mcb 2module 2pole 16a 10ka
MCB commercial  2P 2 modules; Max 4; Clipsal
mcb 2module 2pole 16a 10ka
MCB commercial  2P 2 modules; Max 4; Clipsal

Max 4 Miniature Circuit Breakers, 2 Pole, 2 Modules, 36Mm, 415V, 16A, 10Ka

Catalogue Number: 4CB216/10
mcb 2module 2pole 16a 10ka
MCB commercial  2P 2 modules; Max 4; Clipsal
mcb 2module 2pole 16a 10ka
MCB commercial  2P 2 modules; Max 4; Clipsal
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Product brand
Clipsal
Curve code
C
Number of poles
2
[In] rated current
16 A
Number of modules
2
[Ue] rated operational voltage
415 V
Breaking capacity
10 kA conforming to EN 60898
Network type
AC
Network frequency
50/60 Hz
[Ui] rated insulation voltage
500 V
Mechanical durability
20000 cycles
Electrical durability
20000 cycles
Connections - terminals
  • screw terminal for 1 cable(s) 0.75-16 mm² rigid
  • screw terminal for 1 cable(s) 0.33-10 mm² flexible
  • screw terminal for 1 cable(s) 0.33-10 mm² flexible with ferrule
    • Wire stripping length
      13 mm
      Tightening torque
      2 N.m
      IP degree of protection
    • IP20 conforming to IEC 60529
    • IP40 (modular enclosure) conforming to IEC 60529
      • Ambient air temperature for operation
        -25-70 °C
        Ambient air temperature for storage
        -40-70 °C
        Standards
        AS/NZS 60898
        Tropicalisation
        2 conforming to IEC 60068-1
        Relative humidity
        95-95 % at 55-55 °C
        Height
        81 mm
        Width
        36 mm
        Depth
        78.5 mm
        Net weight
        215 g
        Sustainable offer status
        Green Premium product
        REACh Regulation
        Free of Substances of Very High Concern above the threshold
        EU RoHS Directive
        Compliant
        Mercury free
        Yes
        RoHS exemption information
        Yes
        China RoHS Regulation
        Product out of China RoHS scope. Substance declaration for your information
        Environmental Disclosure
        ENVPEP1304004

        Frequently Asked Questions

        hide show

        What is part number for 2pole 10ma 16amp MCB/RCD?

        Part no 4RCBE216/10

        What is the cable size to suit 4CB3100/10?

        The part number 4CB3100/10 will accommodate up to 50mm2 normal cable and up to 35mm2 flexible cable.

        What is part number for Resimax Busbar to suit RCBM216/30?

        RCBM216/30 can be used with RMXPH105,RMXPH112 or RMXPH124.

        What size cables fit into the 4CB3125/10?

        If the cable is Rigid/ Semi Rigid the 4CB3125/10 breaker will take a cable from 1mm²- 50mm².

        OR

        If the cable is Flexible or Ferrule the 4CB3125/10 breaker will take a cable from 1.5mm²- 35mm².

        Is there a lock-off to suit the 4CB3100/10?

        Yes, the Schneider MGN26380 will suit the Clipsal Max 4 Range.

        What is the part code for a 10A 1phase Socket protected by 10mA RCD

        You can use 56SO310 +56CB4 + 56E3 + 4RCBE210/10

        Are the RCBM series of RCBOs double pole isolating?

        Yes they are.

        Can 4CB220/6DC, 6KA C curve DC breaker be used for AC applications?

        4CB220/6DC is a dedicated D.C, polarized circuit breaker and cannot be used for alternating currents (A.C.) or A.C. application.
        For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=4CB220/6DC
        User-added image
        Other references: 4CB206/6DC , 4CB210/6DC , 4CB216/6DC , 4CB225/6DC , 4CB232/6DC , 4CB240/6DC

         

        What is the replacement for a 4EBE216/10?

        The replacement for a 4EBE216/10 is a 4RCBE216/10.
        Some of the key features are:
        • Unique new white finish for a fresh modern look
        • Base module = 18 mm wide, compact standardised and consistent module dimensions
        • Lift-up terminals. Safer ‘no hot spot’ terminations and all cable strands are locked in
        • Cable automatically guided to the correct position: terminals with guard
        • Fast closure
        • The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety
        • Same housing as AC type MCBs. Uniformity in space requirements and installation
        • Superior, safe and reliable DC breaking per pole
        • Used with marine, telecommunications, solar power, emergency power, battery power
        • Excellent breaking capability for its compact size
        • 36mm Modular Spacing
        • Surge current protected to 250 A at 8/20 uS
        • Operating temperature: -5 to 40 deg C
        • 2 degree of pollution
        • Rated Impulse withstand Voltage is 4kV
        • 40 ms Trip times
        • Standard type
        • 1 phase
        For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=4RCBE216/10

         

        Is the RCBM216/30 fed from the top or the bottom?

        The RCBM216/30 line and load terminals may be connected to either the top or bottom for ease of installation.

        Some of the key features are:
        • Separate RCD trip flag for easy fault finding
        • New insulated openings for easy busbar installation
        • No need to cut the busbar providing safe and quick fit off
        • Top and bottom line load compatible for easy installation

        For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=RCBM216/30

        What is the part number for the RCD that goes into 485P4CB30/10

        The part numbers are the 4EBE210/30 and 4EBE210/10 - these are no longer available to purchase but are still being used within the 485 range of portable outlets.
        They are not available as spare parts. The 485 series is currently undergoing a redesign to move away from these parts but is not yet complete. This redesign will use a standard part again.

        What is the replacement for a 4EBE216/30?

        The replacement for a 4EBE216/30 is a RCBM216/30.
        Some of the key features are:
        • Separate RCD trip flag for easy fault finding
        • New insulated openings for easy busbar installation
        • No need to cut the busbar providing safe and quick fit off
        • Top and bottom line load compatible for easy installation
        • Operating temperature: -5 to 40 deg C/li>
        • Mechanical combination Standard-type
        • 4 kV Rated impulse withstand voltage
        For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=RCBM216/30