Frequently Asked Questions

hide show

Enabling NLD function for a ATV61 drive

Issue: Enabling NLD function for a ATV61 drive

Product Line: ATV61

Environment: ALL ATV61 Drives

Cause:  Needs the NLD feature  for the ATV61 drive?

Resolution: The ATV61 has this feature in Menu 1.4 , under the Motor Control Type, select energy Savings ( NLD). The NOLD (no load) function: Reduces the voltage to the motor when selected for variable torque loads. A constant volts/Hz ratio is maintained during acceleration. The output voltage will then automatically adjust to meet the torque requirement of the load

What is the part number for the open close auxiliary to suit Acti 9 iLD RCCBs?

The part number for the open close auxiliary to suit Acti 9 iLD RCCBs is - A9A26924

https://www.schneider-electric.com.au/en/search/a9a26924



 

Can you get a cover only for a SC2025XA outlet?

Yes, however it only made as a specials item.

For further information please visit https://www.clipsal.com/Trade/search-results?q=sc2025cover

 

Is there a mounting block that suits the 40?

Yes, there is a mounting block for the 40. The part number is 447.

Some of the key features are:
  • Moulded mounting blocks
  • With metal inserts
  • 3 mounting screw positions
  • suits 40, 40D and switches with 115x48 mm flush plates and 98 mm mounting centres

For further information please visithttps://www.clipsal.com/Trade/Products/ProductDetail?catno=447

 

What is SSF code on the ATV320 drives?

Issue:
Altivar 320 drive is showing SSF and the motor will not run. 

Product line:
Altivar 320, Altivar Machine

Environment:
All model numbers, all serial numbers

Cause:
Torque Limitation

Resolution:
SSF means the drive has reach the Torque Limit fault setting.  This parameter is not enabled by default on the drive. 
To disable go to CONF > FULL > FLT > TLD > SSD and change the setting to 'no'.

Compatible I/O units for VAMP 221

Issue
User needs to know which I/O units are compatible with VAMP 221

Product Line
VAMP 221

Environment
I/O units

Resolution
The following I/O units are compatible with VAMP 221. Details for each unit are provided below.

  • VAM 12L accommodates up 10 arc APS_SENSORS, 3 APS_SENSORS have dedicated trip outputs
  • VAM 12LD accommodates up 10 arc APS_SENSORS, 3 APS_SENSORS have dedicated trip outputs
  • VAM 10L accommodates up 10 arc APS_SENSORS
  • VAM 10LD accommodates up 10 arc APS_SENSORS
  • VAM 3L accommodates up to 3 fiber loops
  • VAM 3LX accommodates up to 3 fiber loops with sensitivity adjustment
  • VAM 4C accommodates up to 3 current transformers
  • VAM 4CD accommodates up to 3 current transformers

Is old style A25A still available?

No. Part number A25A is no longer available in Old style.

Does the old Auxiliary contact of old contactor suit the new LC1D contactors?

Old Auxiliary contact for contactors won't go with new contactors but new auxiliary contacts will go with old contactos.

What replacement parts for the 230DRAVL combine meter/ switchboard are avaliable?

For a list of replacement parts see table below:
 
Description Part Number
Bracket only for temporary power service pole (excludes pipe).
Note: a pipe and bracket are required for temporary power service.
230PBV
Spare U-bolt and hex nuts for 230PBV 230UB
Spare doors to suit 230DRAVL 230DRAVAD
Spare neutral and earth bar assembly SP-6500138
Sliding bracket for temporary power leads SP-6330135

For further information please visit https://www.clipsal.com/Trade/search-results?q=230DRAV
or see PDF attached.
 

 

How should I care and maintain my Electrical accessories?

Cleaning and maintenance is an essential part of being a home owner. Maintenance of Switches and powerpoints is really simple, you just wipe them down with a damp cloth to remove any marks or finger prints. Chemical cleaners should never be used on these products and don't ever spray water directly on to them. If you notice any damaged to a switch or outlet have an electrician replace it for you.

What is the replacement for the old Video distribution Unit?

The alternative for the old Video distribution is a 3105VDU38IR.
 

Can the LED kits for the 56 Series be mounted to the old range

No, there is no support shaft on the old products
Show More