RCD commercial 4P 4 modules; Max 4; Clipsal
rcd 4mod 4p 40a 30ma si type
RCD commercial 4P 4 modules; Max 4; Clipsal
rcd 4mod 4p 40a 30ma si type

Max 4 Combination Residual Current Device, 2 Module, 2 Phase, 40A, 30mA, SI Type

Catalogue Number: 4RC440SI30
RCD commercial 4P 4 modules; Max 4; Clipsal
rcd 4mod 4p 40a 30ma si type
RCD commercial 4P 4 modules; Max 4; Clipsal
rcd 4mod 4p 40a 30ma si type
Retail
$570.54
RRP (Inc. GST)

Specifications

hide show
Range
MAX4
Product or component type
residual current circuit breaker (RCCB)
Product brand
Clipsal
Poles description
4P
Number of modules
4
[In] rated current
40 A
Earth-leakage sensitivity
30 mA
Earth-leakage protection class
type A-SI
[Ue] rated operational voltage
415 V AC
[Uimp] rated impulse withstand voltage
6 kV
Mounting support
DIN rail
Size
81 x 72 x 75 mm conforming to DIN 43880
Standards
AS/NZS 61008
IP degree of protection
IP40
Pollution degree
2
Ambient air temperature for operation
-5-40 °C
Package 1 Weight
363.5 g
Package 1 Height
85 mm
Package 1 width
92 mm
Package 1 Length
77 mm
Sustainable offer status
Green Premium product
EU RoHS Directive
Compliant
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
ENVPEP110203EN

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • Product Environmental

  • Installation Instruction

  • Operating Manuals

  • Certificates (MSDS)

  • Corporate Marketing

Frequently Asked Questions

hide show

What would be the replacement for a 4RCD440A30 ?

The replacement part would be a 4RC440SI30 which is super immune.

For more information on this product range please visit the Clipsal website on the link provided
https://www.clipsal.com/Trade/search-results?q=4rc440si30

What are the features for the 4RC440SI30?

Some of the key features are:
  • Unique new white finish for a fresh modern look
  • Base module = 18 mm wide, compact standardised and consistent module dimensions
  • Lift-up terminals. Safer ‘no hot spot’ terminations and all cable strands are locked in
  • Cable automatically guided to the correct position: terminals with guard
  • Fast closure
  • The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety
  • Same housing as AC type MCBs. Uniformity in space requirements and installation
  • Superior, safe and reliable DC breaking per pole
  • Used with marine, telecommunications, solar power, emergency power, battery power
  • Excellent breaking capability for its compact size
  • Super immune type
  • 75 mm modular spacing
  • Operating temperature: -5 to 40 deg C
  • Degree of pollution is 2
  • Rated Impulse withstand voltage is 6 kV
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RC440SI30
 

 

What is the difference between the RCD440/30 and 4RC440/30?

The RCD440/30 id 6ka with a fuse and the 4RC440/30 is 10ka.

Is there an alternative for part no 4EL40/4/30?

4RC440/30

Does the 4 pole 63A super immune 4RC463SI30 RCD have a kA rating?

No as it doesnt deal with over current fault protecttion.

 

What is the replacement for 4EL40/2/30?

The replacement part name is 4RC240/30

What is the replacement for a 4RC440G30?

The alternative is a 4RC440SI30

What is replacement part for 4RC440G100?

The replacement part is a 4RC440SIS300

for more information on this part please refer to https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RC440SIS300

What is the difference between 4RC440/30 and RCD440/30?

The 4RC440/30 is from the Clipsal Max 4 range and the RCD440/30 is from the Clipsal ResiMax range.

For more information, please refer to the link:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=RCD440/30 
https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RC440/30 



 

What is the replacement for a 4EL40/4/30

Replacement for the discontinued 4EL40/4/30 is the 4RC440/30.

For more information on our Circuit protection range please go to the Clipsal web site on the link supplied https://www.clipsal.com/Trade/search-results?q=4RC440/30

What is the closest alternative to a 4RC425A30?

The closest alternative to a 4RC425A30 is a 4RC425SI30.
Some of the key features are:
  • Unique new white finish for a fresh modern look
  • Base module = 18 mm wide, compact standardised and consistent module dimensions
  • Lift-up terminals. Safer ‘no hot spot’ terminations and all cable strands are locked in
  • Cable automatically guided to the correct position: terminals with guard
  • Fast closure
  • The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety
  • Same housing as AC type MCBs. Uniformity in space requirements and installation
  • Superior, safe and reliable DC breaking per pole
  • Used with marine, telecommunications, solar power, emergency power, battery power
  • Excellent breaking capability for its compact size
  • Super immune type
  • 75 mm modular spacing
  • Operating temperature: -5 to 40 deg C
  • Degree of pollution is 2
  • Rated Impulse withstand voltage is 6 kV
For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=4RC425SI30






 

Can part number 4RC425/30 be operated without neutral?

The 4RC425/30 can be operated without neutral through resistor.
Show More