24VDC to suit a miniature circuit breaker 4CB363/10.
The part number is A9N26948. 
 
For further information please visit
https://www.clipsal.com/Trade/Products/ProductDetail?catno=A9N26948